An abnormal flame pattern will likely be the result of incorrect settings (jet size, burner aeration
collar). Check that these are correct before proceeding. If an abnormal flame pattern is still present,
please contact Escea.
It is the responsibility of the installer to ensure a correct flame pattern.
F7 Wall Linings
The final wall lining can only be commenced after all previous applicable sections have been completed.
The appliance must be installed prior to and behind the finished wall surface. Allow clearance for any
plasterboard, tiles, or other finishing materials that may be intended for the finished wall surface. Wall
finishing materials must not encroach upon the minimum cavity clearances given in previous sections.
The wall board that lines the outside of the opening can be normal plaster board and does not need
to be non-combustible. The plasterboard is to protrude beyond framework as shown in the following
diagram.
Note: The final wall lining must not encroach within the specified dimensions in this section. These
dimensions indicate the opening required in the wall lining. Encroaching on the minimum cut out
dimension may inhibit the future serviceability of the fire.
KS-Series Minimum Wall Lining Dimensions
Note: The wall lining directly above the appliance will get warm and hence may discolour paint finishes
that are susceptible to temperature damage. The heat may also distort vinyl wall coverings.
For durability
of finishes and surfaces you should contact the relevant manufacturer for their specification and avoid
materials with temperature ratings of less than 80deg C.
The wall lining can be fixed to the gib fixing bracket (shaded below). There are four areas on the