Universal Function Blocks
56
10/00 AWB27-1301-GB
Description of the
function block outputs
Inputs
Table 11 lists in alphabetical order the function block inputs
that can occur in the individual versions. In certain versions,
some inputs may not be available on account of the limited
functionality of the function block.
Table 11: Inputs
Inputs
Data
type
Range of
values
Description
acd
BOOL
0/1
Request to access high-priority data at a
secondary station.
acd_length
USINT
1 to 220
ACD length
acd_offset
USINT
0 to 219
ACD offset
acd_subaddress
USINT
0 to 255
ACD subaddress
address_of_
station_1
USINT
1 to 254
Address of the 1st secondary station
address_of_
station_n
USINT
1 to 254
Address of the nth secondary station
auto
BOOL
0/1
Automatic mode
baudrate
UINT
R
Transmission speed (observe the admissible values
for the telecontrol card/module)
300, 600, 1200, 2400, 4800, 9600, 19200
command
USINT
10 to 32
Command code for the offered service
(see Table 7)
cyclic
BOOL
0/1
Selects a polling cycle (one-off polling of all
stations)
destination_
offset
USINT
0 to 219
Specifies the destination offset address for
variable length frames
Содержание S40-AM-TL
Страница 7: ...10 00 AWB27 1301 GB 4 ...
Страница 9: ...6 10 00 AWB27 1301 GB ...
Страница 13: ...10 10 00 AWB27 1301 GB ...
Страница 55: ...Basic Function Blocks 52 10 00 AWB27 1301 GB ...
Страница 103: ...100 10 00 AWB27 1301 GB ...
Страница 107: ...104 10 00 AWB27 1301 GB ...
Страница 113: ...10 00 AWB27 1301 GB 110 ...