Страница 1: ...C 99A C 100A FIRE ALARM CONTROL PANELS INSTALLATION OPERATION MAINTENANCE MANUAL...

Страница 2: ...November 1994 The C 99A C 100A FireAlarm C o n t r o lPanels I O M Manual P N001 097 00 includes t h e following addendum A oMONACO ENTERPRISES INC 1994 DOCUMENTNO 001 097 00 PAGE Monaco Ente p ises...

Страница 3: ...DDENDUM A The attached INTERCONNECTION DRAWING YPICAL FIRE AIARM EQUIPMENT replaces the drawing on pages C4 C5 in the Appendix of this Manual MONACO ENTERPRISES INC 1994 DOCUMENT NO 001 097 00 ADD A P...

Страница 4: ...n i s expressly prohibited unless authorized i n writing by Monaco Enterprises Inc These instructions a r e not intended t o cover a l l d e t a i l s or variations i n equipment nor t o provide f o r...

Страница 5: ......

Страница 6: ...I X APPENDIX A WARRCWTY A1 B SCHEMATIC DIAGRAMS C 99A 12 Control Panel PCB Assembly B1 C 99A 24 Control Panel PCB Assembly B2 C 99A 24 Transformer Assembly B3 C 100A 24 Control Panel PCB Assembly B4 C...

Страница 7: ...3 1 C 99A 24 Transformer and PCB Assembly 3 3 C 100A 24 PCB Assembly 3 4 End of Line Diode Configuration E2 LIST O F TABLES TABLE DESCRIPTION P A G E 1 1 Control Panel Versions 1 1 2 1 Standard Contr...

Страница 8: ...Figure 1 1 Low Voltage F i r e Alarm Control Panel 555 LDOCUMENT NO 001 097 00 PAGE 4 Monaco E n t e p i s e s INC SPOKANE WASHINGTON 99214...

Страница 9: ...ng transmitters or Radio Alarm System transceivers Table 1 1 shows the available versions TABLE 1 1 CONTROL PANEL VERSIONS MODEL VOLTAGE Volts Amperes C 99A 12 C 99A 24 NOTE The 12 Vdc 3 Amp version o...

Страница 10: ...n Operation and Maintenance of the C 99A 12 C 99A 24 and C 100A 24 low voltage automatic fire alarm Control Panels 1 2 FUNCTIONAL DESCRIPTION I All the Control Panels operate identically except for th...

Страница 11: ...NOTES...

Страница 12: ......

Страница 13: ...and 25 o Resistor R2 o Milliamp meter between terminals 4 and 5 o AC monitor relay K3 contacts 8 and 6 o Trouble relay K2 coil pins 7 and 2 o Resistor R3 between terminals 12 and 11 o Circuit trace be...

Страница 14: ...e horn LS1 goes ON o Silenceable remote Trouble bell goes ON terminals 17 and 18 o Nonsilenceable remote Trouble device goes ON terminals 15 and 16 The silenceable Trouble horn and remote Trouble bell...

Страница 15: ...ells turn ON between terminals 22 and 21 o Circuit conducts between terminals 21 and 11 Silencing the Alarm bell circuit is done by placing the Alarm Silence switch S2 in the Silence position The Alar...

Страница 16: ...tor relay K3 contacts 1 and 4 close o AC monitor relay K3 contacts 6 and 8 open o Battery power i s applied t o Control Panel o Trouble condition occurs see Paragraph 1 2 3 When AC power i s restored...

Страница 17: ...E n t e p i s e s r c SPOKANE WASHINGTON 99214 Trouble Signal Silence Switch Yel Alarm Signal Silence Switch Red Alarm Test Switch Wht Reset Switch Blk AC P i l o t Lamp Grn Alarm Lamp Red Trouble Lam...

Страница 18: ...IMC SPOKANE WASHINGTON 99214 Trouble Signal Silence Switch Yel Alarm Signal Silence Switch Red Alarm Test Switch Wht Reset Switch Blk AC P i l o t Lamp Grn Alarm Lamp Red Trouble Lamp Wht Alarm Silenc...

Страница 19: ...GS 2 2 1 Personnel Safeguards The following general safety precautions must be observed during all phases of operation service and repair of this equipment Failure to comply with these precautions or...

Страница 20: ...rm any unauthorized modifications to the equipment before consulting with Monaco to ensure that safety features are maintained 2 2 2 Equipment Protection The following general requirements must be obs...

Страница 21: ...onfiguration Contact Monaco Enterprises Inc to purchase additional copies of these manua1s Every configuration is available with the options pre wired in an enclo sure External wiring is required to c...

Страница 22: ...LE 2 1 STANDARD CONTROL PANEL CONFIGURATIONS one for l2VDC McCulloh Type Annunciator Part Number two for 24VDC 555 N DOCUMENT NO 001 097 00 PAGE 2 4 Monaco E n t e p i s e s INC SPOKANE WASHINGTON 992...

Страница 23: ...ate wall anchors toggle bolts lag bolts etc to adequately support the weight of the enclosure Mounting holes are provided in the back of the enclosure Install any conduit necessary B After all mountin...

Страница 24: ...h the aid of an end of line power supervision relay module Figure 2 1 shows the super visory scheme The miscellaneous part Tables in Section 5 contain ordering information for this module L Single Loo...

Страница 25: ...g Appendix G contains a condensed Control Operation Instruction label included with each Control Panel 3 1 NORMAL CONDITION In a Normal condition the o AC pilot lamp is ON front of enclosure o Milliam...

Страница 26: ...lly restores the system to normal with one exception The ring back feature causes the Trouble horn to sound again This alerts the Operator to restore the Trouble Silence switch Sl to the normal up pos...

Страница 27: ...e following switches located on the PCB o Momentarily place the Reset switch S2 in the reset down position o Place Trouble Silence switch Sl in the normal up position o Place Alarm Silence switch 52 i...

Страница 28: ...ally places the Control Panel in Normal condition The Trouble ring back feature alerts the Operator to the changed condition 3 5 INITIAL TEST After the Alarm system installation is completed wiring sh...

Страница 29: ...0 0 0 21 to 22 0 0 0 23 to 24 12 24 24 L 25 to 26 J 28 to 27 12 24 24 Alarm Condition I2 to 11 11 5 23 5 21 to 22 12 24 23 to 24 12 24 25 to 26 0 0 28 to 27 0 0 I Battery Power Condition I2 to 11 0 0...

Страница 30: ...tem the authority having jurisdiction shall be notified No tests shall be made without proper notification NOTE Terminals 19 and 20 on all Control Panel terminal blocks are not used 555 0 DOCUMENT NO...

Страница 31: ...he Normal condition Occupants of the building shall be notified in advance as to time of testing of sounding devices Such tests should be held during daytime hours 4 2 DISASSEMBLY AND REASSEMBLY Remov...

Страница 32: ...re Assembly of a new Control Panel into the enclosure is the reversal of the above procedure I 4 2 2 Transformer Assembly C 99A 24 version only The transformer assembly is located at the top of the en...

Страница 33: ...e with one exception D o not crush the back of the new indicator lamp CAUTION I The AC p i l o t lamp i s a l i g h t emitting diode LED Polarity must be observed when i n s t a l l i n g o r it w i l...

Страница 34: ...defective Check f o r c o r r e c t system wiring Check i f EOL diode i s backward Check f o r defective detector Check f o r defective b e l l Reduce peripherals Short across t h e following Control...

Страница 35: ...Kl a r e t h e same and can be interchanged i f e i t h e r is suspected of causing a problem Detector Loops Not Shorted Terminals 25 t o 26 TABLE 4 3 NO BATTERY P O W E R Replace Alarm relay Kl b PRO...

Страница 36: ......

Страница 37: ...585 000 00 426 000 00 Description RELAY DPDT 12VDC lOA CONT RELAY SPDT I OPERATED 2A CONT FUSE FAST BLOW 1 5AMP 250V FUSE FAST BLOW 8AMP 32V LAMP INCAND RED l4V lOOMA QC LAMP INCAND AMB 14V lOOMA QC...

Страница 38: ...000 00 HORN MIDI 12VDC O O5A SCR MT C 100A 24 PIN 175 014 01 Part Number Description 452 300 00 RELAY DPDT 24VDC lOA CONT 455 000 00 RELAY SPDT I OPERATED ZA CONT 500 123 00 FUSE SLO BLOW l AMP 250V...

Страница 39: ...C 100A 24 Control Panel PCB Assembly Wiring Diagrams C 99A 12 Control Panel C 99A 24 Control Panel C 100A 24 Control Panel Typical Fire Alarm 24V Installation Additional Equipment for Custom Configur...

Страница 40: ...manufactured by it However in the event of the failure of any component or accessory not manufactured by the Company the Company will give reasonable assis tance to the buyer in seeking an adjustment...

Страница 41: ...LOOP A M P I METER BATTERY F 3 LAST DESIGN CHART RELAY CONDITION CHART E ErJCRGlZtP NE NOT ENIICLGIZEP N I T I...

Страница 42: ...I AC PILOT I I LOOP E EhlELZGIZED NE N O T ENEffiIZED...

Страница 43: ...GRN GRN I II C 99A 24 Transformer Assembly Schematic 555 R DOCUMENT NO 001 097 00 PAGE B3 Monaco E n t e p i s e s r c SPOKANE WASHINGTON 99214...

Страница 44: ...4HLDED TCF MINALSA L F I N 9 I P E E V I S O L Y LCOP COMMON 3 L L L R E S I S T O K 5 M E A S U P E D I N OHMS 4 ALL C A P A L I T O R S F I E A S V E E D I l u MILS2DFAfZADS A L M L A M 5 POLARITY S...

Страница 45: ...m devices when an audible device is connected to terminals 11and 12 Only circuits connected to terminals 25 through 28 are limited energy arcuits The system is actuated manually or automatically throu...

Страница 46: ...alarm devices when an audible device is connected to terminals 11and 12 Only circuits connected to terminals 25 through 28 are limited energy circuits The system is actuated manually or automatically...

Страница 47: ...tations and smoke detectors may be used with the C 100A but must be U L listed The C 100A is also suitable for connection of waterflow alarm deviceswhen an audible device is connected to terminals 11...

Страница 48: ...A W I SEE NOTE 6 I r l AM 0 0 0 0 0 0 KEMUL 1 u PI PZ n n NI I I P A I C D lRlNC DI RT 100 SUPERMSION INTERFACE P N 750 300 00 r P N A I C D 0 0 0 0 0 0 1 2 3 4 5 6 7 8 9 10 TWPER EOL FROM INPUT CONT...

Страница 49: ...GH CONNECTIONS FOll F A C P DETECTION LOOP EXFANSION AND ARE ISOUTED FROM THE RT 100 PANEL INTERFACE FVNCTION NO CONNECTIONS T O TERMINALS ARE REWIRED F M INTER FACE OPERATION 79 000 00 RESISTOR ASSY...

Страница 50: ...nnunciator 24 VDC GFA24 Two Zone Class AIB Annunciator 24 VDC Sealed Gel Type Battery 12Vl5AH See Note 1 Sealed Gel Type Battery 12Vl20AH See Note 2 Sealed Gel Type Battery 12V16 5AH See Note 1 Nicad...

Страница 51: ...will be 00 18 Enclosure 01 24 Enclosure 02 12 Enclosure 03 3 6 Enclosure 04 42 Enclosure If your component and space measurements total 25 the correct control panel enclosure would be 36 and the part...

Страница 52: ...rm stations may be intalled on the detector circuits provided that the stated wire resistance on the Installation Wiring Diagram is not exceeded Smoke detectors may be installed on the detector circui...

Страница 53: ...ge is reversed Alarm mode the internal bell diodes become conducting paths allowing the Alarm bells to ring Figure 6 1 shows two sets of polarity markings above Terminals 21 and 22 the bell terminals...

Страница 54: ...de is connected to Terminal 21 The Red lead cathode is connected to Terminal 22 When used in the last bell box make sure the diode s Black wire connects to the bell loop wiring that originates at Term...

Страница 55: ...riate series dropping resistor When connecting a trip coil to terminals 11 and 12 of the Control Panel remove the 5 watt resistor and connect the trip coil directly The total resistance across Termina...

Страница 56: ...rouble Connection SmokeDetector s normal 0 005 Smoke Detector s alarm 0 05 Alarm Bell s 0 125 TOTAL BATTERY CAPACITY REQUIRED 9 Use the alarm current of 10 of the number of smoke Detectors connected t...

Страница 57: ...mentary Black Reset switch to DOWN position Red alarm light will go out White trouble light will go out Trouble horn will sound Silence horn by returning Trouble Silence switch Yellow UP to normal pos...

Страница 58: ...HOME OFFICE E 14820 SPRAGUE AVE SPOKANE WA 99216 509 926 6277 SPOKANE WASHINGTON SAN ANTONIO TEXAS PANAMA CITY FLORIDA HONOLULU HAWAII WASHINGTON D C TAMUNING GUAM OKINAWA JAPAN SEOUL KOREA 5839...