281
FX
3UC
Series Programmable Controllers
User’s Manual - Hardware Edition
9 CC-Link/LT Built-in master ability (Only FX3UC-32MT-LT)
9.9 Setting of CC-Link/LT built-in master and remote I/O units
1
O
utline
2
Exter
nal
D
im
en
sions
3
Ge
ne
ric
Speci
ficat
ions
4
Pow
er Suppl
y
Specif
icati
ons
5
Input
Spec
ific
ations
6
O
utput
Specif
icat
ions
7
Exam
pl
es
of
W
iri
ng
fo
r
Va
rious U
ses
8
Te
rm
inal B
lock
9
CC
-L
in
k/L
T
Ma
ste
r F
X
3UC
(LT
only)
10
D
ispl
ay m
odule
FX
3UC
(L
T only)
9.9.1
Setting DIP switches in built-in master (operation mode/Communication speed/
Point mode)
1
Turn the power OFF
2
Remove the display module of the FX
3UC
-32MT-LT.
→
For the display module removal method, refer to Section 3.8.
3
Setting the TEST mode Transmission speed and Point mode
B RATE (Transmission speed) setting
[DIP switch 1, 2]
16pts/4pts (Point mode) setting [DIP switch 3]
4
Setting the CONFIG mode
Set the operation mode to "CONFIG".
Selecting the Operation mode [DIP switch 6, 7]
[DIP switch 4, 5, 8]
The DIP switches 4, 5 and 8 are unavailable. Make sure to set them to OFF.
1. Setting example of transmission speed (B RATE), point mode (16 pts/4 pts) and operation
mode
Set the DIP switches as shown in the right figure to set the following
status.
Set the station number of remote I/O units in reference to Subsection
9.9.2.
DIP switch status
Setting Content
1
2
OFF
OFF
156kbps
ON
OFF
625kbps
OFF
ON
2.5Mbps
ON
ON
Prohibited to use
DIP switch status
Setting Content
3
ON
16-point mode
OFF
4-point mode
DIP switch status
Setting Content
6
7
OFF
OFF
ONLINE mode
ON
OFF
CONFIG mode
OFF
ON
TEST mode
Item
Setting Content
B RATE
2.5Mbps
16pts/4pts
4-point mode
operation mode
CONFIG mode
DIP switch
6 = ON
DIP switch
2 = ON
Содержание FX3UC Series