4
.
Product Specifications
For detail specifications which do not appear in the specification comparison charts contained herein, see the user's
manual supplied with the MELSEC-Q Series Module you use. Also, check that the specifications of the
connected devices meet the specifications of the MELSEC-Q Series Module.
Conversion Adapter
Model
Before replacement
Module Model
No. of
output
points
After replacement
MELSEC-Q Series
Module Model
Conversion
Adapter
Weight (g)
No. of
modules
ERNT-1Y2Q904914
JAMSC-B2904 16
QY18A
2
280
JAMSC-B2914 16
2
TB1
MEMOCON-SC
GL Series
(2000 Series I/O)
Module
Internal circui t diagram of
ERNT-1Y2Q904914
TB1
TB2 TB3
TB4 TB5
TB6 TB7
TB8 TB9
TB10 TB11
TB12 TB13
TB14 TB15
TB16 TB17
TB18 TB19
TB20 TB21
TB22 TB23
TB24 TB25
TB26 TB27
TB28 TB29
TB30 TB31
TB32 TB33
TB34 TB35
TB36 TB37
TB38
MELSEC-Q
Series
Module
(Slot No.)
MELSEC-Q
Series
Module
(Slot No. +1)
TB1
TB2 TB3
TB4 TB5
TB6 TB7
TB8 TB9
TB10 TB11
TB12 TB13
TB14 TB15
TB16 TB17
TB18
TB1
TB2 TB3
TB4 TB5
TB6 TB7
TB8 TB9
TB10 TB11
TB12 TB13
TB14 TB15
TB16 TB17
TB18
L
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
TB10
TB11
TB12
TB13
TB14
TB15
TB16
TB17
TB18
TB19
TB20
TB21
TB22
TB23
TB24
TB25
TB26
TB27
TB28
TB29
TB30
TB31
TB32
TB33
TB34
TB35
TB36
TB37
TB38
100 to 240VAC
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
Y00
TB9
TB10
TB11
TB12
TB13
TB14
TB15
TB16
TB17 Open
TB18 Open
Y01
Y02
Y03
Y04
Y05
Y06
Y07
Output
1
Output
2
Output
3
Output
4
Output
5
Output
6
Output
7
Output
8
Output
9
Output
10
Output
11
Output
12
Output
13
Output
14
Output
15
Output
16
TB2
TB3
TB4
TB5
TB6
TB7
TB8
Y00
TB9
TB10
TB11
TB12
TB13
TB14
TB15
TB16
TB17 Open
TB18 Open
Y01
Y02
Y03
Y04
Y05
Y06
Y07
Open
Open
24V
0V
FG
FG
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
FG terminal
is not requierd.
Terminal
No.
Signal
Name
Signal
Name
Terminal
No.
Signal
Name
TB1
*1
*2
External power
supply is not
requierd.
Do not use
110VDC.
Terminal
No.
Precautions for wiring
External power supply connected to the terminal numbers TB35 and TB36 on the
MEMOCON-SC GL Series (2000 Series I/O)-side terminal block becomes unnecessary.
However, that leaving the terminals connected will not cause a problem because the wire is
not connected inside the Conversion Adapter.
FG terminal connected to the terminal numbers TB37 and TB38 on the MEMOCON-SC GL
Series (2000 Series I/O)-side terminal block becomes unnecessary. However, that leaving
the terminals connected will not cause a problem because the wire is not connected inside
the Conversion Adapter.
< Specification Comparison >
Model
Specifications
MEMOCON-SC GL Series
(2000 Series I/O)
MELSEC-Q Series
JAMSC-B2904 JAMSC-B2914
QY18A
No. of output points
16 points
16 points
8 points
Rated switching
voltage/current
DC110V, 0.3A
AC220V, 0.5A
DC110V, 0.3A
AC220V, 0.5A
24VDC, 2A (resistive load)/point
240VAC, 2A (cos
φ
=1)/point
8A/unit
Minimum switching load
5VDC, 1mA
24VDC, 10mA
5VDC, 1mA
Maximum switching load
110VDC 0.5A
220VAC 15A
110VDC 0.5A
220VAC 15A
125VDC
264VAC
Response
time
OFF to ON
6ms or less
6ms or less
10ms or less
ON to OFF
4ms or less
4ms or less
12ms or less
Surge suppressor
None
None
None
Fuse None
None
None
Isolation method
Relay isolation
Relay isolation
Relay isolation
Common terminal arrangement
All points independent
All points independent
All points independent
External connection system
38-point
terminal block
38-point
terminal block
18-point
terminal block
Make sure the
section of the above table meets the specification of the machines and equipment connected to the
MELSEC-Q Series Module.
5
.
Mounting and Installation
5.1
Handling Precautions
(1) Before attempting to install the Unit or carry out the necessary wiring, make certain that the
external power supply, used in the system, is shut off on all three phases. Failure to do so may
result in electric shock or damage to the product.
(2) Do not touch live terminals. There is a danger of electric shock or malfunction.
(3) Do not modify the Conversion Adapter or take it apart. Doing so will cause failure, malfunction,
personal injury, or fire.
(4) Do not touch the energized part of the Conversion Adaptor directly. Contact will cause
malfunction or failure in the system.
(5) Fasten the Conversion Adapter and the Mounting Bracket securely with retaining screws, and
tighten the screws by applying torque within specified limits. Loose screws can lead to the
dropping of the Conversion Adapter, or Mounting Bracket, possibly causing breakage thereof.
Excessive tightness of the screws can lead to breakage of the screws, Converter Adaptor,
Mounting Bracket, or MELSEC-Q Series Module, possibly causing the dropping, shorting, and
malfunction thereof.
(6) Use care to prevent foreign materials including cuttings and wiring debris from entering the
Conversion Adapter or the MELSEC-Q Series Module. These will be cause for fire, failure or
malfunction.
(7) Do not drop the Conversion Adapter and Mounting Bracket or do not give a strong impact to it.
This will cause damage.
5.2
Use Precautions
Item Use
Precautions
Depth
dimension
The depth dimension required for installation is 141.6mm. Check the installation
condition.
MELSEC-Q Series
Renewal Tool
+
MEMOCON-SC GL Series
(2000 Series I/O)
UP
31.6mm
Unit:mm
110
141.6
*
The each depth dimension is measured from the panel surface.
MEMOCON-SC GL Series (2000 Series I/O): Base Unit + Input/output
Terminal block, MELSEC-Q Renewal Tool: Base Unit + Input/output
Conversion A Terminal block
Interference
of the terminal
block
When mounting either of the following Conversion Adapters on the right side of the
Conversion Adapter, leave one slot open between them so that the Conversion
Adapter does not interfere with the terminal block of the existing module.
Conversion Adapters : ERNT-1Y2Q500, ERNT-1JQ33S
Conversion Adapter
Terminal block of the
MEMOCON-SC GL Series
(2000 Series I/O)
The Conversion Adapter interferes with the terminal block
of the MEMOCON-SC GL Series (2000 Series I/O).
Leave one slot open.
Input / Output
Module
Conversion Adapter
・
ERNT-1Y2Q500
・
ERNT-1JQ33S
5.3
Installation Environment
The installation environment is the same as MELSEC-Q Series CPU Module to use. Refer to the user's
manual of the MELSEC-Q Series CPU Module to be used.
6
.
Part Names and Installation Method
Mounting Bracket (Conversion Adapter accessory)
Mounting Bracket
M3.5×6(Conversion Adapter accessory)
Conversion Adapter installation screw
M3×30
Conversion Adapter
bottom installation
screw
M3×20
Conversion Adapter
Anchor Base
Conversion Adapter
Conversion Adapter Anchor Base installation screw
M4×8(Conversion Adapter Anchor Base accessory)
Terminal block
installation crew(M3)
MELSEC-Q Series Module
Precaution
3
1
2
2
2
2
4
4
4
4
5
5
6
6
MEMOCON-SC
GL Series
(2000 Series I/O)
Terminal block
6.1
Installation Method
①
Secure the Conversion Adapter Anchor Base to the Base Adapter or control panel using the
Conversion Adapter Anchor Base installation screws (M4
8) provided as an accessory. (Two
end locations)
②
Remove the terminal block attached with the MELSEC-Q Series Module after loosening the
terminal block installation screws (2 places top and bottom).
Secure the Mounting Bracket to the Q Series Module using the Mounting Bracket fixing screws
[M3.5
6 (Conversion Adapter accessory); four upper/lower locations].
③
Mount the Conversion Adapter onto the Mounting Bracket.
④
Secure the Conversion Adapter using the Conversion Adapter installation screws (M3
30; 4
locations).
Precaution
Before tightening the installation screws, check that the Conversion Adapter has been
securely installed on the MELSEC-Q Series Module. Tightening the screws in floating-off state
or tilting state will damage the Conversion Adapter installation screws and the Mounting
Bracket.
⑤
Secure the Conversion Adapter using the Conversion Adapter bottom installation screw (M3
20; 2 location).
⑥
Secure the terminal block of the MEMOCON-SC GL Series (2000 Series I/O) to the Conversion
Adapter with the terminal block installation screws (M3; two upper/lower locations).
6.2
Tightening Torque
Tighten the installation screws to the specified torque below. An inappropriate tightening torque could
cause the product to fall or result in a short circuit, product failure or malfunction.
Screw Location
Tightening Torque Range
Conversion Adapter Anchor Base installation screw (M4×8)
1.39 to 1.89N
・
m
Mounting Bracket fixing screw (M3.5×6)
0.68 to 0.92N
・
m
Conversion Adapter installation screw (M3×30)
0.43 to 0.57N
・
m
Conversion Adapter bottom installation screw (M3×20)
Terminal block installation screw (M3)
0.5 to 0.6N
・
m
7
.
External Dimensions
Unit
:
mm
20
4
41
.9
55.2
18.9
92
53.5
Conversion Adapter
Mounting Bracket
Duplication Prohibited
This manual may not be reproduced in any form, in part or in whole, without written permission from
Mitsubishi Electric Engineering Company Limited.
©2016 MITSUBISHI ELECTRIC ENGINEERING COMPANY LIMITED ALL RIGHTS RESERVED
MELSEC is a registered trademark of Mitsubishi Electric Corporation.
MEMOCON is a registered trademark or a trademark of YASKAWA Electric Corporation.
Product Warranty Details
Please confirm the following product warranty details prior to product use.
Gratis Warranty Terms and Gratis Warranty Range
If any fault or defect (hereinafter referred to as “Failure”) attributable to Mitsubishi Electric Engineering
Company Limited (hereinafter referred to as “MEE”) should occur within the gratis warranty period, MEE
shall repair the product free of charge via the distributor from whom you made your purchase.
Gratis Warranty Period
The gratis warranty period of this product shall be one (1) year from the date of purchase or delivery
to the designated place.
Note that after manufacture and shipment from MEE, the maximum distribution period shall be six
(6) months, and the gratis warranty period after manufacturing shall be limited to eighteen (18)
months.
In addition, the gratis warranty period for repaired products shall not exceed the gratis warranty
period established prior to repair.
Gratis Warranty Range
The gratis warranty range shall be limited to normal use based on the usage conditions, methods
and environment, etc., defined by the terms and precautions, etc., given in the instruction manual,
user’s manual and caution labels on the product.
Warranty Period after Discontinuation of Production
(1) MEE shall offer product repair services (fee applied) for seven (7) years after production of the
product has been discontinued. Discontinuation of production shall be reported via distributors.
(2) Product supply (including spare parts) is not possible after production has been discontinued.
Exclusion of Opportunity Loss and Secondary Loss from Warranty
Liability
Regardless of the gratis warranty period, MEE shall not be liable for compensation for damages arising
from causes not attributable to MEE, opportunity losses or lost profits incurred by the user due to Failures
of MEE products, damages or secondary damages arising from special circumstances, whether foreseen
or unforeseen by MEE, compensation for accidents, compensation for damages to products other than
MEE products, or compensation for other work carried out by the user.
Changes in Product Specifications
The specifications given in the catalogs, manuals and technical documents are subject to change without
notice.
This document is a new publication, effective November 2016. Specifications are subject to change
without notice.
Developed November 2016
50CM-D180259-B
MELSEC-Q Series terminal block installation screw
(Secure it in two places, top and bottom.)
*1
*2