13
9
WIRING SPECIFICATIONS
9-1. FIELD ELECTRICAL WIRING (power wiring specifications)
S1
S2
S3
S1
S2
S3
A-Control
Outdoor Unit
3 poles isolator
400V
3 phase
Isolator
A-Control
Indoor Unit
P200, P250
Outdoor unit model
P200, 250
Outdoor unit
Power supply
Phase
Frequency & Voltage
3N~(3ph 4-wires), 50 Hz,
400 V
Outdoor unit input capacity
*1
Main switch (Breaker)
32 A
Outdoor unit power supply
5
%
Min. 4
Indoor unit-Outdoor unit
*2
Cable length 50 m : 3
%
4 (Polar)/Cable length 80 m : 3
%
6 (Polar)
Indoor unit-Outdoor unit earth
1
%
Min. 2.5
Remote controller-Indoor unit
*3
2
%
0.3 (Non-polar)
Wiring
Wire No.
%
size(mm²)
Circuit rating
Outdoor unit L1-N, L2-N, L3-N
AC 230 V
Indoor unit-Outdoor unit S1-S2
*4
AC 230 V
Indoor unit-Outdoor unit S2-S3
*4
DC 24 V
Remote controller-Indoor unit
*4
DC 12 V
*1 A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
*2 Max. 80 m Total Max. including all indoor/indoor connection is 80 m.
Use one cable for S1 and S2 and another for S3 as shown in the picture.
Max. 50m Total Max. for PEA-200, 250, 400, 500
Wiring size 3
%
1.5 (Polar)
*3 The 10 m wire is attached in the remote controller accessory.
*4 The figures are NOT against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulated by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and Indoor unit/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord.
(Design 60245 IEC 57)
3. Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied.
Warning:
In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation
between power line and communication signal line. Therefore, please turn off the main power supply when servicing.
And do not touch the S1, S2, S3 terminals when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use
3-pole type.
Caution: Be sure to install N-line. Without N-line, it could damage the unit.
Earth leakage breaker
wiring circuit breaker or
isolating switch
1
2
1
2
S1
Indoor
unit
S2
S3
S1
S2
S3
S1
S2
S3
Unit
power
supply
Indoor/outdoor
unit connection
cable
Indoor
unit
Outdoor
unit
Remote
controller
Outdoor
unit
L
3
L
2
L
1
N
Earth leakage breaker
wiring circuit breaker or
isolating switch
1
2
1
2
1
2
S1
S2
S3
S1
S2
S3
S1
S2
S3
S1
S2
S3
Indoor/outdoor
connection cable
Indoor
unit
Indoor
unit
Indoor
unit
Remote
controller
Unit
power
supply
Outdoor
unit
L
3
L
2
L
1
N
Synchronized twin and triple system Electrical wiring
• Synchronized twin
• Synchronized triple