background image

12

D

F

E

I

NL

P

GR

RU

TR

CZ

SV

SL

HG

PO

GB

1. Use dedicated power supplies for the outdoor unit and indoor unit.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one rank thicker in diameter.

Make sure the power-supply voltage does not drop more than 10%.

4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57). For example,

use wiring such as YZW.

6. A switch with at least 3 mm contact separation in each pole shall be provided by the Air Conditioner installer.

30

32

32

4.0

Main cable

Local swtich (A)

Minimum wire thickness (mm

2

)

Capacity

Fuse

Outdoor unit

Breaker for

wiring  (NFB) (A)

Ground

RP250

Model

30A 100mA 0.1sec. or less

Breaker for current leakage

*1

Max. Permissive

System Impedance

10.4. Wiring of main power supply and equipment capacity

Schematic Drawing of Wiring (Example)

[Fig. 10.4.1]

 

(P.5)

A

Switch (Breakers for wiring and current leakage)

B

Breakers for current leakage

C

Outdoor unit

Thickness of wire for main power supply, capacities of the switch and system impedance

10. Wiring 

(For details, refer to the installation manual of each unit and controller.)

10.1. Caution

1

Follow ordinance of your governmental organization for technical standard re-
lated to electrical equipment, wiring regulations and guidance of each electric
power company.

2

Wiring for control (hereinafter referred to as transmission line) shall be (5 cm or
more) apart from power source wiring so that it is not influenced by electric
noise from power source wiring (Do not insert transmission line and power
source wire in the same conduit).

3

Be sure to provide designated grounding work the to the outdoor unit.

4

Give some allowance to wiring for electrical part box of indoor and outdoor
units, because the box is sometimes removed at the time of service work.

5

Never connect the main power source to terminal block of transmission line. If
connected, electrical parts will burn out.

6

Use 2-core shield cable for transmission line. If transmission lines of different
systems are wired with the same multiplecore cable, the resultant poor trans-
mitting and receiving will cause erroneous operations.

7

Only the transmission line specified should be connected to the terminal block
for outdoor unit transmission.
Erroneous connection does not allow the system to operate.

10.2. Control box and connecting position of

wiring

1

Outdoor unit

1. Remove the front panel of the control box by removing the 4 screws and push-

ing it up a little before pulling it out.

2. Connect the indoor - outdoor transmission line to the terminal block (TB3) for

the indoor - outdoor transmission line.
If multiple outdoor units are connected in the same refrigerant system, daisy-
chain TB3 (M1, M2, 

 Terminal) on the outdoor units. Connect the indoor -

outdoor transmission line for the outdoor units to TB3 (M1, M2, 

 Terminal) of

only one of the outdoor units.

3.

In the case of indoor-outdoor transmission line, connect the shield ground to
the grounding terminal (

).

4. Fix the connected wires securely in place with the cable strap at the bottom of

the terminal block. External force applied to the terminal block may damage it
resulting in a short circuit, ground fault, or a fire.

[Fig. 10.2.1]

 

(P.5)

A

Power source

B

Transmission line

C

Earth screw

[Fig. 10.2.2]

 

(P.5)

A

Cable strap

B

Power source line

C

Transmission line

2

Conduit tube installation

Close by hammering the knockout holes for the conduit tube located on the
base and the bottom part of the front panel.

When installing the conduit tube directly through the knockout holes, remove
the burr and protect the tube with masking tape.

Use the conduit tube to narrow down the opening if there is a possibility of
small animals entering the unit.

10.3. Wiring transmission cables

1

Types of control cables

1. Wiring transmission cables

Types of transmission cables: Shielding wire CVVS, CPEVS or MVVS

Cable diameter: More than 1.25 mm

2

Maximum wiring length: Within 80 m

2. Remote control cables

Remote Controller

2

Wiring examples

Controller name and symbol.

<Examples of transmission cable wiring>

[Fig. 10.3.1]

A

Shielded wire

Set the address setting switch of all unit as zero (0). (factory setting)

Name

Code

Outdoor unit
Indoor unit
Remote controller

Outdoor unit controller
Indoor unit controller
Remote controller

OC

IC

RC

Kind of remote control cable

Cable diameter

Remarks

Sheathed 2-core cable (unshielded) CVV
0.3 to 1.25 mm

2

 (0.75 to 1.25 mm

2

)*

Within 200 m

*

Connected with simple remote controller.

 Warning:

Be sure to use specified wires for connections and ensure no external
force is imparted to terminal connections. If connections are not fixed
firmly, heating or fire may result.

Be sure to use the appropriate type of overcurrent protection switch. Note
that generated overcurrent may include some amount of direct current.

 Caution:

Some installation sites may require attachment of an earth leakage breaker
for the inverter. If no earth leakage breaker is installed, there is a danger
of electric shock.

Do not use anything other than a breaker and fuse with the correct ca-
pacity. Using a fuse or wire of too large capacity may cause malfunction
or fire.

Note:

This device is intended for the connection to a power supply system with
a maximum permissible system impedance shown in the above table at
the interface point (power service box) of the user’s supply.

The user must ensure that this device is connected only to a power sup-
ply system which fulfils the requirement above.
If necessary, the user can ask the public power supply company for the
system impedance at the interface point.

This equipment complies with IEC 61000-3-12 provided that the short-
circuit power S

SC 

is greater than or equal to S

SC 

(*2) at the interface point

between the user’s supply and the public system. It is the responsibility
of the installer or user of the equipment to ensure, by consultation with
the distribution network operator if necessary, that the equipment is con-
nected only to a supply with a short-circuit power S

SC

  greater than or

equal to S

SC 

(*2).

S

SC

 

(*2)

RP250

1.27

Model

S

SC 

(MVA)

*1: Meets technical requirements of IEC61000-3-3

4.0

Содержание PUHZ-RP250YHM-A

Страница 1: ...OUTDOOR UNIT PUHZ RP250YHM A For use with R410A INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit GB...

Страница 2: ...Unit height C Back D Air outlet guide Procured at the site A Front B Must be open C Wall height H 15 15 450 300 A A 100 450 50 50 A A A B B 500 H h h H 240 45 A D C 50 C 1000 30 450 300 C B B C A 100...

Страница 3: ...When closing Turn the shaft clockwise with a hexagonal wrench Turn around the shaft until it stops C Flare nut Coat the flare contact surface with refrigerating machine oil small amount of ester oil...

Страница 4: ...C A B D E Fig 9 4 1 B A D C E E E D A B A B A Inner wall concealed A B D C B Outer wall A Steel wire B Piping C Asphaltic oily mastic or asphalt D Heat insulation material A E Outer covering B A Liqui...

Страница 5: ...2 L3 N Terminal block for indoor outdoor transmission line TB3 Power supply terminal block TB1 Control box A B Fig 10 2 1 10 3 10 2 Fig 10 2 2 A B C Fig 10 3 1 10 A Power source B Transmission line C...

Страница 6: ...When installing and moving the air conditioner to another site do not charge it with a refrigerant different from the refrigerant specified on the unit If a different refrigerant or air is mixed with...

Страница 7: ...hazardous sulphur oxides dust dirt shaving particles oils moisture or any other contami nant Contaminants on the inside of the refrigerant piping may cause the refriger ant residual oil to deteriorate...

Страница 8: ...eight 4 If there are obstacles at the upper part of the unit 2 In case of collective installation Fig 5 0 2 P 2 A Front B Must be open C Wall height H When multiple units are installed adjacent to eac...

Страница 9: ...9 05 for R410A air conditioner choice of pipe type is up to you 8 Never use refrigerant to perform an air purge Always evacuate using a vacuum pump 9 Always insulate the piping properly Insufficient i...

Страница 10: ...ming Open fully after these operations are completed When opening Turn the shaft counterclockwise with a hexagonal wrench Turn around the shaft until it stops When closing Turn the shaft clockwise wit...

Страница 11: ...t D Heat insulation material A E Outer covering B Glass fiber Steel wire Adhesive Heat resistant polyethylene foam Adhesive tape Indoor Vinyl tape Floor exposed Water proof hemp cloth Bronze asphalt O...

Страница 12: ...e outdoor units to TB3 M1 M2 Terminal of only one of the outdoor units 3 In the case of indoor outdoor transmission line connect the shield ground to the grounding terminal 4 Fix the connected wires s...

Страница 13: ...rted up Operate remote controller again after H0 or PLEASE WAIT disappear This is a switching sound of the refrigerant circuit and does not imply a problem Unstable flow of the refrigerant emits a sou...

Страница 14: ...GB E F I NL E P GR RU TR...

Страница 15: ...GB E F NL E P GR RU TR...

Страница 16: ...e number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on t...

Отзывы: