FX

2N

-2LC SPECIAL FUNCTION BLOCK

USER’S GUIDE 

JY992D85601C

Cautions on Safety
(Make sure to read this paragraph before using the unit.)

Thoroughly read this manual, a separate USER’S MANUAL and all attached documents of the connected
programmable controller (hereafter referred to as "PLC") and other related units before starting installation, 
operation and inspection/maintenance of the temperature control block. Acquire the knowledge on 
equipment, the information on safety and all cautions before using the temperature control block.
In this instruction manual, cautions on safety are classified as "DANGER" or "CAUTION".

This symbol indicates that incorrect handling may generate a dangerous situation which may lead
to death or serious injury.

This symbol indicates that incorrect handling may generate a dangerous situation which may lead
to medium or minor injury or physical damage.

Even an item classified as "CAUTION" may lead to a severe result depending on the situation.
Each item describes important information. Make sure to observe each item marked with "DANGER" or
"CAUTION".
Carefully store the instruction manual offered together with the temperature control block so that the 
operator can refer to it at any time necessary. Make sure to deliver the instruction manual to the end user.

We appreciate it very much that you have purchased the temperature control block FX

2N

-2LC for Mitsubishi

programmable controller.
This manual describes handling of the MELSEC-F Series Temperature Control Block FX

2N

-2LC.

Thoroughly read this manual and other manuals of related products, and sufficiently understand the 
specifications before use.
Make sure to deliver this manual to the end user.

Brand and product names described by/in this manual are trademarks or registered trademark of the 
irrespective ownes.

Related Manuals

If necessary, obtain them from the dealer from which you have purchased the FX

2N

-2LC.

Manual name

Manual No.

Supplied with 

product or 

separately supplied

Description

FX

2N

-2LC 

USER’S MANUAL

JY992D85601

Additional Manual

Describes the specification, wiring, 
installation of FX

2N

-2LC.

FX

2N

 

HARDWARE MANUAL

JY992D66301 Supplied with product

Describes the specification, wiring 
and installation of FX

2N

 series PLC.

FX

2NC

 

HARDWARE MANUAL

JY992D76401 Supplied with product

Describes the specification, wiring 
and installation of FX

2NC

 series PLC.

FX

3U

 Series

HARDWARE MANUAL

JY997D18801 Supplied with product

Describes the specification, wiring 
and installation of FX

3U

 series PLC.

FX

3U

 Series

User’s Manual
- Hardware Edition

JY997D16501

Additional Manual

Describes the specification, wiring 
and installation of FX

3U

 series PLC.

FX SERIES 
PROGRAMMING 
MANUAL 

ΙΙ

JY992D88101

Additional Manual

Describes the instructions of FX

1S

/

FX

1N

/FX

2N

/FX

2NC

 series PLC.

FX

3U

/FX

3UC

 Series

Programming Manual
- Basic & Applied 
Instruction Edition

JY997D16601

Additional Manual

This manual explains the installations 
of FX

3U

/FX

3UC

 series PLC.

When you using the FX

2N

-2LC for the first time, a separate FX

2N

-2LC USER’S MANUAL is required.

Make sure to obtain the USER’S MANUAL from the dealer from which you have purchased the FX

2N

-

2LC, and safely use the FX

2N

-2LC.

1. Outline of Product

Cautions on design

Install a safety circuit outside the PLC so that the entire system conservatively operates even if
an abnormality occurs in the external power supply or a failure occurs in the PLC.
If the safety circuit is installed inside the PLC, malfunction and erroneous output may cause
accidents.
Make sure to construct an emergency stop circuit, protection circuit, interlock circuit to prevent
damage to a machine or instrument outside the PLC.

When the PLC or FX

2N

-2LC detects an abnormality such as a watch dog timer error or input

value error by the self-diagnosis circuit, and all outputs turn off. When an abnormality occurs in
the I/O control area which cannot be detected by the CPU in the PLC, output control may be
disabled.
Design external circuits and the structure so that the entire system conservatively operates in
such cases.

When a failure occurs in a relay, transistor, triac, etc. in the FX

2N

-2LC or output unit of PLC,

outputs may keep ON or OFF.
For output signals which may lead to severe accidents, design external circuits and the struc-
ture so that the entire system conservatively operates.

Caution on disposal

When disposing of the unit, treat it as industrial waste.

The temperature control block FX

2N

-2LC (hereafter referred to as "temperature control block" or "FX

2N

-2LC")

equipped with two temperature input points and two transistor (open collector) output points is a special
block to control outputs of temperature inputs from thermocouples and platinum resistance thermometer
bulbs by PID control.
Connect the FX

2N

-2LC to the FX

1N

/FX

2N

/FX

2NC

/FX

3U

 Series PLC.

1) As input sensors, two thermocouples, two platinum resistance thermometer bulbs or one thermocouple

and one platinum resistance thermometer bulb are available.

2) Data can be read and written using FROM/TO instructions when the FX

2N

-2LC is connected to the

FX

1N

/FX

2N

/FX

2NC

/FX

3U

 Series PLC.

(The FX

2N

-2LC performs arithmetic operation for PID control and output control. The PLC does not

have to perform such control.)

3) Disconnection of heaters can be detected by current detection.

4) The proportional band, the integral time and the derivative time can be easily set by auto tuning.

5) Channels are isolated from each other.

2. Outside Dimension

Extension 
cable

Mounting hole 2-

Φ

4.5

DIN rail mounting hook

DIN rail 
(width: 35 mm)
mounting groove

Connector for next 

step extension cable

4(0.16)

OUT2

2N

24V

OUT1

POWER

FX  -2LC

24

+

24

-

O

87(3.43)

55(2.17)

90(3.54)

Status indicator LED

80(3.15)

PT
B

PT
B

24
+

CO

M

24
-

OU

T1
OU

T2

CT

CT

FG

PT
A

TC
-

TC
+

PT
B

PT
B

CT

CT

FG

PT
A

TC
-

TC
+

CH1

CH2

Terminal block

Unit  : mm (inch)

Mass: 0.3kg

Terminal screws M3 (0.12)

3. Installation Method

Cautions on installation

Use the unit in the environment for the general specifications described in the manual.
Never use the unit in a place with dust, soot, conductive dust, corrosive gas or flammable gas,
a place exposed to high temperature, dew condensation or rain and wind or a place exposed
to vibration or impact.
If the unit is used in such a place, electrical shock, fire, malfunction, damage in the product or
deterioration of the product may be caused.

Never drop cutting chips or electric wire chips into the ventilation window of the FX

2N

-2LC

while drilling screw holes or wiring cables.
Such chips may cause fire, failure or malfunction.

After finishing installation, remove a dust preventing sheet adhered on the ventilation window
of the PLC and the FX

2N

-2LC.

If the sheet remains attached, fire, failure or malfunction may be caused.

Securely connect connection cables such as extension cables and memory cassettes to specified
connectors.
Imperfect contact may cause malfunction.

The FX

2N

-2LC can be installed on the right side of an FX

1N

/FX

2N

/FX

2NC

/FX

3U

 Series PLC main unit or

extension unit.
The FX

2N

-2LC can be attached with a DIN rail DIN46277 (width: 35 mm) or directly attached to a panel

surface with screws (M4).

3.1 Installation on DIN rail

Align the upper side of the DIN rail mounting groove of the FX

2N

-2LC with a DIN rail DIN46277 (width: 35

mm) (

), and push it on the DIN rail.(

)

When removing the FX

2N

-2LC, pull out downward the DIN rail mounting hook.(

), and remove from DIN

rail.(

)

3.2 Direct installation on panel surface

Screw-tighten the FX

2N

-2LC with M4 screws to a panel surface using two (upper and lower) mounting

holes provided on the left side of the FX

2N

-2LC.

Assure the interval of 1 to 2 mm between a unit or block installed on the left side of the FX

2N

-2LC.

„

ƒ

‚



When attached to DIN rail

When removed from DIN rail

4. Connection to PLC Main Unit

Connect the FX

2N

-2LC to the PLC main unit with an extension cable.

FX

2N

-2LC units are treated as special units of the PLC, and the special unit No. 0 to 7 is automatically

assigned to each FX

2N

-2LC unit from the one nearest to the PLC main unit. (These unit Nos. are used in

FROM/TO instructions.)
One FX

2N

-2LC unit occupies eight I/O points in the PLC main unit.

For the details of I/O assignment in the PLC, refer to the manual of the PLC main unit.

Please check power supply specifications to decide the number of FX

2N

-2LC units that can be connected 

to the FX

1N

/FX

2N

/FX

2NC

/FX

3U

 extension unit and PLC.

To connect the FX

2N

-2LC unit to the FX

2NC

 Series PLC, the interface FX

2NC

-CNV-IF is required.

For extension, an extension cable FX

0N

-65EC (650 mm) and the FX

2N

-CNV-BC sold separately are 

required. Only one FX

0N

-65EC can be used in one system.

(  ) indicates the I/O No.

FX

2N

-32ER

FX

2N

-4AD

FX

2N

-2LC

FX

2N

-2LC

FX

2N

-32MR

(X000 to X017)

FX

2N

-4AD

FX

2N

-2LC

FX

2N

-2LC

(Y000 to Y017)

Special block

No. 0

Special block

No. 1

(Y020 to Y037)

7

2

4 5 6

1

3

0

16

11

15

14

17

10

12 13

14

17

15

10

12 13

7

2

4 5 6

1

3

0

16

11

OUT

IN

L

X13

X15

X10

X14

X16

24+

N

COM

X4

X7

Y4

Y5

Y6

COM3

Y10

Y11

Y12

Y13

Y1

Y2

Y3

Y14

Y15

X3

X2

X1

POWER

BATT.V

RUN

CPU.E

PROG.E

POWER

A/D

24V

X0

X5

7

2

4

5

6

1

3

0

7

2

4

5

6

1

3

0

OUT

IN

L

X1

X3

X5

X7

X6

X0

X2

X4

X6

24+

N

COM

X4

X7

COM4

COM2

Y4

Y5

Y6

Y7

COM3

Y0

Y1

Y2

Y3

COM1

Y0

Y1

Y2

Y3

Y4

Y5

Y6

Y7

X3

X2

X1

POWER

0

1

2

3

4

5

6

7

7

6

5

4

3

2

1

0

POWER

OUT1

24V

OUT2

POWER

OUT1

24V

OUT2

FX

2N

-32MR

FX

2N

-32ER

(X020 to X037)

Special block

No.2

Содержание FX2N-2LC

Страница 1: ...separately supplied Description FX2N 2LC USER S MANUAL JY992D85601 Additional Manual Describes the specification wiring installation of FX2N 2LC FX2N HARDWARE MANUAL JY992D66301 Supplied with product Describes the specification wiring and installation of FX2N series PLC FX2NC HARDWARE MANUAL JY992D76401 Supplied with product Describes the specification wiring and installation of FX2NC series PLC F...

Страница 2: ... block to control outputs of temperature inputs from thermocouples and platinum resistance thermometer bulbs by PID control Connect the FX2N 2LC to the FX1N FX2N FX2NC FX3U Series PLC 1 As input sensors two thermocouples two platinum resistance thermometer bulbs or one thermocouple and one platinum resistance thermometer bulb are available 2 Data can be read and written using FROM TO instructions ...

Страница 3: ... rail Align the upper side of the DIN rail mounting groove of the FX2N 2LC with a DIN rail DIN46277 width 35 mm and push it on the DIN rail When removing the FX2N 2LC pull out downward the DIN rail mounting hook and remove from DIN rail 3 2 Direct installation on panel surface Screw tighten the FX2N 2LC with M4 screws to a panel surface using two upper and lower mounting holes provided on the left...

Страница 4: ...ints in total including input points and output points PTA FG PTB TC PTB TC FX2N 2LC Resistance thermometer bulb Shielded cable 24 24 OUT1 COM OUT2 CT CT PTA FG PTB TC PTB TC CT CT PTA FG PTB TC PTB TC SSR SSR FX2N 2LC DC24V CT CT Heater Heater Shielded cable Thermocouple AC power supply Shielded cable Thermocouple 1 When a temperature sensor is a thermocouple When a temperature sensor is a resist...

Страница 5: ...3 C 5 C 0 3 of range span 1 digit Ambient temperature 0 C to 55 C 0 7 of range span 1 digit However 0 to 399 C 0 to 799 F in B inputs as well as 0 to 32 F in PLII and WRe5 26 inputs are outside precision guarantee range Cold contact tempera ture compensation error Within 1 0 C However within 2 0 C while input value is 150 to 100 C within 3 0 C while input value is 200 to 150 C Resolution 0 1 C 0 1...

Страница 6: ... transistor output Rated load voltage 5 to 24V DC Maximum load voltage 30V DC or less Maximum load current 100mA Leak current in OFF status 0 1 mA or less Maximum voltage drop in ON status 2 5V maximum or 1 0V typical at 100 mA Control output cycle 30 seconds Variable within range from 1 to 100 seconds Guidelines for the safety of the user and protection of the FX2N 2LC This manual has been writte...

Страница 7: ...nput points and two transistor open collector output points is a special block to control outputs of temperature inputs from thermocouples and platinum resistance thermometer bulbs by PID control Connect the FX2N 2LC to the FX1N FX2N FX2NC FX3U Series PLC 1 As input sensors two thermocouples two platinum resistance thermometer bulbs or one thermocouple and one platinum resistance thermometer bulb ...

Страница 8: ... S E T B N PLII WRe5 26 U L JIS C 1602 1995 Resistance ther mometer bulb 3 wire Pt100 JIS C 1604 1997 JPt100 JIS C 1604 1981 Measurement precision Ambient temperature 23 C 5 C 0 3 of range span 1 digit Ambient temperature 0 C to 55 C 0 7 of range span 1 digit However 0 to 399 C 0 to 799 F in B inputs as well as 0 to 32 F in PLII and WRe5 26 inputs are outside precision guarantee range Cold contact...

Отзывы: