48
-
(2)
Memory flap
While the flap is operating if the AIRFLOW button is pushed once, it stops swinging at an angle.
As this angle is memorized in the microcomputer, the flap will be automatically set to the angle when next operation is started.
¡
Recommendable stopping angle of the flap
Horizontal
blowing
COOL•DRY
Slant forward
blowing
HEAT
¡
SKM model
(3)
Swing flap
Flap moves in upward and downward directions continuously.
¡
STM model
4.6 Comfortable timer setting
If the timer is set at ON when the operation select switch is set at the cooling or heating, or the cooling or heating in auto mode
operation is selected, the comfortable timer starts and determines the starting time of next operation based on the initial value of
15 minutes and the relationship between the room temperature at the setting time (temperature of room temperature sensor) and
the setting temperature. (Max. 60 minutes)
COOL•DRY
HEAT
Horizontal
blowing
Slant forward
blowing
Capacity control is within the range shown above. If demand capacity of the indoor units exceeds the maximum capacity of the
outdoor unit, the demand capacity will be proportionally distributed.
(b) Outdoor unit speed control
4.7 Cooling operation
(1)
Summary
(a) Capacity control
Model
Capacity
SCM40ZF-S
1.9 ~ 4.9 kW
SCM45ZF-S
0.7 ~ 5.6 kW
SCM48ZF-S
1.1 ~ 6.7 kW
SCM60ZF-S
1.4 ~ 6.9 kW
SCM80ZF-S
1.0 ~ 9.3 kW
0 rps
A rps or less
More than A rps, but B rps or less
More than B rps
Decision speed
0 rps
A rps
A rps to B rps
B rps
35
85
Indoor unit command total speed value
Model
A
B
40
10
126
45
10
120
48
10
95
60
10
95
80
¡
Values of A, B
Note (1) The indoor unit command total speed value is the total of the values from each unit in item (2).
(2)
Mode switching
Within the selected mode, the unit operates using the values shown below which were obtained by multiplying a conversion
coefficient to the indoor unit command speed.
(a) SCM40ZF-S, 45ZF-S
◆
SKM model
Model (Indoor)
Operation Mode
Automatic
High
Medium
Low
Hi power
Econo
12 ~ 45
12 ~ 45
12 ~ 36
12 ~ 24
45
12 ~ 36
12 ~ 46
12 ~ 46
12 ~ 39
12 ~ 25
46
12 ~ 39
12 ~ 55
12 ~ 55
12 ~ 42
12 ~ 27
48
12 ~ 42
12 ~ 66
12 ~ 66
12 ~ 43
12 ~ 28
52
12 ~ 43
22
12 ~ 43
12 ~ 43
12 ~ 34
12 ~ 24
43
12 ~ 34
20
25
28
35
(rps)