Installation
20
10/06 AWB2300-1433GB
The following conductor cross-sections can be used.
Table 5:
Maximum conductor cross-sections of the motor
cables
Mounting for low motor currents
At the ZEV-XSW-25, the cables for motors operating with a
current < 1 A are looped. The number of loops is determined
by the rated operational current of the motor
I
N
(
Figure 10:
Loops of the motor feed cables
Table 6:
Number of loops
I
N
= rated operational current of the motor
I
e
= current setting at the ZEV
Current sensor
Feedthrough
O
Conductor cross-section
mm
mm
2
AWG
ZEV-XSW-25
6
10 solid or multi-wire
10
ZEV-XSW-65
13
50 fine-wire
1
ZEV-XSW-145
21
150 fine-wire
2/0
I
N
[A]
0.25 to 0.4
0.41 to 0.62
0.63 to 1.24
Number of
loops
4
3
2
I
e
4
x
(0.25 to 0.4)
3
x
(0.41 to 0.62)
2
x
(0.63 to 1.24)