STERAPORE 5600 Series (FF) Instruction Manual
44/59
Equipment
Inspection Item
Normal State
Maintenance and
Inspection
Disinfection tank
Check chlorinated compound
(if solid chlorinated compound is
used)
Sufficient amount of chlorinated
compound
Chlorinated compound
replenishment
NaClO tank
State of remaining amount
At or above the specified volume
NaClO replenishment
Dilution water
tank
State of water level
At the specified water level
Inspection of the feedwater line
Coagulant tank
State of remaining amount
At or above the specified volume
Coagulant consumed as specified
Coagulant replenishment
Flow adjustment of the coagulant
injection pump
Table 6-3
Items Controlled Using Measurement Devices and Responses to be Taken
Object
Control Range
Outside the Controlled Range
Response
Trans membrane
pressure
Initial value -15 kPa or
higher
Initial value -15 kPa or lower
Perform maintenance
cleaning (automatic)
Membrane scour
aeration amount
Calculated at 75 to
150 m
3
/(m
2
•h)
75 m
3
/(m
2
•h) or less
150 m
3
/(m
2
•h) or more
Increase the air flow rate
Decrease the air flow rate
Filtration flow rate
Calculated using the set
value
(0.2 to (0.8) m/d)
At or above the set value
At or below the set value
Decrease the filtration
amount
Increase the filtration amount
DO
(Aerobic tank)
About 1 to 4 mg/L
1 mg/L or less
4 mg/L or more
*
Increase the air flow rate.
Reduce the MLSS
concentration (within the
control range).
Reduce the air flow rate.
Increase the MLSS
concentration (within the
control range).
MLSS
About 5,000 to
10,000 mg/L
5,000 mg/L or less
10,000 mg/L or more
Decrease the amount of
sludge extraction.
(Take note of a lack of a DO
due to an increase in MLSS
concentration.)
Increase the amount of
sludge extraction.
(Take note of an increase in
DO due to a decrease in
MLSS concentration.)
ORP
(Anoxic tank)
About -200 to 0 mV
-200 mV or less
0 mV or greater
(To prevent putrefaction)
Increase DO, decrease the
MLSS concentration, and
increase circulation ratio in
the aerobic tank.
Decrease DO, increase the
MLSS concentration, and
decrease circulation ratio in
the aerobic tank.
*
DO in membrane tanks of separate MBR systems tends to be 4 mg/L or greater, in which case, determine the air
flow rate with a priority on ensuring the air flow rate for membrane cleaning, leaving DO as it stands.