INSTALLATION - UNIT MOUNTING / PIPING / ELECTRICAL CONNECTIONS

INSTALLATION

Unit Mounting

1. Open front panel and line up end compartment with roughed-

in piping and position unit at ceiling or wall location. (Hinged 

cabinet doors may be removed to facilitate unit installation.)

2. Fasten floor or wall mounted unit to wall studs through 

the four mounting holes in the back of the unit. For ceiling 

mounted units sizes 002-006, suspend four 1/4" threaded 

hanger studs from ceiling joists to match mounting holes in 

back of unit and fasten with lockwashers and hex nuts. (For 

sizes 008-014, use a 3/8" threaded rod.)

Perma-Lap

®

 Frames

A Perma-Lap

®

 frame (see Figure 11.3 on page 10) provides 

a finished appearance to a recessed wall or ceiling cabinet 

unit heater.  The installation is easy and assures a perfect fit 

by neatly framing the heater and covering any irregularities 

between the heater and the opening in the wall or ceiling.  

Because the bond between wall or ceiling surfaces and the 

Perma-Lap® framing is permanent, there is no opportunity for 

air leakage which can cause wall streaking.

Since the enclosure front panel is never in contact with the wall 

or ceiling, servicing the heater involves simply removing the 

heater front panel and leaving the Perma-Lap® and cabinet 

enclosure permanently fixed in the recess opening.

Perma-Lap

®

 frames allow flexibility in recessing depth. Enclosures 

may be flush, recessed or partially recessed. Desired unit projection 

on partially recessed units is accomplished by positioning the unit 

within the Perma-Lap

®

 frame. The four sided Perma-Lap® frame 

has a 3/8” projection and a 1 ½” width.

Piping

1. On standard coil (single row), connections are 3/4" MPT on 

unit sizes 002 through 006.

  On high capacity coil (2 row), connections are 5/8" ID sweat 

on unit sizes 002 through 006. On high capacity coil (3 & 4 

row), connections are 3/4" NPT on unit sizes 002 through 006.

  On unit sizes 008 through 014, either standard or high capacity 

coil, connections are 1" NPT. On high capacity coil (3 & 4 row), 

connections are 1" NPT on unit sizes 008 through 014.

2. Supply and return lines should be adequately sized to handle 

heating requirements under maximum load.

3. Attach air vent fitting at the high point of the piping in the unit 

on hot water systems.

4. Install piping to provide for expansion and contraction 

normally encountered with temperature changes.

Electrical Connections

1.  Installation of wiring must conform with local building 

codes, or in the absence of local codes, with the National 

Electric Code ANSI/NFPA 70 - Latest Edition. Unit must 

be electrically grounded in conformance to this code. In 

Canada, wiring must comply with CSA C22.1, Electrical 

Code.

2.  Electric wiring must be sized to carry the full load amp draw 

of the motor and any controls that are used with the unit 

heater. Overcurrent protectors should be sized based on 

motor current rating shown on the unit serial plate, and    

applicable national electric code procedures.

 

All units are provided with an electrical junction box. Make 

wiring connections from 115V/60Hz/1Ø building service to 

control box as shown on wiring diagram furnished with the 

unit.  

 

 

Any damage to or failure of Modine units caused by  

 

incorrect wiring of the units is not covered by Modine’s  

 

standard warranty.

3.  Location of room thermostat, when supplied, should be in   

the natural circulating path of room air. Mount thermostat    

about five feet above floor level where it will not be affected  

by heat from the unit or other sources of drafts that would   

prevent it from properly controlling room temperature. See   

instructions packed with the thermostat. 

4.  With ceiling mounted units, a multi-speed remote fan 

switch is supplied as standard. The switch can be recessed 

into a standard 2 x 4 electrical wall box.

 

Failure to wire this unit according to this wiring diagram may 

result in injury to the installer or user. For deviations, contact 

the factory.

 CAUTION

Figure 3.1

Standard Wiring Diagram for Cabinet Unit Heaters 

 CAUTION

1. Do not reuse any electrical component which has been  

 

  wet. Such component must be replaced.

2. Do not operate the units within steam pressure greater  

 

  than 10 psig. Steam pressure must be 10 psig. or lower    

  to avoid excessive discharge air temperatures that could    

  cause burns or personal injury.

 WARNING

1. Disconnect power supply before making wiring connections 

to prevent electrical shock and equipment damage.

2. All appliances must be wired strictly in accordance with 

wiring diagram furnished with the appliance. Any wiring 

different from the wiring diagram could result in a hazard to 

persons and property.

3. Any original factory wiring that requires replacement must 

be replaced with wiring material having a temperature 

rating of at least 105°C.

16 AWG 

16 AWG

L1

L2

MAIN

GROUND

Factory Installed Disconnect Option or

1

2

AQUASTAT

ACCESSORY

MOTOR

STARTER

4

3

REQUIRED FOR

SIZES 008 - 014

ACCESSORY

F1

F2

SPEED

CONTROL

FIELD INSTALLED

CONTROL VALVE

(ACCESSORY OR

BY OTHERS)

FIELD INSTALLED

THERMOSTAT

WHT

BLK

WHT

BLK

MOUNT INSIDE J-BOX

OPTIONAL MOTOR PLUG 

AND SOCKET CONNECTIONS 

Rated Amps

2.5 A
5.0 A

RED

BLK

Terminal 3 Terminal 4

WHT
RED

GRN

Ground

10.0 A

BLK

WHT

Motor Type

Shaded Pole

PSC

High Static

See Below Motor Key For Motor

Information and Wiring Configuration

Ground

N / A

N / A

FIELD INSTALLED

MOTORIZED DAMPER

(ACCESSORY)

Motorized Damper Option or

Factory Installed

Return Air Option or

115V / 60HZ /

1PH POWER

CIRCUIT

BREAKER

BY OTHERS

FIELD INSTALLED

DISCONNECT

Содержание Model FC series

Страница 1: ...nsers are warranted for operation at hot water pressures up to 200 lbs per sq in gauge and or temperatures up to 240 F or steam pressures up to 10psig for one row coils only The 3 4 row condensers are...

Страница 2: ...blanketed by their air streams 8 Mounting height is critical for optimum performance Refer to Mounting Height on page 4 before installation WARNING 1 Disconnect power supply before making wiring conn...

Страница 3: ...ring must comply with CSA C22 1 Electrical Code 2 Electric wiring must be sized to carry the full load amp draw of the motor and any controls that are used with the unit heater Overcurrent protectors...

Страница 4: ...unit heaters when operated with steam pressures other than 2 pounds or with water at other than entering temperature of 220 F 1 3 1 2 1 1 1 0 9 8 7 6 5 CORRECTION FACTOR R AVERAGE WATER TEMP F 150 160...

Страница 5: ...Arrangement 98 Model CW Arrangement 97 Model CW Arrangement 96 Model CW Arrangement 90 Model CW Arrangement 00 Model CW Arrangement 06 Model CW Arrangement 07 Model CW Arrangement 58 Model CW Arrangem...

Страница 6: ...r left or right side connection with left hand piping as factory standard Power Assembly STD Blower platform blower and blower motor on all sizes are removable as a single unit A direct drive multi sp...

Страница 7: ...NPT 1 NPT 1 NPT 1 NPT Blowers Direct Drive No Dia x Width Inches 1 5 1 4 x 7 1 5 3 4 x 7 2 5 1 4 x 7 2 5 3 4 x 7 3 5 3 4 x 7 3 5 3 4 x 7 4 5 3 4 x 7 4 5 3 4 x 7 High Speed Rpm 1625 1625 1625 1625 1625...

Страница 8: ...12 10 7 5 7 8 47 5 8 39 5 8 9 3 4 205 012 83 3 4 28 12 10 7 5 1 8 59 5 8 51 5 8 9 3 4 240 014 83 3 4 28 12 10 7 5 7 8 59 5 8 51 5 8 9 3 4 240 Unit Size Approx Unit Weight lbs Figure 8 1 Floor Model FC...

Страница 9: ...3 4 240 014 83 3 4 28 12 5 7 8 59 5 8 9 3 4 240 Table 9 1 Cabinet Dimensions inches Table 9 2 Filter Dimensions inches Model Size Filter Size 002 8 1 2 x 20 3 4 x 1 2 003 8 1 2 x 25 3 4 x 1 2 004 8 1...

Страница 10: ...COIL CONNECTION DIMENSIONS 3 4 ROW COIL UNITS Table 10 1 10...

Страница 11: ...Duct Collar Table 11 2 Model FC 25 and 100 Fresh Air Duct Collar All dimensions are in inches Includes 3 4 top and bottom duct flanges for duct connection Outside Air Percentage 25 100 1 3 or 6 2 4 o...

Страница 12: ...cleaned frequently Do not use any commercial solvent that could deteriate the coil and do not use any liquid or steam sprays that could damage electrical components Good filter maintenance will minimi...

Страница 13: ...SHIPMENT FROM SELLER These warranties are issued only to the original owner user and cannot be transferred or assigned No provision is made in these warranties for any labor allowance or field labor p...

Отзывы: