7.0 Cable Gland
The X450 and LED450 beacons are supplied as standard with 1 x M20 threaded side cable entry with
provision for up to 4 supplied to special order.
SAFETY WARNING
If the X450 and LED450 are used at high ambient temperatures, ie over +40
0
C then the cable entry
temperature may 70
0
C and therefore suitable heat resisting cable glands must be used, with a rated
service temperature of at least 95
0
C.
If a high IP (Ingress Protection) rating is required, a suitable sealing washer must be fitted under the cable
gland. When only one cable entry is used, the other one must be closed with a blanking plug, which must
be suitably approved for the installation requirements.
8.0 End of Line Monitoring
An end of line monitoring diode or an end of line monitoring resistor can be connected across the 24v+ and
0 terminals. If an end of line monitoring resistor is required, this must be specified by the customer.
9.0 Maintenance
During the working life of the product, little or no maintenance is required due to the robust maintenance-free
surface. Composite material of PC (Polycarbonate) is abrasion and corrosion resistant therefore the
products are able to be used in both indoor and outdoor industrial conditions/under harsh environments.
It can also be applied in areas with high impact loads without additional protective constructions due
to very good mechanical properties.
If abnormal or unusual environmental conditions occur due to accident etc, visual inspection is
recommended. To avoid electrostatic charge build-up, only the exterior of the product can be cleaned
with a damp cloth. If spare parts are required, these can be supplied by Moflash. If any failure occurs but
not caused by human factor, the product can be returned to Moflash for free repair or replacement during
warranty period.
CAUTION:
Not suitable to be used under circumstance which exposed or near to the source or concentrated acids,
aromatic hydrocarbons, halogens and ketones.
10.0 Conditions for Safety Use
i) This apparatus is suitable to be used only in ambient temperature as stated below:
ii) Other than by the product manufacturer, painting and surface finishing are not permitted by the
third party.
iii) When used in dusty atmosphere, cable entry devices or stopping plugs have to be selected and installed
carefully in order to maintain the IP rating (IP66) of the product.
Moflash part code S00583 - Issue 2
INSTALLATION &
TECHNICAL INFORMATION
PLEASE READ PRIOR TO INSTALLATION
X450 & LED450 Series
Industrial Xenon & LED Beacons
VISUAL SIGNALLING DEVICES
Website: www.moflash.com Email: [email protected]
Type
Ambient Temp
X450 and LED450
-40
0
C to +70
0
C
APPROVALS
AND
CONFORMITIES