10

Fig. 8-3

B

A

C

1

1

D

E

2

F

G

F

B

1

Fig. 8-4

8. Installing the grille

8.2. Preparing to attach the grille (Fig. 8-2)

• With the gauge supplied with this kit, adjust and check the positioning of the unit

relative to the ceiling. If the unit is not properly positioned in the ceiling, there may
be air leaks, condensation may form, or the up/down vanes may not operate cor-
rectly.

• Make sure that the opening in the ceiling is within the following tolerances:

576 

×

 576 - 620 

×

 620

• Make sure that step A is performed within 27-32 mm. Damage could result by fail-

ing to adhere to this range.

A

Main unit

B

Ceiling

C

Gauge (Accessory)

D

Ceiling opening dimensions

8.2.1. Removing the intake grille (Fig. 8-3)

• Slide the levers in the direction indicated by the arrow 

1

 to open the intake grille.

• Unlatch the hook that secures the grille.

* Do not unlatch the hook for the intake grille.

• With the intake grille in the “open” position, remove the hinge of the intake grille

from the grille as indicated by the arrow 

2

.

8.2.2. Removing the corner panel (Fig. 8-4)

• Remove the screw from the corner of the corner panel. Slide the corner panel as

indicated by the arrow 

1

 to remove the corner panel.

A

Intake grille

B

Grille

C

Intake grille levers

D

Grille hook

Fig. 8-2

E

Hole for the grille’s hook

F

Corner panel

G

Screw

8.3. Installing the grille

• Please pay attention because there is a restriction in the attachment position of the

grille.

8.3.1. Preparations (Fig.8-5)

• Install the two enclosed screws with washer in the main unit (at the corner refriger-

ant pipe area and at the opposite corner) as shown in the diagram.

A

Main unit

B

Detailed diagram of installed screw with washer (accessory).

15~20

A

B

(mm)

Fig. 8-5

8.3.2. Temporary installation of the grille (Fig.8-6)

• Align the electric component box of the main unit and the receiver of the grille, and

then temporarily secure the grille using the bell shaped holes.

* Make sure that the lead wiring of the grille does not get pinched between the

grille and the main unit.

A

Main unit

B

Electric component box

C

Screw with washer (for temporary use)

D

Screw with washer (Accessory)

E

Grille

F

Bell shaped hole

G

Receiver

8.3.3. Securing the grille (Fig. 8-7)

• Secure the grille to the main unit by tightening the previously installed two screws

(with captive washer) as well as the two remaining screws (with captive washer).

* Make sure that there are no gaps between the main unit and the grille or the

grille and the ceiling.

A

Ceiling

B

Main unit

C

Grille

D

Make sure that there are no gaps.

A

C

D

B

Fig. 8-6

Fig. 8-7

Содержание SLZ-A18AR

Страница 1: ...korrekt bruk innan luftkonditioneringen installeras INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeer...

Страница 2: ...esult in a fire or an electric shock Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the s...

Страница 3: ...1 2 Washers with insulation 4 Washers without insulation 4 3 Pipe cover for refrigerant piping joint small diameter liquid 1 large diameter gas 1 4 Band large 6 Band small 2 5 Screw with washer M5 25...

Страница 4: ...hich inner diameter fits into the outer diamete of the duct flange In case that the environment above the ceiling is high temperature and high humid ity wrap the duct in a heat insulate to avoid causi...

Страница 5: ...C Installation template Accessory D Screw with washer Accessory Fig 4 7 5 Refrigerant piping work 5 1 Refrigerant pipe Fig 5 1 s Check that the difference between the heights of the indoor and outdoo...

Страница 6: ...rged in the outdoor unit Use leak detector or soapy water to check for gas leaks after connections are com pleted Use refrigerant piping insulation provided to insulate indoor unit connections Insu la...

Страница 7: ...valve remains in the same position Confirm that the pressure gage show 0 101MPa 760 mmHg Pipe length 7 m maximum No gas charge is needed Pipe length exceeding 7 m Charge the prescribed amount of gas...

Страница 8: ...ould cause a fire A switch with at least 3 mm contact separation in each pole shall be provided by the air conditioner installation A Terminal block B Indoor unit Refer to 7 2 C Breaker D 4 core cable...

Страница 9: ...he same terminal block and polarity as is used with the indoor unit For aftercare maintenance give extra length to connecting cable Both end of connecting cable extension wire are peeled off When too...

Страница 10: ...l A Intake grille B Grille C Intake grille levers D Grille hook Fig 8 2 E Hole for the grille s hook F Corner panel G Screw 8 3 Installing the grille Please pay attention because there is a restrictio...

Страница 11: ...on 8 Installing the grille C B A D B A D Fig 8 9 A Button B Vane motor C Up down vanes D Connector E F A Fig 8 10 E A D B E C Fig 8 11 8 5 Installing the intake grille Fig 8 11 Perform the procedure t...

Страница 12: ...ctronic sound is heard from the indoor unit Press the ON OFF button again to turn the air conditioner off If the indoor unit is operated with the remote controller both the test run and the emergency...

Страница 13: ...f the refrigerant is charged from the gas phase composition change may occur in the refrigerant inside the cylinder and the outdoor unit In this case ability of the refrigerating cycle decreases or no...

Страница 14: ...C Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2...

Отзывы: