INSTALLATION INSTRUCTIONS

 

BEFORE INSTALLING OR ADJUSTING THIS PRODUCT,                                                                                                         
PLEASE READ THESE INSTRUCTIONS CAREFULLY. 
PLEASE KEEP THIS GUIDE FOR FUTURE REFERENCE

 

 

MIIM E-Module 

 

1.0  SCOPE 

 

This document provides installation instructions for the Molex IMD-00001 MIIM E-Module. 

 

The following panels are compatible with the IMD-00001 E-Module: 
 

  PID-00266 

  PID-00271 

  PID-00268 

  PID-00272 

  PID-00269 

  PID-00273 

  PID-00270 

  PID-00274 

 

 

2.0  PROCEDURE 

 

IMPORTANT:  Removing E-modules or MIIM continuity boards from the panel will result in loss of 
continuity on all jacks in the panel.  This is a service-affecting event and removal or replacement 
procedures should be done off-hours or during a scheduled maintenance window.  Continuity is 
restored as soon as the E-module or continuity boards are inserted in the panel.  Jacks do not have  
to be removed when removing or adding E-modules. 

 

 

Fig.1 

 

Remove Continuity Boards 

 

To remove MIIM continuity boards, pull the strap straight back on each of the four continuity boards 
(See Fig. 1). 

 

 