54
Start
Indoor unit
operates.
Outdoor unit
doesn't
operate.
Indoor unit
doesn't receive
the signal from
remote controller.
Indoor unit
operates.
Outdoor unit
doesn't operate
normally.
OPERATION INDICATOR
lamp on the indoor unit is
flashing on and off.
Outdoor unit
operates in
only Test Run
operation.
Outdoor unit
doesn't
operate
even in
Test Run
operation.
Indoor unit
operates, when
the EMERGENCY
OPERATION
switch is pressed.
Indoor unit
doesn't operate,
when the
EMERGENCY
OPERATION
switch is pressed.
Check room
temperature
thermistor.
Refer to
"Test point
diagram and
voltage" on
page 67
or 68.
Refer to
D
"Check of
outdoor unit"
on page 61
or 62.
Refer to
B
"Check of
remote controller
and receiver
P.C. board"
on page 59.
Flash on and
off at 0.5-
second
intervals
Cause:
Indoor/
Outdoor unit
• Mis-wiring
2-time flash
Cause:
Indoor unit
• Trouble of
room temp-
erature/
indoor coil
thermistor
3-time flash
Cause:
Indoor unit
• Trouble of
indoor fan
motor
6-time flash
Cause:
Outdoor unit
• Trouble of
thermistor
in outdoor
unit
7-time flash
Cause:
Outdoor unit
• Trouble of
outdoor
control
system
Refer to
H
"How to
check
mis-wiring
(When
outdoor unit
doesn't work)"
on page 65.
Check room
temperature
thermistor
and indoor
coil thermis-
tor.
Refer to
"Test point
diagram and
voltage"
on page 67
or 68.
Refer to
A
"Check of
indoor fan
motor"
on page 59.
Refer to
J
"Check of
outdoor
thermistor"
on page 66.
Replace the
deicer
P.C. board.
MSH-30RV
10-time flash
Cause:
Outdoor unit
• Trouble of
low discharge
temperature
protection
Refer to
I
"Check of
LEV"
on page 66.
MSH-30RV
4-time flash
Cause:
Indoor unit
• Trouble of
indoor unit
control
system
Replace the
indoor
electronic
control
P.C. board.
MSH-24RV
1-time flash
Cause:
Outdoor /
Indoor unit
• Trouble of
serial signal
Refer to
G
"How to
check mis-
wiring and
serial signal
error (When
outdoor unit
doesn't
work)" on
page 64.
W
1
1. Check indoor /
outdoor
connecting wire.
2. Refer to
C
"Check of indoor
electronic control
P.C. board"
on page 60.
Outdoor unit
doesn't
stop even
if indoor unit
stops.
Unit doesn't
operate
normal
operation in
COOL or
HEAT mode.
Refer to
E
"Check of
outdoor unit"
on page 63.
Refer to
F
"Check of
R.V. coil"
on page 63.
W
1.<The case of the trouble of the serial signal>
When the power is turned off and then turned on again, the indication shows “the trouble of mis-wiring”.
MSH-24RV
MSH-30RV
MSH-24/30RV
OB272-2.qxp 02.1.26 1:23 PM Page 54