10
Set the dip switches for function selection according to the system to be used.
At the time of shipment, all dip switches are set to OFF and the M-NET address is set to 01.
*1: When using a system controller (G(B)-50A or TG-2000A), select the "SC setting" and set the pulse weight value settings from a system controller. If set
to another setting, this dip switch setting is prioritized even when set from a system controller.
*2: The pulse unit of the watt-hour meter being used should be 1 kWh/pulse or less. Note that the apportioning error will increase if a watt-hour meter with
large pulse unit is used.
9
Switch List
SW
Supported
Channel
Function
OFF
ON
Remark
SW01
1
Channel 1
Use of input contact
No
Yes
Set whether to use the Channel 1 input.
2
Channel 2
Use of input contact
No
Yes
Set whether to use the Channel 2 input.
3
Channel 3
Use of input contact
No
Yes
Set whether to use the Channel 3 input.
4
Channel 4
Use of input contact
No
Yes
Set whether to use the Channel 4 input.
5
Unused
Set to OFF
6
Unused
Set to OFF
7
Unused
Set to OFF
8
Unused
Set to OFF
SW02
1
Channel 1
Pulse weight value setting:
SC setting (*1):
× 0.1:
× 1:
× 10:
SW02-1,
OFF
OFF
ON
ON
SW02-2
OFF
ON
OFF
ON
Set 1 pulse of the meter connected to channel 1.
2
3
Channel 2
Pulse weight value setting:
SC setting (*1):
× 0.1:
× 1:
× 10:
SW02-3,
OFF
OFF
ON
ON
SW02-4
OFF
ON
OFF
ON
Set 1 pulse of the meter connected to channel 2.
4
5
Channel 3
Pulse weight value setting:
SC setting (*1):
× 0.1:
× 1:
× 10:
SW02-5,
OFF
OFF
ON
ON
SW02-6
OFF
ON
OFF
ON
Set 1 pulse of the meter connected to channel 3.
6
7
Channel 4
Pulse weight value setting:
SC setting (*1):
× 0.1:
× 1:
× 10:
SW02-7,
OFF
OFF
ON
ON
SW02-8
OFF
ON
OFF
ON
Set 1 pulse of the meter connected to channel 4.
8
SW03
1
Unused
Set to OFF
2
Unused
Set to OFF
3
Unused
Set to OFF
4
Unused
Set to OFF
5
Unused
Set to OFF
6
Unused
Set to OFF
7
Unused
Set to OFF
8
Unused
Set to OFF
SW06
M-NET address
(Address 10s) 0 to 9 (decimal)
An address from 01 to 50 can be set.
Set an address that is not the same as that of
another unit.
SW07
(Address 1s) 0 to 9 (decimal)
SW08
1
Communication error status display (error code
display)
Temporary mask setting
Change the switch to ON once
and then return it to OFF.
Only enabled during communication error status
display.
* The communication error status display is
masked for 10 seconds and the contact input
status is displayed.
2
Unused
Set to OFF
3
Unused
Set to OFF
4
Unused
Set to OFF
5
Unused
Set to OFF
6
Unused
Set to OFF
SW09
1
Unused
Set to OFF
2
Unused
Set to OFF