Mitsubishi Mr.Slim PUHZ-RP HA2 Скачать руководство пользователя страница 10

10

10.System control (Fig. 10-1)

* Set the refrigerant address using the DIP switch of the outdoor unit.

1

Wiring from the Remote Control

This wire is connected to TB5 (terminal board for remote controller) of the indoor unit
(non-polar).

2

When a Different Refrigerant System Grouping is Used.

Up to 16 refrigerant systems can be controlled as one group using the slim MA re-
mote controller.

Note:
In single refrigerant system (twin/triple), there is no need of wiring 

2

.

Operation according to switch setting

ON

OFF

Start

Normal

Clear

Normal

Settings for outdoor unit ad-
dresses 0 to 15

SW1
Function table

<SW1>

Function

1 Compulsory de-

frosting

2 Error history clear
3
4
5
6

ON

1 2 3 4 5 6

OFF

A

Outdoor unit

B

Indoor unit

C

Master remote controller

D

Subordinate remote controller

E

Standard 1:1 (Refrigerant address = 00)

F

Simultaneous twin (Refrigerant address = 01)

G

Simultaneous triple (Refrigerant address = 02)

TB4

TB5

TB1

TB4

TB5

TB4

TB1

TB4

TB1

TB4

TB4

TB5

1

1

2

2

A

A

B

B

B

B

B

B

C

D

A

F

G

E

ON

OFF

3

4

5

6

E

 SW 1 - 3 ~ 6

ON

OFF

3

4

5

6

F

 SW 1 - 3 ~ 6

ON

OFF

3

4

5

6

G

 SW 1 - 3 ~ 6

SW1
function
settings

Fig. 10-1

Refrigerant sys-
tem address set-
ting

9. Special Functions

9.1. Low noise mode (on-site modification) (Fig. 9-1)

By performing the following modification, operation noise of the outdoor unit can be
reduced by about 3-4 dB.
The low noise mode will be activated when a commercially available timer or the
contact input of an ON/OFF switch is added to the CNDM connector (option) on the
control board of the outdoor unit.
• The ability varies according to the outdoor temperature and conditions, etc.

1

Complete the circuit as shown when using the external input adapter (PAC-
SC36NA). (Option)

2

SW1 ON: Low noise mode
SW1 OFF: Normal operation

9.3. Refrigerant collecting (pump down)

Perform the following procedures to collect the refrigerant when moving the indoor
unit or the outdoor unit.

1

Supply power (circuit breaker).

* When power is supplied, make sure that “CENTRALLY CONTROLLED” is not

displayed on the remote controller. If “CENTRALLY CONTROLLED” is dis-
played, the refrigerant collecting (pump down) cannot be completed normally.

2

After the gas stop valve is closed, set the SWP switch on the control board of the
outdoor unit to ON. The compressor (outdoor unit) and ventilators (indoor and
outdoor units) start operating and refrigerant collecting operation begins. LED1
and LED2 on the control board of the outdoor unit are lit.

* Only set the SWP switch (push-button type) to ON if the unit is stopped. How-

ever, even if the unit is stopped and the SWP switch is set to ON less than
three minutes after the compressor stops, the refrigerant collecting operation
cannot be performed. Wait until compressor has been stopped for three min-
utes and then set the SWP switch to ON again.

3

Because the unit automatically stops in about two to three minutes after the refrig-
erant collecting operation (LED1 and LED2 are lit), be sure to quickly close the
gas stop valve. When LED1 and LED2 are lit and the outdoor unit is stopped, open
the liquid stop valve completely, and then repeat step 

2

 after three minutes have

passed.

* If the refrigerant collecting operation has been completed normally (LED1 and

LED2 are lit), the unit will remain stopped until the power supply is turned off.

4

Turn off the power supply (circuit breaker).

A

Circuit diagram example (low noise mode)

B

On-site arrangement

C

External input adapter (PAC-SC36NA)

SW1

CNDM

Red

Brown

Orange

B

C

D

E

3

1

D

Outdoor unit control board

E

Max. 10 m

Fig. 9-1

A

9.2. Demand function (on-site modification) (Fig. 9-2)

By performing the following modification, energy consumption can be reduced to 0–
100% of the normal consumption.
The demand function will be activated when a commercially available timer or the
contact input of an ON/OFF switch is added to the CNDM connector (option) on the
control board of the outdoor unit.

1

Complete the circuit as shown when using the external input adapter (PAC-
SC36NA). (Option)

2

By setting SW7-1 and SW7-2 on the control board of the outdoor unit, the energy
consumption (compared to the normal consumption) can be limited as shown
below.

SW7-1

SW7-2

Energy consumption (SW2 ON)

OFF

OFF

0% (Stop)

ON

OFF

50%

OFF

ON

75%

A

Circuit diagram example (Demand
function)

B

On-site arrangement

C

External input adapter (PAC-SC36NA)

D

Outdoor unit control board

E

Max. 10 m

Fig. 9-2

A

SW2

CNDM

Red

Brown

Orange

B

C

D

E

3

1

8. Initial settings for refrigerant leakage detection function

[Display 

D

] Waiting for stabilization

Stabilized

After 45 minutes

Fig. 8-3

3

Press 

FILTER

 ( ) button to confirm. (Fig. 8-3)

s

How to finish the initial learning

Once the unit’s operation is stabilized, the initial learning is completed.

4

Press 

TEST

 button for more than three seconds to cancel the initial learning.

The initial learning can also be cancelled by pressing 

ON/OFF

 button.

* Refer to the Technical Manual for the refrigerant leakage detection judgment method.

Содержание Mr.Slim PUHZ-RP HA2

Страница 1: ...lish INSTALLATION MANUAL For safe and correct use read this manual and the indoor unit installation manual thoroughly before installing the air conditioner unit Air Conditioners PUHZ RP HA2 FOR INSTAL...

Страница 2: ...10A to charge the refrigerant lines Do not mix it with any other refrig erant and do not allow air to remain in the lines Air enclosed in the lines can cause pressure peaks resulting in a rupture and...

Страница 3: ...own may result Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may resu...

Страница 4: ...low 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for RP100 140 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional...

Страница 5: ...pipes Fig 4 1 When commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more Th...

Страница 6: ...lve opening method The stop valve opening method varies according to the outdoor unit model Use the appropriate method to open the stop valves 1 Gas side of RP60 140 Fig 4 5 1 Remove the cap then turn...

Страница 7: ...nstalling the refrigerant piping 4 8 For twin triple combination Refrigerant piping limitation of length height difference are shown in the figure Fig 4 7 A Indoor unit B Outdoor unit C Multi distribu...

Страница 8: ...24 V DC 24 V DC 24 V DC 24 V DC 24 V DC 12 V DC 12 V DC 12 V DC 12 V DC 12 V 1 A breaker with at least 3 0 mm contact separation in each poles shall be provided Use non fuse breaker NF or earth leakag...

Страница 9: ...roller and LED1 and LED2 on the control board of the outdoor unit flash together 3 The duration of the replacement operation is determined by the length of the pip ing Always perform the replacement o...

Страница 10: ...egins LED1 and LED2 on the control board of the outdoor unit are lit Only set the SWP switch push button type to ON if the unit is stopped How ever even if the unit is stopped and the SWP switch is se...

Страница 11: ...1000 100 150 500 1000 200 300 1000 1500 300 500 1000 1500 Max 300 1000 1500 1000 1500 300 500 500 1000 400 600 1000 2000 100 150 1000 1500 500 800 150 1000 1500 400 600 2000 3000 300 500 Fig 2 6 Fig 2...

Страница 12: ...3 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MA...

Отзывы: