![Mitsubishi GOT2000Series Скачать руководство пользователя страница 114](http://html1.mh-extra.com/html/mitsubishi/got2000series/got2000series_connection-manual_1809187114.webp)
5 - 14
5. CONNECTION TO FUJI TEMPERATURE CONTROLLER
5.5 Temperature Controller Side Setting
5.5
Temperature Controller Side Setting
POINT
POINT
POINT
(1) FUJI temperature controller
For details of FUJI temperature controller, refer to
the following manual.
User's Manual of the FUJI temperature
controller
(2) Interface converter
For details on communication settings of the
interface converter, refer to the following manual.
User's Manual of interface converter
5.5.1
Connecting to PXR3/4/5/9
Communication settings
Make the communication settings by operating the key
of the temperature controller.
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the station No. with any of the other
units.
5.5.2
Connecting to PXG4, PXG5 or
PXG9
Communication settings
Make the communication settings by operating the key
of the temperature controller.
(1) RS-485 communication settings
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the station No. with any of the other
units.
*3
Set as necessary.
(2) RS-232 communication settings (PC loader
communication)
Model name
Refer to
Temperature controller
PXR3, PXR4, PXR5,
PXR9
PXG4, PXG5, PXG9
PXH9
Interface converter
RC-77
SI-30A
KS-485
K3SC-10
Item
Set value
Transmission speed
9600bps (fixed)
Data bit
8bits (fixed)
Parity bit
*1
Even, Odd, None
Stop bit
1bit (fixed)
Station No.
*2
1 to 255
Communication protocol
MODBUS
Item
Set value
Transmission speed
*1
9600bps, 19200bps
Data bit
8bits (fixed)
Parity bit
*1
Even, Odd, None
Stop bit
*1
1bit (fixed)
Station No.
*2
1 to 255
Communication
permissions
*3
Read only permission or read and overwrite
permission
Item
Set value
Transmission speed
9600bps (fixed)
Data bit
8bits (fixed)
Parity bit
None (fixed)
Stop bit
1bit (fixed)
Содержание GOT2000Series
Страница 2: ......
Страница 17: ...A 15 REVISIONS WARRANTY...
Страница 52: ...1 30 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring...
Страница 54: ......
Страница 78: ...3 10 3 CONNECTION TO HITACHI PLC 3 6 Device Range that Can Be Set...
Страница 100: ...4 22 4 CONNECTION TO FUJI PLC 4 7 Precautions...
Страница 174: ...7 24 7 CONNECTION TO YOKOGAWA PLC 7 4 Device Range that Can Be Set...
Страница 262: ...9 54 9 CONNECTION TO RKC TEMPERATURE CONTROLLER 9 7 Precautions...
Страница 280: ...10 18 10 CONNECTION TO ALLEN BRADLEY PLC 10 4 Device Range that Can Be Set...
Страница 296: ...11 16 11 CONNECTION TO GE PLC 11 7 Precautions...
Страница 308: ...12 12 12 CONNECTION TO LS INDUSTRIAL SYSTEMS PLC 12 6 Device Range that Can Be Set...
Страница 332: ...14 18 14 CONNECTION TO SIEMENS PLC 14 4 Device Range that Can Be Set...
Страница 334: ...REVISIONS 2...
Страница 337: ......