85
Outdoor unit
frequency
4-Way valve
(20S)
EEVA
EEVB
EEVC
EEVD
Outdoor unit fan
Functional
components
Operation
Heating
Cooling
Heating
If stopped by outdoor protection function. If restarted by operation switching.
If stopped by indoor unit control. If permanent stop.
Cooling
Decision frequency
0 Hz
According to Hz
OFF
ON
OFF
Fully
closed
2 minutes 55 seconds
2 minutes 55 seconds
2 minutes
2 minutes
25seconds
2 minutes
2 minutes
2 minutes
55
seconds
Stopped
(0 Hz command)
All stopped
Stopped
(0 Hz command)
All stopped
Stopped
(0 Hz command)
Restart
Stopped
(0 Hz command)
Restart
EEV
control
Fully
closed
EEV
control
2 minutes
25seconds
2 minutes
25seconds
200 Pulse
2 minutes
25seconds
200 Pulse
200 Pulse
200 Pulse
200 Pulse
200 Pulse
200 Pulse
200 Pulse
55 seconds
Operated
successively
(n)
Serial transmission abnormality protection
An abnormal stop is made if the outdoor unit does not receive serial signal commands, other than “Stop: 0 Hz,” from all the
indoor controllers continuously for 1 minute and 55 seconds when the compressor is operating at an outdoor frequency of
other than 0 Hz. At the same time, LED 5 on the printed circuit board for the outdoor unit will flash 6 times at a 0.5 second
interval every 8 seconds. (The timer lamp on the indoor unit will flash 6 times.)
The unit can be restarted if serial signal is restored and/or the 3-minute delay has finished.
(o) Stop mode : When the decision frequency is 0 Hz; during switching mode, during protection function
operation.