16
Control modes
Control details
1-1. Thermo regulating function (Function to prevent restarting for 3 minutes)
Setting the Dry thermo by the thermo regulating signal and the room
temperature (TH1).
Dry thermo ON Room temperature
]
desired tempe 2
°
F
Dry thermo OFF Room temperature
[
desired temperature
1-2. Frozen prevention control
No control function
Indoor fan operation controlled depends on the compressor conditions.
3. Drain pump
1. Thermo regulating
function
Remarks
Room
temperature
3 min. passed since starting operation
Thermo regulating signal Room temperature (T1)
Dry thermo
ON
time (min)
Dry thermo
OFF
time (min)
Less than 64
°
F
Over 64
°
F
ON
OFF
T1
]
83
°
F
83
°
F > T1
]
79
°
F
79
°
F > T1
]
75
°
F
75
°
F > T1
Unconditional
9
3
7
3
5
3
3
3
10
3
Dry thermo OFF
2. Fan
Note: Remote controller setting is not acceptable.
Dry thermo
Fan speed notch
ON
OFF
[Low]
Stop
4. Vane
(up/ down vane change)
Same control as COOL operation
Same control as COOL operation
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK
DAY
MONITOR/SET
CLOCK
ON/OFF
˚F˚C
˚F˚C
ERROR CODE
AFTER
TIMER
TIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTER
FUNCTION
ONLY1Hr.
WEEKLY
SIMPLE
AUTO OFF
8-2. DRY OPERATION
<How to operate>
1
Press POWER ON/OFF button.
2
Press the operation MODE button to display DRY.
3
Press the TEMP. button to set the desired temperature.
NOTE: The set temperature changes 2°F when the or button is
pressed one time. Dry 67 to 87°F.
OC340A--1.qxp 06.7.25 0:39 PM Page 16