INVERTER SETTING
4.1 Parameter List
The following parameters are used for the plug-in option (FR-A7NC).
Set the values according to need.
*1
Parameters which can be displayed when the plug-in option (FR-A7NC) is mounted.
*2
The setting is reflected after inverter reset or at the next power-on.
*3
"L.ERR" of the LED flickers if the setting is changed. If the inverter is reset, the setting is reflected and LED turns off.
*4
The setting range differs according to the inverter.
For details, refer to
page 58
*5
These parameters can be set for the FR-A700 series only.
*6
Pr.544 CC-Link extended setting
= "100, 112, 114, 118" are available with the FR-A700 series-NA/EC version inverter only.
Parameter
Number
Name
Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
79
Operation mode selection
0 to 4, 6, 7
1
0
313
DO0 output selection
0 to 8, 10 to 20, 25 to 28, 30 to 36, 39,
41 to 47, 64, 70, 85 to 99, 100 to 108,
110 to 116, 120, 125 to 128, 130 to 136,
139, 141 to 147, 164, 170, 185 to 199
1
9999
314
DO1 output selection
315
DO2 output selection
338
Communication operation command source
0, 1
1
0
339
Communication speed command source
0, 1, 2
1
0
340
Communication startup mode selection
0, 1, 2, 10, 12
1
0
342
Communication EEPROM write selection
0, 1
1
0
349
Communication reset selection
0, 1
1
0
500
Communication error recognition waiting time
0 to 999.8s
0.1s
0
501
Communication error occurrence count display
0
1
0
502
Communication error time stop mode selection
0 to 3
1
0
541
Frequency command sign selection (CC-Link)
0, 1
1
0
542
Communication station number (CC-Link)
1 to 64
1
1
543
Baud rate selection (CC-Link)
0 to 4
1
0
544
CC-Link extended setting
0, 1, 12, 14, 18, 100, 112, 114, 118
1
0
550
NET mode control source selection
0, 1, 9999
1
9999
804
Torque command source selection
0, 1, 3, 4, 5, 6
1
0