9
A
kW
W
kW
K
/min(CFM)
dB
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
L
mm(in.)
mm(in.)
Power supply (phase, cycle, voltage)
Running current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan
Fan(drive)
o
No.
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
Function
Cooling
Heating
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F)
Heating : Indoor
: D.B. 20˚C(68˚F)
Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C(43˚F)
Refrigerant piping length (one way) : 5m (16ft)
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor Unit
1 phase 230V 50Hz
Outdoor Unit 1 phase 230V 50Hz
5. Refer to the service manual of indoor unit for tha indoor unit's specifications.
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Lower limit
Indoor
D.B. 35˚C, W.B. 22.5˚C
D.B. 19˚C, W.B. 15˚C
D.B. 28˚C
D.B. 17˚C
Outdoor
D.B. 46˚C
D.B. -5˚C
D.B. 21˚C, W.B. 15˚C
D.B. -11˚C, W.B. -12˚C
Cooling
Heating
Service Ref.
PUHZ-RP4VHA
PUHZ-RP4VHA
1
PUHZ-RP3VHA
PUHZ-RP3VHA
1
PUHZ-RP2.5VHA
PUHZ-RP2.5VHA
1
Cooling
8.04
TNB220FMBH
Propeller fan
o
1
0.060
55(1,940)
47
48
943(37-1/8)
75(165)
3.5(7.7)
0.87(NEO22)
Max. 50m
Munsell 3Y 7.8/1.1
Linear Expansion Valve
Hermetic
Line start
—
Plate fin coil
Reverse cycle
950(37-3/8)
330+30(13+1-3/16)
R410A
9.52(3/8)
15.88(5/8)
Flared
Flared
Max. 30m
Heating
9.74
Cooling
6.61
Heating
7.50
Cooling
12.33
ANV33FDAMT
1.9
Propeller fan
o
2
0.060+0.060
100(3,530)
49
51
1,350(53-1/8)
121(267)
5.5(12.1)·····RP4VHA
5.0(11.0)·····RP4VHA
1
1.40(MEL56)
Max. 75m
Heating
13.94
HP switch
Discharge thermo
HP switch
LP switch
Discharge thermo
Single, 50Hz, 220-230-240V
OUTDOOR UNIT
REFRIGERANT PIPING
1.6
1.4
OC294-C-1.qxp 04.10.7 5:10 PM Page 9