FX2N-64CL-M CC-Link/LT Master Block
System Configuration 4
4-3
4.2
PLC connection
This section explains which PLC series are connectable with the FX
2N
-64CL-M and gives
cautions on the number of connectable FX
2N
-64CL-M blocks.
4.2.1
Applicable PLC and number of connectable FX
2N
-64CL-M
*1 Up to 7 units can be connected to an FX
3UC
-32MT-LT PLC.
•
Connect the FX
2N
-64CL-M to the right side of the PLC using an extension cable.
•
The number of occupied I/O points is "8 (either input or output) Number of
connected remote I/O points (in multiples of eight)".
The total number of I/O points including extended points must not exceed 128 points for the
FX
1N
Series or 256 points for the FX
2N
, FX
2NC
, FX
3U
and FX
3UC
Series.
For the number available of I/O points of the connected PLC, refer to the manual of the PLC
main unit.
•
The FX
2N
-64CL-M consumes 190 mA from the 5V DC source.
The total current consumption from the 5V source of special function blocks connected to
the PLC must not exceed the 5 V power capacity of the main unit and extension units.
When connecting to the FX
1N
Series PLC, a maximum of two FX
2N
-64CL-M can be
connected to the main and another two on the extension unit.
For details on connection to the PLC main unit, refer to the manual of the PLC main unit.
Applicable PLC
FX
1N
/FX
2N
/FX
2NC
/FX
3U
/FX
3UC
Series PLC
(FX
2NC
-CNV-IF is required when an FX
2NC
Series PLC is connected.)
(FX
2NC
-CNV-IF or FX
3UC
-1PS-5V is required when an FX
3UC
Series PLC is
connected.)
Number of connect-
able master blocks
FX
1N
Series: Up to 4
FX
2N
Series: Up to 8
FX
2NC
Series: Up to 3
FX
3U
Series: Up to 8
FX
3UC
Series: Up to 8
*1
Содержание FX2N-64CL-M
Страница 1: ...USER S MANUAL Detailed Volume FX2N 64CL M CC Link LT Master Block ...
Страница 4: ...FX2N 64CL M CC Link LT Master Block ii ...
Страница 6: ...FX2N 64CL M CC Link LT Master Block iv ...
Страница 12: ...FX2N 64CL M CC Link LT Master Block x ...
Страница 26: ...FX2N 64CL M CC Link LT Master Block System Startup Procedure 3 3 2 ...
Страница 48: ...FX2N 64CL M CC Link LT Master Block Connection of Cables Connectors and Terminating Resistors 6 6 10 ...
Страница 50: ...FX2N 64CL M CC Link LT Master Block Various Modes 7 7 2 ...
Страница 74: ...FX2N 64CL M CC Link LT Master Block Model Assignment of Buffer Memory 10 10 14 ...
Страница 93: ......