background image

USER'S GUIDE

JY992D52801C

FX-2DA

SPECIAL FUNCTION BLOCK

This manual contains text, diagrams and explanations which will guide the reader in the correct installation
and operation of the FX-2DA special function block and should be read and understood before attempting
to install or use the unit.
Further information can be found in the FX PROGRAMMING MANUAL and FX SERIES HARDWARE
MANUAL.

The FX-2DA analog special function block has two output channels. The output channels take a digital value
and output an equivalent analog signal. This is called a D/A conversion. The FX-2DA has a maximum
resolution of 12 bits.

The selection of voltage or current based input/output is by user wiring. Analog ranges of -10 to 10V
(resolution: 5mV), and/or 4 to 20mA (resolution: 20

µ

A) maybe selected.

FX programmable controllers versions 2.0 or later (those with serial number 13XXXX or larger) are
required; as these units have the TO/FROM applied instructions in their instruction set. Data transfer
between the FX-2DA and the FX base unit is by buffer memory exchange. There are 32 buffer memories
(each of 16 bits) in the FX-2DA.

The FX-2DA occupies 8 points of I/O on the FX, FX

2C

 expansion bus. The 8 points can be allocated from

either inputs or outputs. The FX-2DA draws 30mA from the 5V rail of the base unit or powered extension
unit.

INTRODUCTION

1

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Содержание Melsec FX-2DA

Страница 1: ... underutilized and idle equipment along with credit for buybacks and trade ins Custom engineering so your equipment works exactly as you specify Critical and expedited services Leasing Rentals Demos In stock Ready to ship TAR certified secure asset solutions Expert team I Trust guarantee I 100 satisfaction All trademarks brand names and brands appearing herein are the property of their respective ...

Страница 2: ...bits The selection of voltage or current based input output is by user wiring Analog ranges of 10 to 10V resolution 5mV and or 4 to 20mA resolution 20µA maybe selected FX programmable controllers versions 2 0 or later those with serial number 13XXXX or larger are required as these units have the TO FROM applied instructions in their instruction set Data transfer between the FX 2DA and the FX base ...

Страница 3: ...current and voltage output loads at the same time b Shorting the voltage output terminals may da mage the unit FX 2DA special function block V V I I 2 Groove for 35mm 1 38 wide DIN rail 2 5 5mm 0 22 hole M3 5 0 14 terminal screws Wiring 2 2 Apply 1 point grounding at the load side of the output cable class 3 grounding 100 Ω or less If electrical noise is caused from grounding disconnect from groun...

Страница 4: ...Digital input Overall accuracy Conversion speed Resolution Current output 5mV 10V full scale 1 2000 DC 4mA to 20mA external load 500 Ω or less Current 0 to 1000 1 full scale 20mA range 20µA 20mA full scale 1 1000 Factory Presets Load 10kΩ Ω Ω Ω Ω voltage Output 250Ω Ω Ω Ω Ω current Output Analog output 2047 10V 5V 5V 10V 2000 1000 2048 10 24V 10 235V Digital input Gain and offset can be adjusted u...

Страница 5: ...ce of the DC24V for the analog circuits and other power lines of the base unit the output of the FX 2DA special function block may behave erroneously before settling down to operational conditions in approximately 1sec Therefore ensure that this behavior is taken into account such that the end performance of the system is not degraded example Power switch Miscellaneous DC24V supply FX 2DA special ...

Страница 6: ...t is 0 Gain value the actual output value when the digital input is 1000 contents channel Initialization Default H00 channel 1 channel 2 Reserved Last data reset Default 0 Reserved selection of A D conversion speed see note Reserved Gain offset adjust prohibit Initial value 0 1 Offset gain setting command G 2 O 2 G 1 O 1 Pro hibit Permit b 3 b 2 b 1 b 0 Reset all to default default value 0 Offset ...

Страница 7: ...eed does not depend on the number of channels being used On power up the FX 2DA is set for normal speed conversion and BFM 7 contains 0 4 Adjusting Gain and Offset Values When BFM 20 is set to K1 all settings in the buffer memory are reset to their default settings This allows the buffer memory settings to be set from the beginning again when many settings have been corrupted If b1 b0 of BFM 21 is...

Страница 8: ...BFM 21 is set at 1 0 Values of BFM 0 5 21 23 and 24 are stored in EEPROM memory of the FX 2DA BFM 23 and BFM 24 are only copied when the gain offset setting command BFM 22 is used Also BFM 20 causes resetting of the EEPROM memory The EEPROM has a life of about 10 000 cycles changes so do not use programs which frequently change these BFMs Because of the time needed to write to the EEPROM memory a ...

Страница 9: ...her RUN or STOP mode Offset and gain can be used independently or together Reasonable offset ranges are 5V to 5V or 20mA to 20mA and gain offset difference 1V to 15V or 4mA to 32mA Gain and offset can be adjusted by software in the FX base unit see program example 2 or by the switches on the FX 2DA with the aid of a voltmeter ammeter Bit device s b0 b1 of the gain offset BFM 21 should be set to 0 ...

Страница 10: ... if OK M1 is turned ON These two program steps are not strictly needed to perform an analog output They are however a useful check and are recommended as good practice The analog output channels CH1 CH2 are set up by writing H10 to BFM 0 of the FX 2DA Output data normal The operational status of the FX 2DA is read from BFM 29 and output as bit devices at the FX base unit D0 BFM 1 output to CH1 D1 ...

Страница 11: ...djusting gain offset via software settings X010 M0 T0 T1 K1 K1 H10 K1 K0 K21 K1 K1 K1 K0 K22 K1 TO TO P TO P TO P TO P K1 K1 K1 K1 K23 K24 K22 K21 K0 K20000 HC RST K2 K1 K1 K1 M0 K1 Adjustment start H10 BFM 0 initialize input channels In the program shown at left the programmable controller should be in RUN status and MODE switch of the FX 2DA in the READY position K1 BFM 21 BFM 0 should be of HEX...

Страница 12: ...remember the loading on the FX base unit or a powered extension unit varies according to the number of extension blocks or special function blocks connected 6 Pit the main processing unit into RUN 6 2 Error checking Check the status of the POWER LED Lit The extension cable is properly connected Otherwise Check the connection of the extension cable Check the external wiring Check the status of 24V ...

Страница 13: ...ill Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of the installation or use of this equipment All examples and diagrams shown in this manual are intended only as an aid to understanding the text not to guarantee operation Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples JY992...

Страница 14: ...quipment Have surplus equipment taking up shelf space We ll give it a new home Learn more Visit us at artisantg com for more info on price quotes drivers technical specifications manuals and documentation Artisan Scientific Corporation dba Artisan Technology Group is not an affiliate representative or authorized distributor for any manufacturer listed herein We re here to make your life easier How...

Отзывы: