INSTALLATION &
TECHNICAL INFORMATION
PLEASE READ PRIOR TO INSTALLATION
Website: www.moflash.com Email: [email protected]
APPROVED
AND
CONFORMITIES
Alarm Stages
The alarm stages are set as follows:
Refer to Tone Selection Sheet ref: S00600 for Tone Selection and Volume Control.
Sound Pause Option
Briefly close the loop between ‘S0 – Dly’ for 1 second minimum each time to give the
required pause interval. The sound automatically restarts at the end of the interval.
5.0 End of Line Monitoring
An end of line monitoring diode or an end of line monitoring resistor can be
connected across the 24V+ and 0 terminals. Resistor values for the End of Line will be
determined by the customer with a minimum value of 1.2kΩ
6.0 Maintenance
Little or no maintenance is required during the normal working life of the product. The
Moflash Exd enclosures are resistant to most acids, alkalis and chemicals and have been
designed to withstand severe weather conditions. However it is suggested that to avoid
the possibility of a potential electrostatic charge build up, the exterior of the product is
periodically wiped down with a clean damp cloth. At this point a visual inspection is
recommended to ensure that the product is in good working order and no damage has been
sustained during its normal operation.
7.0 Conditions for Safety Use
i) This apparatus is suitable to be used only in ambient temperature as stated below:
ii) Other than product manufacturer, painting and surface finishing are not permitted
by the third party.
iii) When used in dusty atmosphere, flameproof cable entry devices or stopping plugs
have to be selected and installed carefully in order to maintain the IP rating (IP66)
of the product.
Moflash part code AE100M-S00599-Issue 2
AE100M Series - Weatherproof Sounder
PC - Polycarbonate
AUDIBLE SIGNALLING DEVICE
Type
Ambient Temp
AE100M
-40
0
C to +70
0
C
Stage
Apply Power To
Termination Connection
Tone
1
L & N
-
No sound
2
L & N
S0
to
S1
(Factory pre-set)
Set by
DIP SW1
3
L & N
S0
to
S2
Set by
DIP SW2
4
L & N
S0
to
S1
&
S2
Set by
DIP SW3
No of times
Pause Interval
1
1 minute
2
5 minute
3
10 minutes - Closing the loop again for 1 second during this interval
automatically restores the sound.