background image

23

OCH706

[Output pattern A] Errors detected by indoor unit

[Output pattern B]

E9

1. If the beeper does not sound again after the initial 2 beeps to confirm the self-check start signal was received and 

    the OPERATION INDICATOR lamp does not come on, there are no error records.

2. If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 seconds)” after the initial 2 beeps to confirm 

    the self-check start signal was received, the specified refrigerant address is incorrect.

OPERATION

INDICATOR

lamp blink

pattern

Beep

Beep Beep Beep

Beep

Beep

Beep

Off

Approx. 2.5 s

On

Approx. 3 s

On

0.5 s

On

0.5 s

On

0.5 s

On

0.5 s

Off

Approx. 2.5 s

On

Approx. 3 s

On

0.5 s

On

0.5 s

· · · Repeated

Number of blinks/beeps in pattern indicates the check

code in the following table (i.e., n=5 for “U2”)

Number of blinks/beeps in pattern indicates

the check code in the following table

n

th

1

st

2

nd

3

rd

1

st

2

nd

Self-check

starts

(Start signal

received)

Beeper sounds

[Output pattern B]

OPERATION

INDICATOR

lamp blink

pattern

Beep

Beep Beep Beep

Beep

Beep Beep

Off

Approx. 2.5 s

On

0.5 s

On

0.5 s

On

0.5 s

On

0.5 s

Off

Approx. 2.5 s

On

0.5 s

On

0.5 s

· · · Repeated

Number of blinks/beeps in pattern indicates the check

code in the following table (i.e., n=5 for “P5”)

Number of blinks/beeps in pattern indicates

the check code in the following table

n

th

1

st

2

nd

3

rd

1

st

2

nd

Self-check

starts

(Start signal

received)

Beeper sounds

• Refer to the following tables for details on the check codes.

[Output pattern A]

Notes: 

*The check code in the parenthesis indicates PAR-30/31MAA model.

Beeper sounds/OPERATION

INDICATOR lamp blinks

Check code

Symptom

Remark

(Number of times)

Wireless remote controller Wired remote controller

Beeper sounds/OPERATION

INDICATOR lamp blinks

Check code

(Number of times)

Wireless remote controller Wired remote controller

1

P1

Intake sensor error

P9

Pipe (TH5) sensor error

2

P2

Pipe (TH2) sensor error

3

E6,E7

Indoor/outdoor unit communication error

4

P4

Drain sensor error/Float switch connector (CN4F) open

5

P5

Drain pump error

PA

Forced compressor stop (due to water leakage abnormality)

6

P6

Freezing/Overheating protection operation

7

EE

Communication error between indoor and outdoor units

9

E4, E5

Remote controller signal receiving error

Errors detected by unit other than indoor unit (outdoor unit, etc.)

Symptom

1

Indoor/outdoor unit communication error 

2

(Transmitting error) (Outdoor unit)

3

Open/short of outdoor unit thermistors

UP

U3,U4

14

12

14

Fb (FB)*

PL

Indoor unit control system error (memory error, etc.)

E0, E3

E1, E2

Remote controller control board error

Remote controller transmission error

Abnormality of refrigerant circuit 

Compressor overcurrent interruption

As for indoor 

unit, refer to 

indoor unit's 

service manual.

PL or others

Abnormality of refrigerant circuit or other errors (Refer to the technical manual for the outdoor unit.)

[Output pattern A] Errors detected by indoor unit

Wireless remote controller

Wired remote controller

Symptom

Remark

Beeper sounds/OPERATION 

INDICATOR lamp blinks 

(Number of times)

Checkcode

1

P1

Intake sensor error

As for indoor 

unit, refer to 

indoor unit's 

service manual.

2

P2

Pipe (TH2) sensor error

P9

Pipe (TH5) sensor error

3

E6,E7

Indoor/outdoor unit communication error

4

P4

Drain sensor error/Float switch connector (CN4F) open

5

P5

Drain pump error

PA

Forced compressor stop (due to water leakage abnormality)

6

P6

Freezing/Overheating protection operation

7

EE

Communication error between indoor and outdoor units

9

E4,E5

Remote controller signal receiving error

12

Fb (FB)*

Indoor unit control system error (memory error, etc.)

14

PL

Abnormality of refrigerant circuit

-

E0,E3

Remote controller transmission error

-

E1,E2

Remote controller control board error

[Output pattern B]  Errors detected by unit other than indoor unit (outdoor unit, etc.)

Wireless remote controller

Wired remote controller

Symptom

Beeper sounds/OPERATION

INDICATOR lamp blinks

(Number of times)

Checkcode

1

E9

Indoor/outdoor unit communication error

(Transmitting error) (Outdoor unit)

2

UP

Compressor overcurrent interruption

3

U3,U4

Open/short of outdoor unit thermistors

14

PL or Others Abnormality of refrigerant circuit or other errors 

(Refer to the technical manual for the outdoor unit.)

Notes: 1. If the beeper does not sound again after the initial 2 beeps to confirm the self-check start signal was received and

               the OPERATION INDICATOR lamp does not come on, there are no error records.

 2. If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to 

confirm the self-check start signal was received, the specified refrigerant address is incorrect.

    *The check code in the parenthesis indicates PAR-3xMAA model.("x" represents 0 or later)

Содержание Mr.Slim SUZ-SM71VA.TH

Страница 1: ...CIFICATION 10 5 NOISE CRITERIA CURVES 11 6 OUTLINES AND DIMENSIONS 12 7 WIRING DIAGRAM 13 8 REFRIGERANT SYSTEM DIAGRAM 14 9 ACTUATOR CONTROL 15 10 SERVICE FUNCTIONS 16 11 TROUBLESHOOTING 16 12 DISASSE...

Страница 2: ...rminal all supply circuits must be disconnected 2 SAFETY PRECAUTION MEANINGS OF SYMBOLS DISPLAYED ON THE UNIT WARNING This mark is for R32 refrigerant only Refrigerant type is written on nameplate of...

Страница 3: ...or fire when the unit is being used serviced or disposed of Correct refrigerant is specified in the manuals and on the spec labels provided with our products We will not be held responsible for mechan...

Страница 4: ...ous gases will be released 9 Do not use low temperature solder alloy in case of brazing the refrigerant pipes 10 When performing brazing work be sure to ventilate the room sufficiently Make sure that...

Страница 5: ...e Refrigeration Equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufacturer s maintenance and service guide...

Страница 6: ...procedures shall be used However for flammable refrigerants it is important that best practice is followed since flammability is a considera tion The following procedure shall be adhered to remove ref...

Страница 7: ...o cylinders ensure that only appropriate refrig erant recovery cylinders are employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be...

Страница 8: ...ur sides is open and in a sufficiently large space with out depressions 2 4 Minimum installation area If you unavoidably install a unit in a space where all four sides are blocked or there are depress...

Страница 9: ...er to the spec nameplate or installation manual For the amount to be added locally refer to the installation manual Install the indoor unit so that the height from the floor to the bottom of the indoo...

Страница 10: ...3 Refrigeration oil Model L 0 4 FW68S Fan motor Model RC0J60 BC Current Cooling A 0 83 Heating 0 82 Dimensions W H D mm 840 880 330 Weight kg 55 Special remarks Air flow Cooling High m h 3 426 Med 3 0...

Страница 11: ...30 20 10 63 125 250 500 1000 2000 4000 8000 NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 BAND CENTER FREQUENCIES Hz NC 10 Model Item SUZ SM71VA TH Smoothing capacitor C61 C62 C63 CB1 2 3 560 F 450 V Diode modu...

Страница 12: ...efrigerant pipe joint Refrigerant pipe flared 9 52 Gas refrigerant pipe joint Refrigerant pipe flared 15 88 350 mm or more 100 mm or more REQUIRED SPACE Basically leave this space open Only if front a...

Страница 13: ...13 OCH706 7 WIRING DIAGRAM SUZ SM71VA TH...

Страница 14: ...RT68 Ambient temperature thermistor RT65 Strainer 100 Strainer 50 Strainer 100 Muffler Capillary tube 3 0 2 0 200 6 Distributer ADDITIONAL REFRIGERANT CHARGE R32 g MAX REFRIGERANT PIPING LENGTH Max Le...

Страница 15: ...e fan motor turns OFF 15 seconds after the compressor has stopped running NOTE The 4 way valve reverses for 5 seconds right before start up of the compressor Sensor Purpose Actuator Compressor LEV Out...

Страница 16: ...ABLE and 11 3 HOW TO PROCEED SELF DIAGNOSIS 11 1 CAUTIONS ON TROUBLESHOOTING 1 Before troubleshooting check the following items 1 Check the power supply voltage 2 Check the indoor outdoor connecting w...

Страница 17: ...lly Refer to 11 5 How to check in verter compressor 13 time blink 2 5 seconds OFF DC voltage DC voltage of inverter cannot be detected normally Refer to 11 5 How to check in verter compressor Outdoor...

Страница 18: ...e will appear will appear if no error history is available 4 Resetting the error history Press the F4 button Reset on the screen that shows the error history A confirmation screen will appear asking i...

Страница 19: ...ear on the remote controller display if the correct voltage 8 5 12 V DC is not supplied to the remote control ler If this is the case check the remote controller wiring and indoor units OK No problems...

Страница 20: ...er to the indoor unit installation Check code 4 digits or check code 2 digits Error detection attribute Address 3 digits or unit address No 2 digits When there is no error history When opposite side d...

Страница 21: ...mal Remote controller switching is necessary When the problem is other than the checked remote controller Error display 2 E3 6833 6832 blink Cannot send Error display 3 ERC and data error count are di...

Страница 22: ...sensor emits an intermittent buzzer sound the operation light blinks and the check code is output It takes 3 seconds at most for check code to appear 4 Point the remote controller at the sensor on th...

Страница 23: ...tected by unit other than indoor unit outdoor unit etc Symptom 1 Indoor outdoor unit communication error 2 Transmitting error Outdoor unit 3 Open short of outdoor unit thermistors UP U3 U4 14 12 14 Fb...

Страница 24: ...ture thermistor RT62 Measure the resistance with a tester Before measurement hold the thermistor with your hands to warm it up Refer to 11 6 TEST POINT DIAGRAM AND VOLTAGE for the chart of thermistor...

Страница 25: ...rt the test run and then select the cooling mode For details or for other information about starting the test run when using remote controllers refer to the installation manual for the indoor unit or...

Страница 26: ...od Start heating or cooling test run TEST RUN OPERATION Refer to 11 5 Measurement Measure the time from the start of compressor to the stop of compressor due to overcurrent Is the resistance of thermi...

Страница 27: ...isconnect connector between the compressor and the intelligent power module Turn ON the power supply and start heating test run TEST RUN OPERATION Refer to 11 5 Disconnect connector between the compre...

Страница 28: ...ith a hand Yes Check the outdoor fan motor Refer to Is the fuse F901 blown on the in verter P C board Check the connection of the connectors CN931 CN932 of the outdoor fan mo tor If the connection is...

Страница 29: ...or the installation condition combination of specific conditions such as antennas or wiring Check the following before asking for service 1 Devices affected by the electromagnetic noise TV sets radios...

Страница 30: ...Yes The refrigerant gas amount may be 60 or less than the normal amount Identify where the gas is leaking from and fix the leak No CAUTION Do not start the operation again to prevent hazards The opera...

Страница 31: ...stance k Resistance k Resistance k 11 6 TEST POINT DIAGRAM AND VOLTAGE Inverter P C board SUZ SM71VA TH Fin temperature thermistor RT64 CN673 Ambient temperature thermistor RT65 CN672 Discharge temper...

Страница 32: ...A TH Indicates the visible parts in the photos figures Indicates the invisible parts in the photos figures NOTE Turn OFF the power supply before disassembly OPERATING PROCEDURE PHOTOS FIGURES 1 Removi...

Страница 33: ...res and the lead wires of the inverter P C board 5 Remove the screws of the P B support 6 Remove the P B support from the relay panel 7 Remove the screws of the inverter P C board 8 Remove the inverte...

Страница 34: ...ead wire to the reactor and the following connectors Inverter P C board CN671 Defrost thermistor discharge temperature thermis tor and outdoor heat exchanger temperature ther mistor CN672 Ambient temp...

Страница 35: ...Refer to 1 2 Remove the back panel Refer to 1 3 Remove the screws fixing the relay panel 4 Remove the relay panel 5 Remove the inverter assembly Refer to 2 6 Recover gas from the refrigerant circuit...

Страница 36: ...ICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO100 8310 JAPAN Copyright 2018 MITSUBISHI ELECTRIC CORPORATION Published Dec 2018 No OCH706 Made in Japan Specifications are subject to change withou...

Отзывы: