240
RX14
Setting change
completed
(Coincidence output 1)
• This signal turns on when the changes of the following remote registers (RWw) are reflected
to the high-speed counter module in the coincidence output function.
• Point setting (Coincidence output 1 to 4)/Lower limit value setting (Coincidence output 1 to
4) (RWw0 to RWw1, RWw4 to RWw5, RWw8 to RWw9, RWwC to RWwD)
• Upper limit value setting (Coincidence output 1 to 4) (RWw2 to RWw3, RWw6 to RWw7,
RWwA to RWwB, RWwE to RWwF)
• For Coincidence output 1, Setting change completed (Coincidence output 1) (RX14) turns
on after the changes of Point setting (Coincidence output 1)/Lower limit value setting
(Coincidence output 1) (RWw0 to RWw1) and Upper limit value setting (Coincidence output
1) (RWw2 to RWw3) are reflected to the high-speed counter module by Setting change
request (Coincidence output 1) (RY14).
• For Coincidence output 1, Setting change completed (Coincidence output 1) (RX14) turns
off when Setting change request (Coincidence output 1) (RY14) is turned off.
• For Coincidence output 2 to 4, each corresponding remote I/O signals and remote register
(RWw) are used.
RX15
Setting change
completed
(Coincidence output 2)
RX16
Setting change
completed
(Coincidence output 3)
RX17
Setting change
completed
(Coincidence output 4)
RX1F
External power supply
monitor state flag
• This signal turns on when the external power supply monitoring function is enabled by
turning on External power supply monitor request flag (RY1F).
• This signal turns off when the external power supply monitoring function is disabled by
turning off External power supply monitor request flag (RY1F).
Remote input
(RX) No.
Signal name
Description
Controlled by the high-speed counter module
Controlled by the program
ON
OFF
ON
OFF
0
1000
0
2000
Setting change request
(Coincidence output 1 to 4)
(RY14 to RY17)
Upper limit value setting (Coincidence output 1 to 4)
(RWw2 to RWw3, RWw6 to RWw7,
RWwA to RWwB, RWwE to RWwF)
Point setting (Coincidence output 1 to 4)/
Lower limit value setting
(Coincidence output 1 to 4)
(RWw0 to RWw1, RWw4 to RWw5,
RWw8 to RWw9, RWwC to RWwD)
Setting change completed
(Coincidence output 1 to 4)
(RX14 to RX17)
Controlled by the high-speed counter module
External power supply
monitor request flag
(RY1F)
External power supply
monitor state flag
(RX1F)
ON
OFF
ON
OFF
External power supply
monitoring function
Disable
Enable
Disable