Category 2 Parameters - System Settings (press PROGRAM   to access this category)

Category 1 Parameters - Programmable Thermostat Settings

CM707/702/701 - InSTAllATIOn GuIde

You have now installed the Programmable Thermostat. For gas boiler applications, the factory system settings 

will not need to be changed (for other applications see below). You can now use the 

uSeR GuIde

 to program 

the unit and demonstrate how it works to the homeowner.

using the Programmable Thermostat for Specific Applications

Application

Gas Boiler (<30kW)

Oil Boiler

Thermal Actuator

Zone Valve

Electric Heating 

(resistive load 3-5A)

Settings

Cycle /Hour

6

3

12

6

12

Minimum ON 

time

1

4

1

1

1

What to change

Note: All parameters listed below belong to 

category 2 – system parameters (see Installer 

Parameter Table)

No changes required

Set 1:Ot parameter to 4

Set 2:Cr parameter to 3

Set 2:Cr parameter to 12

No changes required

Set 2:Cr parameter to 12

entering the Installer Mode

1.

  Press the 

OFF 

button.

2. 

Press  and  hold  the 

  button  and  the  two 

PROGRAM

   or   buttons together. 

3. 

The unit will display the first parameter of installer 

parameter group category 1 (from Parameter No. 1 

to 19).

4. 

Press the     or   button to change the factory 

setting.  The  display  will  flash  indicating  that  a 

change has been made.

5. 

Press the green 

 button to confirm the change. 

The display will stop flashing.

6. 

Press the     button to go to the next parameter.

7. 

Press  the 

PROGRAM

 

  button  to  go  to  Installer 

parameter group category 2 (from Parameter No. 1 

to 5).

8. 

To  exit  installer  mode,  press  the 

AuTO

MAn 

or 

OFF 

button.

 

 

AM-PM / 24hr 

Display

Reset Time/ Temp 

Program

Upper Temp Limit

Lower Temp Limit

Temperature Offset

Proportional Band 

Width

Reset Parameters to 

Factory Defaults 

Minimum boiler ON 

time

Cycle Rate

Pump Exercise

1:CL

2:rP

6:UL

7:LL

12:tO

13:Pb

19:FS

1:Ot

2:Cr

5:PE

notes: 

Always remember to press the green 

 button to confirm that you want to store the new Installer Set-Up 

setting. To exit the Installer Set-Up Mode press the 

AuTO 

or 

MAn 

button.

System Commissioning

To enter the diagnostic mode press the 

OFF 

button then press and hold the   button for 5 sec. The unit will enter 

the user settings mode. Next press and hold the   and     buttons together. The unit will hold the relay on 

for 5 minutes and the following information will be available on the display: model ID, date code (WW/YY) and 

checksum. To view this info press the     or   button.

Display

24

1

35

5

0

1.5

1

1

6

0

Factory default Settings

Parameter

Parameter 

no.

Description

 

 

24 hr clock display 

format

Time / Temp profile set to 

factory default

Changes to 0 when one 

of the time/temp profiles 

are changed

35°C Upper Temp. Limit

5°C Lower Temp. Limit

No temperature offset

Proportional band of 1.5 

degree

All settings at factory 

defaults.

Changes to 0 when one of 

the parameter is changed

1 minute minimum ON 

time

6 cycles per hour (cph)

Pump exercise disabled

Display

12

0

1

21-34

6-20

-3..3

1.6..3

0

1

2..5

3,9,12

1

Optional Settings

Description

 

 

12 hr – AM/PM clock 

display format

Time / Temperature are as 

programmed

To restore the factory 

profile set to 1

21°C to 34°C adjustment 

in 1°C steps

6°C to 21°C adjustment in 

1°C steps

-3°C to +3°C adjustment 

in 0.1°C steps

1.6°C to 3.0°C adjustment 

in 0.1°C steps

Settings are as modified 

above

To restore the factory 

profile set to 1

Selection of 2, 3, 4 or 5 

minutes minimum ON time

Selection of 3, 9 or 12 cph

Pump exercise enabled

COPY

DAY

DAY

1..4

1

2

3

4

5

6

7

AUTO

MAN

OFF

1 2

2

2

COPY

DAY

DAY

1..4

MANAUTO

1

2

3

4

5

6

7

AUTO

MAN

OFF

1

Installer Parameters Table