2.2. Boiler Room
The boiler room shall meet requirements of the PN-87/B-02411 standard.
Here are some of the most important of them:
•
waterproof flooring
•
steel or wooden doors lined with sheet metal, opening outwards
•
21x21 cm air supply hole in the bottom part of the boiler room
•
at least 14x14 cm exhaust hole in the upper part of the boiler room
Equipment:
•
tap
•
sewage well
•
sing
Forced ventilation must not be used.
2.3. Boiler Installation
Boiler installation shall be performed by an engineer with appropriate
qualifications and experience (we advice you to seek help from representative
centres, whose installers have undergone training in Moderator Sp. z o.o.).
A faulty installation may cause premature wear of the boiler and threatens fire or
may cause an explosion.
Moderator boilers are delivered in assembled state. Boiler may be
positioned directly on the floor with 1 gradient towards the front wall (the top
point of the boiler after the installation shall be the place close the supply pipe).
During boiler installation, it is necessary to ensure its accessibility in such a
way, so that boiler room walls do not render fuel charging, grate cleaning and
access to the side washout and fan difficult. Recommended distances are: min.
80cm for side walls and 100 cm for the front wall.
2.4. Connecting to the Chimney
Boiler’s smoke breeching shall be seated directly in the chimney, and
after installation sealed along the contact line of: smoke breeching sheet metal –
chimney brick. It is necessary to ensure access to washout doors installed on
side walls of the smoke breeching, which are intended for boiler’s rear part
cleaning.
Chimney outlet shall be located 75 cm above the roof ridge. Square or
rectangular chimneys shall be made of burnt brick; round chimneys (usually