molex TM2000 Скачать руководство пользователя страница 16

Industrial Crimp Quality Handbook 

Doc No: TM-640160065 

Release Date: 00-00-02 

UNCONTROLLED COPY

 

Page 16 of 27 

Revision: C 

Revision Date: 12-23-09 

Wire within 

Outside Diameter 

Exceeds 

Outside Diameter 

Loose Wire 

Expanded Strands 

ACCEPT 

REJECT 

Improper Stripping 

“Nicked” Strands 

Improper Stripping 

Cut Strands 

Proper Stripping 

Undamaged 

Strands 

ACCEPT 

REJECT 

ACCEPT 

Damage Less 

Than 1/2 of 

Insulation Thickness 

Damage 1/2 of 

Insulation Thickness 

or Greater 

Burred or Charred 

Cut 

Split 

Insulation 

Whiskers 

REJECT 

Insulation 

Thickness

 

SECTION 6 

 

PROCEDURES 

 

6.1

 

Preparing the Wire 

 

Check the stranded wire to see if any strands have 
loosened and expanded to be larger than the wire and 
the insulation together. If this has occurred, twist the 
wires to the size they were before they were stripped. Be 

sure that the stranded wire is within the outside diameter 
of the insulation after you have twisted them. 

 
 

 
 
 
 

 
 
 
 

Check the insulation to ensure that there has been 
a nice clean cut.  Wires with damaged insulation 
should not be used. 
 

 
 
 
 

 
 
 

 
 
 
 

 
 
 
 

 
 
 
 

 

Check to see if the stripping tool or machine has cut or 
nicked any of the wires.  If you see nicked wire you must 
cut and re-strip the wire before crimping to be sure that 

the amount of current that can be carried is not reduced. 

 
 

 
 
 
 

 
 
 
 

 
 
 
 

 

6.2

 

Setup and Operation of a Press 

 
1.

 

Check that tooling is clean and not worn. If 

necessary, clean and replace worn tooling. 

2.

 

Disconnect power to the press and remove 
guarding devices. 

3.

 

Install the appropriate tooling into the press. 

4.

 

Load terminals into the tooling so that the first 
terminal is located over the anvil. 

5.

 

Manually cycle the press to help ensure a complete 
cycle can be made without interference.  If it 

cannot, remove tooling and check press shut 
height.  Go to procedure 3. 

6.

 

Check that the tooling is aligned.  Check the 
impression on the bottom of the crimp that was 

made by the anvil tooling. Check that the 
extrusions and crimp form are centered.  If not, 
align tooling and go to 
procedure 5. 

7.

 

Check that the terminal 
feed locates the next 
terminal over the center 
of the anvil tooling.  If 

not, adjust terminal 
feed and the feed finger 
and go to procedure 5. 

8.

 

Re-install all safety 

devices that were removed during the set-up.  

(Follow all safety requirements listed in 
individual press and/or tooling manuals.)

9.

 

Crimp sample terminals under power. 

10.

 

Evaluate cut-off tab length and conductor bell 
mouth.  If adjustment is necessary, disconnect 
power to the press and remove guarding.  Adjust 

Содержание TM2000

Страница 1: ...Industrial Crimp Quality Handbook Doc No TM 640160065 Release Date 00 00 02 UNCONTROLLED COPY Page 1 of 27 Revision C Revision Date 12 23 09 INDUSTRIAL CRIMP QUALITY HANDBOOK Order No 64016 0065...

Страница 2: ...derless Terminals 5 2 Barrel Serration Dimples 5 3 Barrel Styles 5 4 Splices 6 Procedures 6 1 Preparing the Wire 6 2 Setup and Operation of a Press 6 3 Setup and Operation of a Hand Crimp Tool 6 4 Set...

Страница 3: ...g process are the terminal the wire and the tooling Terminal For most applications it is not economically practical for connector manufacturers to design a terminal to accept one wire size one wire st...

Страница 4: ...cut off tab length and the insulation wire position while strip length and wire locations affect the conductor brush and insulation position Adjusting the insulation crimp height may result in a slig...

Страница 5: ...verlapping Chamfer An angle on the inside edge of the barrel entrance of a terminal that permits easier insertion of the wires into the barrel Circular Mil CM A unit of area used to indicate wire size...

Страница 6: ...on the bottom wire barrel resulting from the clearance between the punch and anvil tooling If the anvil is worn or if the terminal is over crimped an excessive extrusion results An uneven extrusion ma...

Страница 7: ...d terminal must be squeezed to get a gas tight seal It s important to crimp the wires tight enough to keep them from slipping out of the connector but not so tight as to crush the wires in the termina...

Страница 8: ...8 Terminal A device designed to terminate a conductor that is to be affixed to a wire or cable to establish an electrical connection It is a synonym for contact There are two main types which include...

Страница 9: ...dle of wires twisted together to act as one Wire Size Wires have varying sizes or gauges that carry different amounts of electrical current with each wire used for a separate purpose The size in AWG i...

Страница 10: ...ce it It has a thin blade that supports the top of the crimp while a pointed section determines the bottom radial curved surface Ruler Pocket Scale This is used to measure the length of bell mouth cut...

Страница 11: ...UL 486 A Terminals Copper conductors only UL 486 C Butt Splices Parallel Splices Closed End Connectors and Wire Nuts UL 310 Quick Disconnects Flag and Couplers Military Class 2 Military Approved Term...

Страница 12: ...mm2 3 The Insulkrimp has a rigid insulation sleeve made of PVC polyvinyl chloride which protection to the Krimptite barrel area in wire sizes of 10 22 AWG or the brazed seam of the Versakrimp barrel o...

Страница 13: ...ations vary The following are some examples Barrel Lengths In wire sizes 26 16 AWG the industry has two standard barrel lengths for the metal barrel The lengths are 6 35 mm 25 and 4 36 mm 11 64 The 4...

Страница 14: ...pecial splices for nearly every type of wiring need Butt Splices On this connector the stripped wires are inserted from each end and they butt in the center Then a crimp at each end secures the connec...

Страница 15: ...has stripped wires that lie side by side in the splice They are secured by a single crimp in the middle Window Butt Splice This connector has military approval Mil T 7928 5 to withstand the harshest...

Страница 16: ...ou must cut and re strip the wire before crimping to be sure that the amount of current that can be carried is not reduced 6 2 Setup and Operation of a Press 1 Check that tooling is clean and not worn...

Страница 17: ...ower and remove guarding Adjust conductor crimp height install guards connect power and go to procedure 18 21 Document measurements 6 3 Setup and Operation of a Hand Crimp Tool 1 Insure that the hand...

Страница 18: ...cator make sure the seam of the barrel is oriented up or down in the tool as this will provide higher pull force values 6 5 Crimping Dies The Molex product line includes seven types of dies for differ...

Страница 19: ...omplete line of fully automatic wire processing machines semi automatic and manual wire crimping tools Each system is tailored to our customer s individual needs by using support equipment and can be...

Страница 20: ...and Military Tensile values See Section 8 Note that the Military pull force is higher than the U L 7 1 Visual Inspection of OPEN BARREL Crimps Insulation Not Damaged 1 Crimp the insulation just enough...

Страница 21: ...contact area of the lug or terminal 2 If the wire strands are in the contact area they will interfere when the terminal is connected No Strands Sticking Out Strand Fold Back 1 Be sure that all of the...

Страница 22: ...On all crimped terminals the conductor crimp should be centered on the conductor barrel This insures even pressure on the entire length of the barrel Good Bell Mouth Present 1 Be sure that a good bell...

Страница 23: ...UNCONTROLLED COPY Page 23 of 27 Revision C Revision Date 12 23 09 Insulation Support Crimp 1 On closed barrel terminals that have a secondary metal sleeve AviKrimp the metal sleeve should be formed s...

Страница 24: ...d similar substances Some reasons for failure of crimped joints to meet minimum tensile requirements include nicked wires nicked or ruptured strands strand turn back at crimp joint and ruptured wires...

Страница 25: ...lt rating of the terminal 8 3 Final Tensile Value The type of die affects the final tensile value in several ways See Crimping Dies Section 6 5 If the die as in the indentor type does not indent far e...

Страница 26: ...mp Some stranded wire crimp configurations are not satisfactory for solid wire More deformation must be imposed in order to form wire and barrel into a solid mass On the other hand finer strands will...

Страница 27: ...e strand and multiply the result by the total number of strands CMA D x D x Number of Strands of one Strand SECTION 9 MISCELLANEOUS AWG CMA Table Terminal Size AWG CMA Range 26 22 202 810 24 20 320 1...

Отзывы: