User Reference Guide
SST-PB3S-CLX-RLL
28
Installing the SST-PB3S-CLX-RLL Slave
©2014 Molex Inc. Industrial Products Business Unit, Integrated Products Division
Document Edition: 1.0, Document #: 715-0109, Template Edition: 1.1, Template #: QMS-06-045
Use, duplication or disclosure of this document or any of the information contained herein is subject to the restrictions on page ii of this document.
4.5.1 Display Tables
The following table shows scrolling LCD display information and descriptions:
Table 8: SST-PB3S-CLX-RLL Display
Display
Meaning/Description
Ver x.xx
Power up message. This message appears briefly during power up. x.xx
is the firmware version.
Invalid Serial Number
The serial number has not yet been programmed on this module.
CLX INIT FALT 0xYY
ControlLogix Initialization fault. The ControlLogix Backplane startup
routines failed, with failure code YY (hex).
CONNCLSD
There are no open ControlLogix Backplane connections.
NVLD XMIT SIZE
Invalid transmit size. The size of the transmitted data for a new connection
does not match that of an existing connection.
NVLD OUT CNPT
Invalid output connection point.
NVLD RCV SIZE
Invalid receive size. The size of the received data for the connection is
invalid.
NVLD RCV BUFF
Invalid receive buffer. Failed to allocate a receive buffer. This should
never happen.
CONN BLKED
Connections blocked (not allowed). The Connection Manager is in a
Connections not allowed state. This should never happen.
DUPLCONN DTCT
Duplicate connection detected. Connection is already open.
RSRC ERR1 INCM
Resource error # 1 in Connection Manager: Out of memory. This should
never happen.
NVLD FWD OPEN
Invalid forward open. CM was unable to parse the Forward open. May be
a key segment mismatch.
NVLD SRVC CODE
Invalid service code. Service code in CLX Forward Open was invalid.
WDOG
Watchdog timeout. The module watchdog has timed out.
OFPT
Slave firmware operational fault.
Backplane OK
SST-PB3S-CLX-RLL resides in the rack that is powered on but not
configured in the CLX Controller.
Booting
SST-PB3S-CLX-RLL is just powering up and initializing.
COPN
Connection open.
MULT
Multiple processors are attempting to connect to the slave.
IDMSM
There is a Profibus Slave ID Mismatch. The DP Master is trying to
configure module with wrong Slave ID
Note
The default LCD display is COPN when the slave is working correctly.