28
SW3-5
Note :
+
4 SW3-5,6
SW3-6
Vane setting
Initial setting
●
Setting
Vane position
OFF
OFF
Set up
Standard
Standard
ON
OFF
Set up
Less draft *
Upward position than the standard
OFF
ON
Set up
Less smudging
Downward position than the standard
ON
ON
unused
—
—
* Be careful of the smudge on ceiling.
Switch
Function
Remarks
Effective
timing
Under
suspension
Under
suspension
Before
power
supply
ON
Before
power
supply
ON
<Initial setting>
ON
OFF
1 2 3 4 5 6 7 8 9 10
Address board
Operation by switch
ON
OFF
Note :
+
1
Fan operation at Heating
mode
+
2
Heating thermo ON is
operating.
Pole
Built-in remote controller
Provided
2,500hr
Effective
Always operated while the heat in ON
+
1
Low
+
3
Setting air flow
+
3
Effective
Effective
Filter clogging detection
Filter cleaning
Fresh air intake
Humidifier control
Air flow set in case of
Heat thermo OFF
Auto restart function
Power ON/OFF by breaker
Indoor unit
Not provided
100hr
Not effective
Operated depends on the condition
+
2
Extra low
+
3
Depends on SW1-7
Not effective
Not effective
Cooling only
Available
Available
Available
Second setting
+
4
Third setting
+
4
Effective
Not effective
—
—
Heat pump/Cooling only
Louver/Humidifier
Vane
Vane swing function in heating
(wave-flow)
Vane horizontal angle
Vane horizontal angle
Sensible temperature correction
Superheat setting temperature
+
5
Sub cool setting temperature
+
5
Heat pump
Not available
Not available
Not available
First setting
+
4
Depends on SW3-5
Not effective
Effective
—
—
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
SW2
Capacity
code
setting
1~6
1~5
SW3
Function
setting
Thermistor <Room temperature
detection> position
<Initial setting>
ON
OFF
1 2 3 4 5 6 7 8 9 10
Indoor controller board
Indoor controller board
<Initial setting>
Set for each capacity.
Indoor controller board
ON
OFF
1 2 3 4 5
SW1
Function
setting
SW4
Model
Selection
(Setting
for
PLFY
series)
Changing the opening of
linear expansion valve
Switching remote display Thermo ON signal display Indicating fan operation
ON/OFF
SW1-7
OFF
ON
OFF
ON
OFF
Extra low
Low
Setting air flow
Stop
OFF
ON
ON
SW1-8
+
3
Note :
+
4 SW3-5,6
+
5 Please do not use
SW-3-9,10 as trouble
might be caused by the
usage condition.
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
P12
MODELS
MODELS
SW2
SW2
P15
P18
P24
P30
P36
10-2. FUNCTION OF DIP SWITCH
The black square (
■
) indicates a switch position.
OCH421B