4
- 53
4.16 Report Slave ID (FC: 17)
4
MODBUS(R) STANDARD FUNCTIONS
4.16 Report Slave ID (FC: 17)
Acquires the information of the slave (QJ71MB91) mounted station into the master.
(1) Request message format (Master Slave)
(2) Response message format (Slave Master)
(When completed normally)
The slave (QJ71MB91) will return any of the following programmable controller CPU
type data.
(Continued on next page)
Figure 4.88 Report slave ID (Request message)
Figure 4.89 Report slave ID (Normal response message)
Table4.8 Programmable controller CPU type data returned to Master
Module type
Programmable controller CPU type data
returned to Master
Programmable controller
CPU
Q00JCPU
50
H
Q00CPU
51
H
Q01CPU
52
H
Q02CPU
41
H
Q02HCPU
Q06HCPU
42
H
Q12HCPU
43
H
Q25HCPU
44
H
Function code
Function
code
(11
H
)
Data
See table below.
Function code
Function
code
(11
H
)
Number of
bytes
(02
H
)
Programmable
controller
CPU type
Programmable
controller CPU
STOP/RUN
state
00
H
: STOP, PAUSE, or in
initial processing
FF
H
: RUN, STEP-RUN