23
-
r
h
Model
Item
All models
One way piping length (
R
)
30 m
Outdoor
unit is lower
20 m
Outdoor unit
is higher
20 m
Vertical
height
difference (h)
(4)
Limitations for one way piping length and vertical
height difference.
(m) Installation space
1)
Walls surrounding the unit in the four sides are not acceptable.
2)
There must be a 1-meter or larger space in the above.
3)
When more than one unit are installed side by side, provide a 250mm or wider interval between them as a service space.
In order to facilitate servicing of controllers, please provide a sufficient space between units so that their top plates can
be removed easily.
4)
Where a danger of short-circuiting exists, install guide louvers.
5)
When more than one unit are installed, provide sufficient intake space consciously so that short-circuiting may not occur.
6)
Where piling snow can bury the outdoor unit, provide proper snow guards.
Intake
(
)
Intake
Outlet
L
3
L
2
L
4
L
1
Example installation
Size
L1
L2
L3
L4
Open
100
100
250
280
75
80
Open
280
Open
80
250
180
Open
80
Open
(mm)
The height of a wall is 1200mm or less.
service
space
1
2
3
4