Diagnostics 7
7-1
7.
Diagnostics
7.1
Preliminary Checks
1) Check POWER and DC LED. If this is OFF, please see section 7.2.
2) Check that the slave address is the same at the 32NT-DP (BFM #27) and the setting value
of the Profibus-DP master configuration tool. If the slave address is not the same, change
this address to match at both sides.
3) Check that the parameters of 32NT-DP are set in the DP-master.
4) Check whether the network wiring and /or extension cables are properly connected on the
32NT-DP.
5) Check that the system configuration rules have not been exceeded (i.e. the number of
blocks does not exceed 8 and the total system I/O is equal or less than 128
*1
I/O).
*1 FX
0N
, FX
1N
Series PLC is 128 I/O points.
FX
2N
, FX
2NC
Series PLC is 256 I/O points.
6) Put the PLC into RUN.
FX0N-32NT-DP Profibus-DP Interface Unit