INSTALLATION & 

TECHNICAL INFORMATION 

PLEASE READ PRIOR TO INSTALLATION 

Website: www.moflash.com        Email: [email protected]

APPROVED

 

AND

CONFORMITIES

Alarm Stages

The alarm stages are set as follows:

Refer to Tone Selection Sheet ref: S00600 for Tone Selection and Volume Control.

Sound Pause Option

Briefly close the loop between ‘S0 – Dly’ for 1 second minimum each time to give the

 

required pause interval. The sound automatically restarts at the end of the interval.

5.0 End of Line Monitoring

An  end  of  line  monitoring  diode  or  an  end  of  line  monitoring  resistor  can  be

 

connected across the 24V+ and 0 terminals. Resistor values for the End of Line will be 

determined by the customer with a minimum value of 1.2kΩ

6.0 Maintenance

Little or no maintenance is required during the normal working life of the product. The 

Moflash Exd enclosures are resistant to most acids, alkalis and chemicals and have been 

designed to withstand severe weather conditions. However it is suggested that to avoid 

the possibility of a potential electrostatic charge build up, the exterior of the product is 

periodically  wiped  down  with  a  clean  damp  cloth. At  this  point  a  visual  inspection  is

 

recommended to ensure that the product is in good working order and no damage has been 

sustained during its normal operation.

7.0 Conditions for Safety Use

i) This apparatus is suitable to be used only in ambient temperature as stated below:

ii) Other than product manufacturer, painting and surface finishing are not permitted  

 

  by the third party.

iii) When  used  in  dusty  atmosphere,  flameproof  cable  entry  devices  or  stopping  plugs 

 

  have  to  be  selected  and  installed  carefully  in  order  to  maintain  the  IP  rating  (IP66)

 

  of the product.   

 

   

 

 

             

Moflash part code AE100M-S00599-Issue 2

AE100M Series - Weatherproof Sounder

PC - Polycarbonate

AUDIBLE SIGNALLING DEVICE

Type

Ambient Temp

AE100M

-40

0

C to +70

0

C

  

Stage

Apply Power To

Termination Connection

Tone

1

L & N

-

No sound

2

L & N

S0

 to 

S1

 (Factory pre-set)

Set by 

DIP SW1

3

L & N

S0

 to 

S2

Set by 

DIP SW2

4

L & N

S0

 to 

S1 

&

 S2

Set by 

DIP SW3

No of times

Pause Interval

1

1 minute

2

5 minute

3

10 minutes - Closing the loop again for 1 second during this interval

automatically restores the sound.