A.  Firebox Certification

NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE.  

This appliance is tested and approved as either supplemen

-

tal room heat or as a decorative appliance.  It should not be 

factored as primary heat in residential heating calculations.

NOTICE: 

This installation must conform with local codes. 

In the absence of local codes you must comply with the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54.

This product is listed to ANSI standards for “Ventless Gas 

Firebox  Enclosures  for  Gas-Fired  Unvented  Gas  Log 

Type Room Heaters".

MODELS:

 ACUF32-BD, ACUF32-GD

 

   ACUF36-BD, ACUF36-GD

 

   ACUF42-BD, ACUF42-GD

LABORATORY:  

Underwriters Laboratories, Inc. (UL)

TYPE:  

Ventless Firebox Enclosures for Gas-Fired 

Unvented Gas Log Type Room Heaters

STANDARD:

 CSA/ANSI-Z21.91:20

B.  BTU Specifications

       WARNING: This product and the 

fuels used to operate this product (liquid 

propane or natural gas), and the products 

of combustion of such fuels, can expose 

you to chemicals including benzene, which 

is known to the State of California to cause 

cancer and reproductive harm. For more 

information go to: www.P65Warnings.

ca.gov.

This  product  is  for  use  ONLY  with  a  listed  decorative 

"Gas-Fired Unvented Room Heaters".

Product Specific Information 

 

Model(s)

Altitude

Maximum 

Allowable 

BTU/hr

ACUF32-BD/GD

(0-2000 FT)

30,000

ACUF36-BD/GD

(0-2000 FT)

40,000

ACUF42-BD/GD

(0-2000 FT)

40,000

D.  Non-Combustible Materials Specification

Material which will not ignite and burn. Such materials are 

those consisting entirely of steel, iron, brick, tile, concrete, 

slate, glass or plasters, or any combination thereof.

Materials  that  are  reported  as  passing 

ASTM E 136, 

Standard Test Method for Behavior of Materials in 

a Vertical Tube Furnace at 750 ºC 

shall be considered 

non-combustible materials.

E.  Combustible Materials Specification

Materials made of or surfaced with wood, compressed pa

-

per, plant fibers, plastics, or other material that can ignite 

and  burn,  whether  flame  proofed  or  not,  or  plastered  or 

unplastered shall be considered combustible materials.

F.  Electrical Codes

NOTICE: 

This appliance must be electrically wired 

and grounded in accordance with local codes or, in the 

absence of local codes, with 

National Electric Code 

ANSI/NFPA 70-latest edition.

C.  High Altitude Installations

NOTICE: 

If the heating value of the gas has been reduced, 

these rules do not apply. Check with your local gas utility 

or authorities having jurisdiction.

When installing above 2000 feet  elevation:
•  In the USA: Reduce input rate 4% for each 1000 feet  

above 2000 feet.

            

Check  with  your  local  gas  utility  to  determine  proper 

orifice size.

Note:  

Smoke, carbon monoxide or combination alarms 

Alarm manufacturers recommend that alarms be kept at 

least 15 ft. to 20 ft. laterally away from fuel-burning sources.  

Installing the alarm closer than 15 ft. will not harm the 

alarm, but may increase the frequency of nuisance alarms.  

Mounting alarms on the wall versus the ceiling will further 

reduce nuisance alarms.

4

Monessen • ACUF32/36/42 Installation Manual • 4136-901 • Rev A • 01/21

Содержание ACUF32-BD

Страница 1: ...ecorative type unvented room heater for the minimum fireplace size requirement DO NOT INSTALL AN APPLIANCE IN THIS FIREBOX UNLESS THIS FIREBOX MEETS THE MINIMUM DIMENSIONS REQUIRED FOR THE INSTALLATION ACUF32 BD ACUF32 GD ACUF36 BD ACUF36 GD ACUF42 BD ACUF42 GD HOT SURFACES Firebox surfaces are hot during operation AND cool down Hot surfaces will cause burns DO NOT touch firebox until it is cooled...

Страница 2: ...rations 5 B Tools and Supplies Needed 5 C Inspect Firebox and Components 5 3 Firebox Dimensions A Firebox Dimensions 6 B Hearth Dimensions 7 C Framing Dimensions 8 D Clearance to Combustibles 9 E Constructing the Appliance Chase 10 4 Firebox Preparation A Securing and Leveling the Firebox 11 B Installing Optional Outside Air Kit s 11 5 Electrical Information A Wiring Requirements 12 B Wiring the J...

Страница 3: ...he installation is complete __________________________ by ______________________on _________ Firebox Install Section s 3 4 Verified clearances to combustibles Firebox is leveled and secured Outside Air Kit Installed Optional Electrical Section 5 Unswitched power 110 120 VAC provided to the firebox Gas Section 6 Proper fuel type Leak check performed and inlet pressure verified Finishing Section 7 C...

Страница 4: ...al which will not ignite and burn Such materials are those consisting entirely of steel iron brick tile concrete slate glass or plasters or any combination thereof Materials that are reported as passing ASTM E 136 Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 ºC shall be considered non combustible materials E Combustible Materials Specification Materials made of ...

Страница 5: ...ric drill and bits Safety glasses Reciprocating saw Caulking material 300ºF minimum continuous exposure rating Note Refer to the installation instructions provided with the log set for items required for log set installation Hearth Home Technologies disclaims any responsibility for and the warranty will be voided by the following actions Installation and use of any damaged firebox or system compon...

Страница 6: ... 76 mm 34 in 864 mm A 20 in 508 mm 15 7 8 in 403 mm 5 3 4 in 146 mm 5 3 4 in 146 mm 15 7 8 in 403 mm 2 in 51 mm 7 3 4 in 197 mm 2 in 50 mm 9 3 8 in 238 mm 32 36 42 A 32 in 813 mm 36 in 914 mm 42 in 1067 mm B 38 in 965 mm 42 in 1067 mm 48 in 1219 mm Gas Access Above Hearth Outside Air Electrical Access Wall Switch Strain Relief Outside Air Gas Access Above Hearth Gas Access Below Hearth 6 Monessen ...

Страница 7: ...ons Model A B C D E ACUF32 28 7 8 in 15 in 20 3 8 in 25 1 2 in 22 5 8 in ACUF36 32 7 8 in 15 in 24 3 8 in 25 1 2 in 22 5 8 in ACUF42 38 7 8 in 15 in 30 3 8 in 25 1 2 in 22 5 8 in B Hearth Dimensions 7 Monessen ACUF32 36 42 Installation Manual 4136 901 Rev A 01 21 ...

Страница 8: ...l installation may vary due to individual design preference Figure 3 3 Framing Dimensions A 5 8 in B F E D D 5 8 in C MODEL A B C D E F ACUF32 38 1 2 in 34 1 4 in 19 3 4 in 47 1 4 in 66 3 4 in 33 1 2 in ACUF36 42 1 2 in 50 in 70 3 4 in 36 in ACUF42 48 1 2 in 54 1 4 in 76 3 4 in 38 1 2 in Note Add 1 2 inch to width A and 1 4 inch to height B dimensions when using optional trim kit to finish the ins...

Страница 9: ...learances to Combustibles Location should be out of high traffic or windy or drafty areas DO NOT INSTALL WHERE CURTAINS FURNITURE CLOTHING OR OTHER FLAMMABLE OBJECTSARE LESS THAN 36 FROM FRONT OF FIREBOX Never obstruct the front opening of the vent free firebox or restrict the flow of combustion and ventilation air 0 in to back 0 in to side 0 in Drywall Combustible flooring may be installed next t...

Страница 10: ...eps Chases should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems The chase should not break the outside building envelope in any manner Walls ceiling base plate and cantilever floor of the chase should be insulated Vapor and air infiltration barriers should be installed in the chase as per regional codes for the rest of the home Additionally in ...

Страница 11: ...ioning and Securing of Firebox B Installing Optional Outside Air Kit s Figure 4 2 Optional Outside Air Kit s 4 Firebox Preparation Note The outside air kit is an optional accessory that can be used to bring in fresh air Use of the air kit is not required for operation unless specified by local codes CAUTION Risk of cuts abrasions flying debris Wear protective gloves and safety glasses during insta...

Страница 12: ...utside of the firebox However for ease of installation it is recommended that the junction box be wired from outside of the firebox If the junction box is wired from OUTSIDE firebox Remove the screw attaching the junction box cover to the outer shell Pull junction box cover out to disengage it from the outer shell See Figures 5 1 Figure 5 1 Junction Box Cover Removal Install electrical wires from ...

Страница 13: ...EMPERATURE SENSOR FAN CONTROL MOUNTED IN FIREBOX F F F F JUNCTION BOX WIRE HARNESS M M F F F F M M WIRE HARNESS M F LIGHT SOCKET ASSEMBLY F F POWER CORD LIGHT CONTROL MOUNTED IN FIREBOX BLK GRN WHT 13 Monessen ACUF32 36 42 Installation Manual 4136 901 Rev A 01 21 ...

Страница 14: ...F F M M WIRE HARNESS F F POWER CORD LIGHT CONTROL MOUNTED IN FIREBOX BLK GRN WHT M F LIGHT SOCKET ASSEMBLY KNOCKOUT Note Wires supplied from remote wall box loca ons to pass through provided knockout in face of junc on box Figure 5 5 Wiring Diagram Remote Fan Control 14 Monessen ACUF32 36 42 Installation Manual 4136 901 Rev A 01 21 ...

Страница 15: ...14 2 MINIMUM WHT BLK BLK WHT LIGHT CONTROL MOUNTED IN REMOTE WALL BOX M F LIGHT SOCKET ASSEMBLY Note Wires supplied from remote wall box loca ons to pass through provided knockout in face of junc on box KNOCKOUT Figure 5 6 Wiring Diagram Remote Light Control 15 Monessen ACUF32 36 42 Installation Manual 4136 901 Rev A 01 21 ...

Страница 16: ...URE SENSOR JUNCTION BOX WIRE HARNESS M M F F M F LIGHT SOCKET ASSEMBLY F F POWER CORD BLK GRN WHT Note Wires supplied from remote wall box loca ons to pass through provided knockout in face of junc on box KNOCKOUT Figure 5 7 Wiring Diagram Remote Fan and Light Controls 16 Monessen ACUF32 36 42 Installation Manual 4136 901 Rev A 01 21 ...

Страница 17: ... appliance IMPORTANT Install manual shut off valve equipment shutoff valve in an accessible location The manual shut off valve is for turning on or shutting off the gas to the firebox Fire Risk Explosion Hazard High pressure will damage valve Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1 2 psig Close the manual shutoff valve BEFORE pressure testing gas lin...

Страница 18: ...will withstand temperatures up to 190 F B Mantel and Wall Projections WARNING Risk of Fire Comply with all minimum clear ances as specified Combustible Noncombustible Mantels Figure 7 1 Minimum Vertical and Maximum Horizontal Dimensions of Combustible and Noncombustible Note Mantel Measurement is taken from top of the firebox opening NOT the top of the unit Reducing non combustible mantel and or m...

Страница 19: ...ly decorative fronts certified for use with this firebox model may be used Contact your dealer for a list of deco rative fronts that may be used Minimum Side Wall Unit Gray area is combustible material White area is non combustible material only 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 9 00 6 00 9 00 19 Monessen ACUF32 36 42 Installation Manual 4136 901 Rev A 01 21 ...

Страница 20: ...odel actual TV temperatures should be validated at the time of each installation TVs should not be used in situations where the actual TV temperature exceeds the manufacturers maximum allowable operating temperatures identified in the TV s technical specifications Contact the TV s manufacturer directly if you cannot locate this information or have questions regarding the information 3 Mantel heigh...

Страница 21: ...1 on each end slide hood into position and secure See Figure 8 1 Figure 8 1 WARNING Risk of Fire The firebox hood must not be modified or replaced with a hood that may be provided with the vent free appliance D Adjustable Firebox Supports This firebox is provided with adjustable supports to allow for proper support of the firebox bottom and reduced sag ging caused by heavy concrete logs To adjust ...

Страница 22: ... screws previously removed See Figure 8 6 Note The front edge of the firebox supports may be ad justed in or out if needed to provide the best support for the selected log set Once the firebox supports are prop erly located to provide maximum support the front edge MUST be secured with a minimum of 1 screw each The rear edge of the firebox supports should not be altered from the factory setting Fi...

Страница 23: ... ID4 4 in Insulated Duct UD4 4 in Uninsulated Duct AKD Outside Air Kit IA32BCF IA36BCF A42BCF Contemporary Front Wire Ties Flexible Duct not supplied Outside Air Collar Outside Air Hood Outside Air Door MONAL VF Light Kit GFK 160VF Blower A32BGL A36BGL A42BGL Black Glass IAL32TK IAL36TK AL42TK Trim Kit 23 Monessen ACUF32 36 42 Installation Manual 4136 901 Rev A 01 21 ...

Страница 24: ... Contact Information NOTES Monessen a brand of Hearth Home Technologies 7571 215th Street West Lakeville MN 55044 www monessenhearth com 24 Monessen ACUF32 36 42 Installation Manual 4136 901 Rev A 01 21 ...

Отзывы: