2. Installation

2.1 Preparation

- Check the membrane of visual transport damage.

- Read and follow the safety instructions and the operating

instructions, before handling with the device !

2.2 Mounting in the vessel

Position the level indicator at the flange and fix it with 4 washers and
screws M5.

2.3 Electrical connection

Circuit diagram

2.4 Cable gland

Screw on the cap nut until the cable gland is closed tightly.

-

3. Commissioning

Put the level indicator into operation only, if the installation and the
electrical connection have been done correctly.

-

4. Setting of the sensitivity

- The level indicator is preset at sensitive.

- With the adjusting screw the device can be set less sensitive.

- Remove the safety screw from the housing cover.

- Pull off the cover from the lower part of housing.

- Set the sensitivity of the switch according to your needs with the

adjusting screw. Clockwise insensitive.

- Put on the housing cover and fasten it with the screw.

M   LLET

Füllstandtechnik

GmbH

02

       MFA-BA        04/13

  ©

 by MOLLET

Operating instructions        MOLLET   D-74706 Osterburken  Tel.  +49  6291 6440-0  Fax  +49  6291 9846

5.

5.1

- Use the level indicator in its intended application only.

- The level indicator is provided for use in silos or vessels with

pressureless operation.

- Comply with the 

 on the data plate. Check the

membrane of the level indicator, when the permissible temperature
of bulk goods was exceeded or was fallen short off.

- Damaged devices have to put out of operation immediately.

5.2 Inexpert handling

-

 of the safety instructions and the operating instructions.

- Not intended use.

- Violation against applicable law and standards.

-

6. Maintenance

- Do maintenance work only, if the silo or the vessel is empty and

if there is no overpressure or vacuum.

- Inspect in regular intervals if there is any wear or abrasion at the

membrane. Define the control intervals, depending on the
characteristics of the bulk goods.

- Replace the device in case of damage or abrasion of the

membrane.

-

7. Storage

- Store the level indicator dry and dust-free.

- Protect the membrane against pointed objects and ultraviolet

radiation.

-

8. Disposal

- The level indicator can be recycled.

- The disposal applies to the valid environmental guidelines

according to the location of the carrier and the local manufacturing
conditions.

Utilization

Normal operation

Ignoring

specifications

NC NO

C

P

2 3/4 1

1

adjusting screw with locking nut

2

3/4

002-AP00

Membrane level indicator