© MOBATIME
70 / 84
800847.08
A.2
Connections (rear view)
1 D
C
in
2 G
N
D
DTS Link
TX RX
9 A
lar
m
1
0
A
la
rm
3 D
C
F
in
+
4 D
C
F
in
-
5 V
B
+
6 G
N
D
7 D
C
F
o
u
t+
8 D
C
F
o
u
t-
24V DC +20/-10%
max: 10W
DTS 4128.timeserver connections
For technical data see in Appendix "F Technical data"
Clamp Connection
Description
Earth connection
1
DC in power
Input for external DC supply
Ground
2
DC in power supply GND
3
DCF input +
DCF input, e.g. for connection of a GPS 4500
– or DCF–
receiver with current loop output.
4
DCF input -
5
DC
DC output for GPS 4500
DC in voltage -2V, max. 400mA
6
DC output GND
7
DCF
DCF output, current loop passive,
Umax= 30VDC, I
on
= 10..15mA, I
off
< 1mA @20VDC
8
DCF output -
9
Alarm relay
Alarm contact, open when alarm is active
Switching load: 30 W (125 VDC or 1 A), e.g. 1 A @ 30 VDC
or 60 VA (150 VAC or 1 A), e.g. 0.5 A @ 120 VAC
10
Alarm relay
DTS link
Optical connection to a 2
nd
DTS 4128.timeserver
Mini GBIC plug-in
24 V
+20%/-10%