5. Wiring
Cautions on wiring
•
Make sure to shut down the power supplies of all phases on the outside before starting installation
or wiring.
If the power supplies are not shut down, you may receive an electrical shock or the unit may be
damaged.
•
As to loads, such as a connector for normal rotation and a connector for reverse rotation,
which are dangerous when turning on at the same time, make sure to interlock them outside
the PLC in addition to interlocking of them in a program in the PLC.
•
Correctly connect the power cable of the FX
2N
-2LC and the PLC as described in this manual.
If the AC power supply is connected to a DC I/O terminal or DC power terminal, the PLC may
be damaged.
•
Perform Class D grounding with an electric wire of 2 mm
2
or more to the grounding terminal in the
FX
2N
-2LC and the PLC. However, never perform common grounding with a strong power system.
6. Specifications
6.1 General specifications
Other General specifications are equivalent to those for the PLC main unit. Refer to the manual of the PLC
main unit.
6.2 Power supply specifications
Item
Specifications
Withstand voltage
500V AC for 1 minute
(between analog input terminal and grounding terminal)
Item
Specifications
Driving power supply
24V DC (-15% to +10% maximum), input from driving power
supply terminal
Power supply for
communication
5V DC (supplied from inside of PLC main unit)
Current consumption
24V DC, 55 mA and 5V DC, 70 mA
Insulation method
Analog input area and PLC are insulated by photocoupler.
Power supply and analog input are insulated by DC/DC converter.
(Channels are insulated from each other.)
Number of occupied
I/O points
8 points in total (including input points and output points)
PTA/
FG
PTB/TC+
PTB/TC-
FX
2N
-2LC
Resistance
thermometer bulb
Shielded cable
24+
24-
OUT1
COM
OUT2
CT
CT
PTA/
FG
PTB/TC+
PTB/TC-
CT
CT
PTA/
FG
PTB/TC+
PTB/TC-
SSR
SSR
FX
2N
-2LC
DC24V
+
-
CT
CT
Heater
Heater
Shielded cable
Thermocouple
AC power
supply
Shielded cable
Thermocouple
*1
When a temperature sensor is a thermocouple
When a temperature sensor is a resistance thermometer bulb
*1 Connect the ground terminals of
the FX
2N
-2LC unit and the main
unit. Use class D grounding on
the main unit.
•
Use the compensating cable
when you use the thermo couple.
•
The temperature sensor must use
three line type.
The resistance of the lead wire is a
little, and use the wire rod without
the resistance difference between
three lines.
•
Secure the termination using a
tightening torque of 0.5 to 0.8N
x
m
6.3 Performance specifications
6.4 Input specifications
6.5 Input range
Item
Description
Control method
Two-position control, PID control (with auto tuning function), PI control
Control operation
period
500ms
Set temperature
range
Equivalent to input range
Heater disconnection
detection
Alarm is detected by buffer memory
(Variable within range from 0.0 to 100.0 A.).
Operation mode
0: Measured value monitor
1: Measured value m Temperature alarm
2: Measured value m Temperature alarm + Control
(selected by buffer memory)
Self-diagnosis
function
Adjustment data check, input value check, watch dog timer check.
Memory
Built-in EEPROM (Number of times of overwrite: 100,000 times)
Indication
POWER
Lit (green): While 5V power is supplied
Extinguished: While 5V power is not supplied
24V
Lit (red): While 24V power is supplied
Extinguished: While 24V power is not supplied
OUT1
Lit (
red
): While control output 1 is ON
Extinguished: While control output 1 is OFF
OUT2
Lit (red): While control output 2 is ON
Extinguished: While control output 2 is OFF
Item
Description
Tempera-
ture input
Number of input points
2 points
Input
type
Thermocouple
K, J, R, S, E, T, B, N, PLII, WRe5-26, U, L, JIS C 1602-1995
Resistance ther-
mometer bulb
3-wire Pt100 JIS C 1604-1997, JPt100 JIS C 1604-1981
Measurement precision
Ambient temperature 23
°
C ± 5
°
C : ± 0.3% of range span ± 1 digit.
Ambient temperature 0
°
C to 55
°
C : ± 0.7% of range span ± 1 digit.
However, 0 to 399
°
C (0 to 799
°
F) in B inputs as well as 0 to 32
°
F in
PLII and WRe5-26 inputs are outside precision guarantee range.
Cold contact tempera-
ture compensation error
Within ±1.0
°
C
However, within ± 2.0
°
C while input value is -150 to -100
°
C
within ± 3.0
°
C while input value is -200 to -150
°
C
Resolution
0.1
°
C (0.1
°
F) or 1
°
C(1
°
F) (Varies depending on input range of used
sensors.)
Sampling period
500ms
Effect of external resis-
tance
Approx. 0.35
µ
V/
Ω
Input impedance
1 M
Ω
or more
Sensor current
Approx. 0.3 mA
Allowable input lead wire
resistance
10
Ω
or less
Operation when input is
disconnected
Upscale
Operation when input is
short-circuited
Downscale
CT input
Number of inputs
2 points
Current detector
CTL-12-S36-8 or CTL-6-P-H (manufactured by U.R.D. Co., Ltd.)
Heater current
measurement value
When CTL-12 is used: 0 to 100A When CTL-6 is used: 0 to 30A
Measurement precision
Larger one between ± 5% of input value and 2 A
(excluding precision of current detector)
Sampling period
1 second
Sensor type
K
J
R
S
Input range
-200.0 to 200.0
°
C
-100.0 to 400.0
°
C
-100 to 1300
°
C
-100 to 800
°
F
-100 to 2400
°
F
-200.0 to 200.0
°
C
-100.0 to 400.0
°
C
-100.0 to 800.0
°
C
-100 to 1200
°
C
-100 to 1600
°
F
-100 to 2100
°
F
0 to 1700
°
C
0 to 3200
°
F
0 to 1700
°
C
0 to 3200
°
F
Sensor type
E
T
B
N
Input range
-200.0 to 200.0
°
C
0 to 1000
°
C
0 to 1800
°
F
-200.0 to 200.0
°
C
-200.0 to 400.0
°
C
0.0 to 400.0
°
C
-300.0 to 400.0
°
F
-300.0 to 700.0
°
F
0.0 to 700.0
°
F
0 to 1800
°
C
0 to 3000
°
F
0 to 1300
°
C
0 to 2300
°
F
•
When B is used, 0 to 399
°
C
(0 to 799
°
F) is outside the precision guarantee range.
•
When PLII is used, 0 to 32
°
F is outside the precision guarantee range.
•
When WRe5-26 is used, 0 to 32
°
F is outside the precision guarantee range.
6.6 Output specifications
Sensor type
PLII
WRe5-26
U
L
Input range
0 to 1200
°
C
0 to 2300
°
F
0 to 2300
°
C
0 to 3000
°
F
-200.0 to 600.0
°
C
-300.0 to 700.0
°
F
0.0 to 900.0
°
C
0 to 1600
°
F
Sensor type
JPt100
Pt100
Input range
-50.0 to 150.0
°
C
-200.0 to 500.0
°
C
-300.0 to 300.0
°
F
-300 to 900
°
F
-50.0 to 150.0
°
C
-200.0 to 600.0
°
C
-300.0 to 300.0
°
F
-300 to 1100
°
F
Item
Description
Number of output points
2 points
Output method
Open collector transistor output
Rated load voltage
5 to 24V DC
Maximum load voltage
30V DC or less
Maximum load current
100mA
Leak current in OFF status
0.1 mA or less
Maximum voltage drop in ON status
2.5V (maximum) or 1.0V (typical) at 100 mA
Control output cycle
30 seconds (Variable within range from 1 to 100 seconds)
Guidelines for the safety of the user and protection of the FX
2N
-2LC
•
This manual has been written to be used by trained and competent personnel. This is defined
by the European directives for machinery, low voltage and EMC.
•
If in doubt at any stage during the installation of the FX
2N
-2LC always consult a professional
electrical engineer who is qualified and trained to the local and national standards. If in doubt
about the operation or use of the FX
2N
-2LC please consult the nearest Mitsubishi Electric
distributor.
•
Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential
damage that may arise as a result of the installation or use of this equipment.
•
All examples and diagrams shown in this manual are intended only as an aid to understanding
the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual
use of the product based on these illustrative examples.
•
Owing to the very great variety in possible application of this equipment, you must satisfy
yourself as to its suitability for your specific application.
Manual number : JY992D85601
Manual revision : C
Date
: March 2007
JY992D85601C
Effective March 2007
Specifications are subject to
change without notice