132
(2) Initial data setting completed flag (RX9)
Turn on Initial data setting request flag (RY9) after writing parameter data to the remote buffer memory with the
REMTO instruction.
This signal turns on when the operating condition is changed.
When the following settings are changed, the signal is used as an interlock condition to turn Initial data setting
request flag (RY9) on and off.
• Alert output signal assignment (address: 0004
H
)
• Error flag assignment (address: 0005
H
)
• Warning flag assignment (address: 0006
H
)
• Cyclic data update watch time setting (address: 0007
H
)
• Input response time setting (address: 0010
H
)
• Digital output HOLD/CLEAR setting (address: 0011
H
)
• D/A conversion enable/disable setting (address: 0102
H
)
• Range setting (address: 0103
H
)
• Analog output HOLD/CLEAR setting (address: 0104
H
)
• Alert output setting (address: 0105
H
)
• CH
Alert output upper limit value (address: 0106
H
, 0108
H
, 010A
H
, 010C
H
)
• CH
Alert output lower limit value (address: 0107
H
, 0109
H
, 010B
H
, 010D
H
)
• Scaling enable/disable setting (address: 010E
H
)
• CH
Scaling lower limit value (address: 010F
H
, 0111
H
, 0113
H
, 0115
H
)
• CH
Scaling upper limit value (address: 0110
H
, 0112
H
, 0114
H
, 0116
H
)
Initial data setting completed flag
(RX9)
(Set value A)
(Set value B)
ON
ON
ON
ON
Module power supply
*1
The operation is started
with the set value A.
Parameter settings are
read from the nonvolatile
memory.
The operation is started with the set value B
stored in the parameter area at this timing.
The set value is
changed by the user.
Controlled by the D/A converter module
Controlled by the program
*1 When data link is started at turning on the module power supply
OFF
OFF
OFF
OFF
Initial data setting request flag
(RY9)
Remote READY (RXB)
*2
Parameter area
OFF
OFF
OFF
ON
*2 Check that Remote READY (RXB) is turned on, and then start the control when turning on and off Initial data setting request flag (RY9).