21
9-511
PERFORMANCE
Certified Tube Lengths (ft.)
Table 21.2 - Utilities
Recommended
Mounting Height (ft.)
➀
20, 30
U-Tube
Straight Tube
Spot or Area
Heating
Total Building
Heating
20, 30, 40
50, 60
Recommended
Tube System
Application
➀
Table 21.1 - Performance
Input MBH
50
60
75
100
125
150
175
200
20, 30,
30, 40, 40, 50,
50, 60,
50, 60,
40 50
➁
60
70
70
10 – 12 10 – 12 12 – 14
➂
12 – 14
15 – 22
15 – 22
18 – 28
20 - 30
➀
Recommended Mounting Height and Tube System Applications are meant as a general guide and are adjusted to meet the requirements of the actual application.
The applications are as follows:
-- Spot or Area Heating is an application where occupant comfort is the goal and occupant(s) are either relatively stationary (Spot - Example: small work cell or dispersed over
a slightly wilder range than with Spot Heating (Area - Example: assembly line). Mounting height is typically at the low end of the range shown above.
-- Total Building Heating is an application where average space temperature is to be maintained, however due to the significant temperature gradient differences on
long straight tube systems, areas may exist where direct occupant comfort is not achieved.
➁
TLP 100 not available for Propane Gas operation at 50 ft. tube system length.
➂
TLP 75 not available for Propane Gas operation at 40 ft. tube section length.
Electrical Rating
Gas Connection
(inch)
Minumum Gas Inlet
Pressure ("W.C.)
Maximum Gas
Pressure ('W.C.)
Manifold Gas
Pressure ("W.C.)
Tube/Vent
Diameter (inch)
115V/60Hz/1Ph
50-60 btu = 1.71 total amps
75-200 btu = 2.66 total amps
1/2 NPT
7.0 (natural gas)
11.0 (propane gas)
14.0
3.5 (natural gas)
10.0 (propane gas)
4 (O.D.)