DIP Switch / S1/S2

S1=OFF

S2=OFF

S1=ON

S2=OFF

S1=OFF

S2=ON

S1=ON

S2=ON

1st DIP

2nd DIP

3rd DIP

Alarm Stage 1

Alarm Stage 2

Alarm Stage 3

Alarm Stage 4

1

1

0(1)

OFF

Flash 

60 (75) times/min

Flash

75 (90) times/min

Steady light

0

1

0(1)

OFF

Rotary 

60 (75) times/min

Rotary

75 (90) times/min

Steady light

1

0

0(1)

OFF

Double Flash 

60 (75) times/min

Double Flash

75 (90) times/min

Double Flash 

100 (120) times/min

0

0

0(1)

OFF

Flash & Rotary 

60 (75) times/min

Flash & Rotary 

75 (90) times/min

Flash & Rotary 

100 (120) times/min

6.0 Wiring

General Requirement: 

Moflash  recommends  that  all  cables  and  cores  should  be  fully  identified

 

(suggest using cable from 2.0 to 2.5 mm²). Ensure that all nuts, bolts and screws are secured. Ensure that

 

only the right and certified cable glands are used and earthed correctly. Ensure that only the right and

 

certified stopping plugs are used to blank off unused gland entry points. In order to maintain the IP

 

rating of the product, we recommend SS316 for this application.

Cable Connection: 

The cable connection is connected with the terminal blocks on the electronic 

PCB/

Terminal Blocks

 assembly located in the flameproof enclosure of the 

Beacon Component

 (see picture 

2).  Cable connection should be carried out in accordance with relevant technical requirement. 

Remove Top Cover (Beacon Component)

Unscrew the six (6) M5 retained hex socket head screws of the 

Beacon Component 

(see picture two).   

This will release the cover from the base and allow the cover to hang on the

retaining wire strap.  Before replacing the cover, check that the

flameproof joints are clean and not damaged, the gasket is

still retained in its groove.

CAUTION:

 Before removing the cover, ensure the power

to beacon is isolated. Remove the four pieces of M5 socket

screws to open the cover.  Twist the cover gently clockwise

and anti-clockwise, whilst pulling away from the base, until it comes off. 

Replace the cover in a similar way, but operate in reverse manner as above.

Power Supply

 <

48v DC or 100-240v AC (50/60 Hz)

 

PCB Wiring Terminals

 (see picture 3).

Apply power supply to 12v/24v/36v/48v DC, 100-240v AC 

(50/60Hz) 

‘L’ & ‘N’

 (see picture 3).

7.0 Status Chosen and Flashing Frequency Adjustment
LED Beacon:

 The LED beacon provides flashing and rotary status to be selected. Use 

DIP Switch

 with 

3 binary codes on the 

LED Beacon PCB

 to select flashing or rotary status  (including steady status), 

the 3rd binary code is for high

and low frequency chosen. 

LED Status Selection Switch:

 

1st & 2nd DIP Switch: ON=1, OFF=0; 

3rd DIP Switch: HIGH=1, LOW=0,  

S1/S2: ON=Connect with O/COM,

OFF=Disconnect with O/COM

1.0 Introduction: 

 

The SB150-1 Explosion Proof sounder/beacon is certified for use and installation in Zone 

1 and Zone 2 areas with gases groups of IIA, IIB, IIC and temperature classification of T4~T6.  It specially

 

applies  to  Oil  &  Gas,  Offshore  Platform,  Chemical,  Petrochemical,  Refinery  and  Marine  Industries  etc.

 

Enclosure material is Stainless Steel. The sounder has 4 stage alarm tones which can be sent out. 64 tones are 

selectable.  Users can record sounds or customize sounds into the sounder by using 5 spare tones. Tone can be 

present during installation. At the same time 4 stages of alarm light can also be sent out.  

 

2.0 Explosion Proof Labelling: 

All products have a rating label with the following important information:

Product order no: eg SB1501RX05DCNNNAR (Refer to the datasheet for product order selection)

Input voltage:    

 

<

48v DC or 100-240v AC (50/60 Hz), Beacon: 

<

25W, Sounder: 

<

20W

Code:   

 

 

Ex d IIC T4~ T6 Gb, Ex tb IIIC T135

0

C~T85

0

C IP66

Nemko ATEX Certificate No:  

Nemko 13ATEX 1566X

ATEX Mark:

IECEx Certificate:   

 

IECEx-NEM 13.0036X

Gas Group and Category:   

II 2GD

CE Mark:  

 

 

Mark No: 0470

Warning:  

DO NOT OPEN WHEN AN EXPLOSIVE GAS ATMOSPHERE IS PRESENT

Finished product serial no (Include date of construction): ie. SB1500201080001

SB150

-GRP Sounder & Beacon, 

Day

-02, 

Month

-01, 

Year

-08, 

Product Serial Number

-0001

3.0 Type Approval Standard:

 

The SB150-1 series products have an EC Type Examination Certificate

 

issued by 

Nemko

 and have been approved to the following standards:  

 

EN 60079-0:2012 (IEC 60079-0:2011),

 

EN-60079-1:2007 (IEC 60079-1:2007) and EN 60079-31:2009 (IEC 60079-31:2008)

4.0 Zones, Gas Group, Category and Temperature Classification

The SB150-1 series products have been certified Ex d IIC T4~T6. This means that the units can be installed in 

locations with the following conditions:

Area Classification:

Zone 1:

 Explosive gas air mixture likely to occur in normal operation.

Zone 2:

 Explosive gas air mixture not likely to occur, and if it does, it

will only exist for a short time. 

Gas Groupings:

Group IIA Propane Group, IIB Ethylene Group and IIC Hydrogen and Acetylene

Equipment Category:

 2Gd    

Temperature Range: 

-40

0

C < Ta <70

0

C

5.0 Installation
General Requirement

: The product must be installed in accordance with the

latest issued relevant requirements in the EN60079-0 and EN60079-1 specification

or the equivalent IEC specification- Selection, Installation and Maintenance of

electrical apparatus for use in potentially explosive atmosphere.  Product installation

must be carried out in accordance with any local codes that may apply and

should only be carried out by a competent electrical engineer.

Location

: The location of the unit should be made with due regard to the

area over which the beacon warning signal must be visible.  The unit should

only be fixed to services that can carry the weight of the unit.

Mounting (Single Unit)

: The single unit only comes with one beacon and can be

mounted via a ‘U’ shaped stainless steel bracket.  It can be done using one 12mm

diameter and two 8.5mm diameter bolt holes in the center of the bracket (see picture 1).  The alignment and 

positions can be adjusted by loosening the two M8 screws, which fastened the stainless steel bracket to the 

sounder.  The sounder should be positioned such that dust, debris or water cannot enter into the horn opening.

Picture 2

Picture 3

Picture 1 

120.0

216.8

3.0

ø282.8

170.0

60.0

30.0

ø12.0

2-

ø8.5

412.3

207.3

205.0

ø150.0

DIP Switch

1    2    3

LED PCB

ON

L      SO     S2

    

N      S1

DIP Switch

1    2    3

XENON PCB

ON

L      SO     S2

    

N      S1