Establishing the connection
between PC and XC600
07/04 AWB2700-1428GB
24
The IP address consists of four groups with three-digit decimal
numbers that are separated by a full stop character. You can enter
numbers from 192.168.119.1 to 192.168.119.254 as the address.
The first three groups must match the default address in the
XC600. The numbers in the last group must be different:
If another device is to be included in the network, in addition to
the PC and XC600, then it may be necessary to change the values.
X
Enter the default mask 255.255.255.0 of the XC600 in the
SUBNETMASK field.
X
Click OK to confirm your entry.
XC600 configuration
Assign the IP address and the SUBNETMASK to the PLC:
X
Use the operator module to select the Network menu via MAIN
MENU
r
DEVICE
r
NETWORK
The precise operating steps are described in the Chapter “Menu
overview of the operator module” from Page 45.
X
Select menu item IP ADDRESS.
The default address 192.168.119.001 will be displayed.
X
Change the address to 192.168.119.004.
X
Select the menu item SUBNETMASK.
The default mask 255.255.255.000 will be displayed. If a different
value appears here, you will have to correct it.
Creating the connection between PC and XC600
Hardware
X
Connect the PLC with the PC, e.g. by means of a standard
crossover Ethernet cable.
Software
Use XSoft to specify the communication parameters. To do this,
proceed as described below. Additional notes can also be found in
the chapter “Online Communication Parameters” in the XSoft
(H1437G.pdf) manual.
The same IP address that you have assigned to the PLC
(192.168.119.004) must now be assigned to the gateway.
Procedure:
X
In XSoft, choose the menu item “Online
r
Communication
Parameters”.
The PC will log into the PLC. An error message will be output if the
connection does not exist or is faulty. The following window
should appear after confirmation:
The “Local” definition states the “Gateway” is located in the PC.
X
Click the “New” button.
h
The PC uses XSoft to communicate via a gateway (server)
with the PLC runtime system of the XC600 (
a
following
diagram).
Figure 34 : Connection between PC and XC600
Figure 35 : “Communication Parameters” main window
h
If the “Local_” point is missing in the “Channels”
window or if a value (address) is present in its place, click
on “Gateway” and select the “Local” connection
(channel) Figure35.
Gateway
PLC runtime system
XC600
PC