1.0 Introduction

The AE100M series is a weatherproof electronic sounder designed for use in harsh 

environmental  conditions  and  is  manufactured  from  UV  Stable  Polycarbonate

 

plastic. The sounder has a 3 stage alarm option & has 60 tone options that can be 

pre-selected. A stainless steel mounting bracket allows the unit to be pivoted through 

180 degrees to maximise directional audibility.

2.0 Voltage Classifications

The AE100M is available for the following voltage ranges:

AE100M-02 – 12-48v DC or AE100M-04 – 100-240V AC

3.0 Installation

General Requirements

• 

Installation must be carried out in accordance with the latest codes and regulations

 

  by a qualified electrician.

• 

Ensure power is disconnected prior to installation or maintenance.

• 

Environmental exposure conditions during installation should be dry, not moist

 

  or wet.

• 

Avoid mounting the sounder where it will be subject to excessive vibration.

Location

The location of the unit should be made with due regard to the area over which the 

sounder warning signal must be audible. The unit should only be fixed to services 

that can carry the weight of the unit.

Mounting

The  unit  mounts  via  a  ‘U’  shaped  stainless  steel  bracket  by  using  one  8mm

 

dia and two 6mm dia bolt holes in the centre of the bracket (see picture 1). The

 

alignment and positions can be adjusted by loosening the two M6 screws, which

 

fasten the stainless steel bracket to the sounder. The sounder should be positioned 

such that dust, debris or water cannot enter into the horn opening.

4.0 Wiring

General Requirement

Moflash recommends that all cables and cores should be fully identified (suggest 

using cable from 2.0 to 2.5 mm²). Ensure that all nuts, bolts and screws are secured. 

Ensure that only the right and certified cable glands are used and earthed correctly. 

Ensure that only the right and certified stopping plugs are used to blank off unused 

gland entry points. In order to maintain the IP rating of the product, we recommend 

SS316L for this application.

Cable Connection

The cable connection is to terminals on the

PCB located within the enclosure of the

sounder. Cable connection should be carried

out in accordance with relevant technical

requirements (see picture 1)

For AC supply - connect to terminals marked ‘L’ & ‘N’.

For DC supply - connect ‘+’ to ‘L’ and ‘-‘ (0v) to ‘N’.

Alarm stages - terminals ‘S0’ (common) ‘S1 & S2’

(refer to table overleaf). With ‘D’ or ‘Dly’ as the delay function.

Do not connect AC or DC to S0, S1, S2 or D.

Removal of End Cover

Unscrew the four (4) M5 retained hex socket head screw (see diagram 2). Twist 

the cover gently clockwise and anti-clockwise, whilst pulling away from the body, 

keeping the cover parallel to the body until it comes free. This will allow the cover to 

hang on its retaining strap. Before replacing the cover, check the joints are clean and 

not damaged, the gasket is retained in its groove.

4 - M5

SOCKET

SCREWS

Picture 1

Diagram 2

Diagram 1