6. Electrical work

6.2. Field electrical wiring

Outdoor unit model

50V

85V

140V

112Y, 140Y

Outdoor unit power supply

~/N (single), 50 Hz, 230 V ~/N (single), 50 Hz, 230 V ~/N (single), 50 Hz, 230 V 3N~ (3 phase), 50 Hz, 400 V

Outdoor unit Circuit Breaker capacity

*1

16 A

25 A

40 A

16 A

Wiring 

Wire No. × 

size (mm²)

Outdoor unit power supply, earth

3 × Min. 1.5

3 × Min. 4

3 × Min. 6

5 × Min. 1.5

Interface unit/Flow temp. controller-Outdoor unit

*2

3 × 1.5 (polar)

3 × 1.5 (polar)

3 × 1.5 (polar)

3 × 1.5 (polar)

Interface unit/Flow temp. controller-Outdoor unit earth

*2

1 × Min. 1.5

1 × Min. 1.5

1 × Min. 1.5

1 × Min. 1.5

Remote controller-Interface unit/Flow temp. controller

2 × 0.3 (Non-polar)

2 × 0.3 (Non-polar)

2 × 0.3 (Non-polar)

2 × 0.3 (Non-polar)

Circuit rating

Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase)

*3

AC 230 V

AC 230 V

AC 230 V

AC 230 V

Interface unit/Flow temp. controller-Outdoor unit S1-S2 *3

AC 230 V

AC 230 V

AC 230 V

AC 230 V

Interface unit/Flow temp. controller-Outdoor unit S2-S3 *3

DC 24 V

DC 24 V

DC 24 V

DC 24 V

Remote controller-Interface unit/Flow temp. controller

*3

DC 12 V

DC 12 V

DC 12 V

DC 12 V

*1. A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use earth leakage breaker (NV).
*2. Max. 80 m
*3.  The 

fi

 gures are NOT always against the ground.

  S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.

Notes:  1.  Wiring size must comply with the applicable local and national codes.

2.  Power supply cables and the cables between Interface unit/Flow temp. controller and outdoor unit shall not be lighter than polychloroprene sheathed 

fl

 exible cables. (Design 60245 IEC 57)

3.  Be sure to connect the cables between Interface unit/Flow temp. controller and outdoor unit directly to the units (no intermediate connections are al-

lowed).
Intermediate connections may result in communication errors. If water enters at the intermediate connection point, it may cause insuf

fi

 cient insula-

tion to ground or a poor electrical contact .
(If an intermediate connection is necessary, be sure to take measures to prevent water from entering the cables.)

4.  Install an earth longer than other cables.
5.  Do not construct a system with a power supply that is turned ON and OFF frequently.

 Warning:

In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power 
line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power 
is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.

Outdoor Unit

3 poles isolator

Power
supply

Isolator

Interface unit /
Flow temp. 
controller

01̲ BH79D067L02̲EN.indd   6

01̲ BH79D067L02̲EN.indd   6

2009/06/03   9:51:03

2009/06/03   9:51:03

Содержание PUHZ-HW*HA series

Страница 1: ...curo e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unit interna prima di installare il condizionatore d aria Nederlands Espa ol Italiano Dansk Svenska INSTALLA...

Страница 2: ...ation has been completed make sure that refrigerant does not leak If refrigerant leaks into the room and comes into contact with the flame of a heater or portable cooking range poisonous gases will be...

Страница 3: ...ods or telephone grounding lines If the unit is not properly grounded there may be a risk to get an electric shock Make sure to use circuit breakers ground fault interrupter isolating switch B fuse an...

Страница 4: ...ion the unit so that the outlet air can blow at right angle to the seasonal wind direction if possible Fig 2 4 B Wind direction A M10 3 8 bolt B Base C As long as possible D Vent E Set deep in the gro...

Страница 5: ...hin the allowable range specified in our technical data etc If the unit is used out of the allowable range the parts of unit might be damaged 5 2 Water quality condition The water in a system should b...

Страница 6: ...terminal However between S3 and S1 these terminals are NOT electrically insulated by the transformer or other device Notes 1 Wiring size must comply with the applicable local and national codes 2 Powe...

Страница 7: ...er ant within the compressor This is not a malfunction Perform the following proce dures 1 Remove the wires from the compressor and measure the insulation resistance of the compressor 2 If the insulat...

Страница 8: ......

Страница 9: ...0 500 1000 400 600 1000 2000 300 1000 1500 500 800 150 1000 1500 400 600 2000 3000 300 500 Fig 2 5 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2...

Страница 10: ...K BH79D067L02 Printed in Japan Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the resident...

Отзывы: