PRE-INSTALLATION INFORMATION
CLEARANCES AND HEIGHT REQUIREMENTS
Ensure that minimum clearances shown in
Figures 4 and
5
are maintained. Left and right clearances are determined
when facing the front of the firebox.
Follow these instructions carefully to ensure safe instal-
lation. Failure to follow these requirements may create a
fire hazard.
Sidewall Clearances
— The clearance from the inside of
the appliance to any combustible adjacent wall should not
be less than 6".
Figure 4
Ceiling Clearance
— The ceiling or any other combustible
material must be at least 36" from the firebox opening.
Figure 4
Back Wall Clearance
— The appliance may be placed
against a combustible back wall.
W
ARNING
The dimensions shown in Figures 4 and
5 are minimum clearances to maintain
when installing this heater. Left and right
clearances are determined when facing the
front of the heater.
Follow these instructions carefully to
ensure safe installation. Failure to follow
instructions exactly can create a fire
hazard.
Floor Clearance
— The fireplace may be installed directly
on a combustible floor or a raised platform of an appropriate
height. Do not place fireplace on carpeting, vinyl, tile or
other soft floor coverings. It may, however, be placed on flat
wood, plywood, particle board or other hard surfaces. Be
sure fireplace rests on a solid continuous floor or platform
with appropriate framing for support so that no cold air can
enter from under the firebox. See note below regarding
floor installation with wide contemporary faces.
Mantel clearances
— Must meet the clearance require-
ments detailed in
Figures 4 and 5.
NOTE: When installing at floor level and using the wide
contemporary face, the fireplace must be raised up a
minimum of 3/4" to allow clearance for flooring material.
36
"
Minimum
From Opening
12
"
Max.
Depth
2
1
/
2
"
Max
Depth
18
"
Min.
From Opening
28
"
Min.
From Opening
6
"
Min.
FP3006
mantel clearances
Figure 4 –
Sidewall and Ceiling Clearances
FP3006
Figure 5 –
Mantel Clearances
23"
28"
18"
12"
6"
2
1
/
2
"
FP3007
mantel clearances
Top of Fireplace
Opening
FP3007
SIDE VIEW
Wall
Insulation
Board
Stud
Standoff
6"
5"
3"
4
¹⁄₂
"
45°
1"
3
¹⁄₂
"
FP3008
mantel leg
1
¹⁄₂
"
2
¹⁄₂
"
Fireplace
Opening
FP3008
TOP VIEW