Post-installation Checks
When you have finished installation work, perform trial operation following the installation manual of the
Lossnay unit, and check for air leakage or abnormal vibration from the joint parts of the Lossnay unit and
silencer box. Inspect the following items according to the following Check list before turning the power on.
Make sure to correct any malfunctions that are found. (The functions is not being demonstrated or safety can not
be ensured)
Check Item
Remedy for Malfunction
Check
Installation of
the product
Are the Lossnay, silencer box and the duct piping installed on the indoor side
of the insulation layer/airtight layer?
Install them on the indoor side of
the insulation layer/airtight layer.
Are the Lossnay and silencer box installed within ±1° of the horizontal?
Install within ±1° of the horizontal
Are the joint parts of the Lossnay unit and silencer box sufficiently caulked?
(Insufficient caulking may cause water leakage, sound leakage, and air
leakage.)
Caulk the joint parts sufficiently.
Duct
connections
Is the outdoor side duct installed tilted 1/30 or more towards the outside to
prevent rain water from entering?
Install the duct tilted
Are there metal chips or other foreign matter (for example paper or vinyl)
inside the product or the ducts?
Remove any foreign matter.
Are ducts insulated down to their base?
* See
3.4.2 Insulating the ducts
at
3. Installation Procedure.
Insulate
Are ducts connected to the product? (Air leakage causes dew condensation.) Securely connect the ducts
Note
-
When discharging the air from a bathroom, use ducts made of
a material that does not allow water to leak.
-
When using PVC ducts or metal ducts for the SA side ducts,
make sure to connect ducts having silencer before the grill.
-
The duct for exhaust from the bathroom and the pipe guide
should be sealed with caulking material.
-
When using calking material, take care to prevent it from
oozing from the ducts. (Otherwise, it could cause aluminum
tape to peel off.)
-
Before connecting the ducts, make sure that there are no metal
chips or other foreign matter (For example paper or vinyl)
inside the ducts or inside the product.
■ P-250/350SB-E
■ P-500SB-E
Duct Inner diameter φ125(P-250SB-E),
φ150(P-350SB-E) (Field supply)
Caulking material
(Field supply)
Aluminum tape
(Field supply)
Pipe guide
(Product)
Duct Inner diameter φ180 or φ160
(Field supply)
Caulking material
(Field supply)
Aluminum tape
(Field supply)
Pipe guide
(Product)
3.4.2 Insulating the ducts
CAUTION
To prevent dew condensation, insulate the ducts and pipe
guide. (glass wool 25 mm or equivalent)
Make sure to insulate up to the base of pipe guide.
When the Lossnay is anticipated to be stopped for a long
time, insulate the RA (Return Air) side ducts also. (i.e. not
operated for 24 hours).
Indoor humidity can cause condensation because exposed
parts can become cold in winter.
Note
-
Attach insulation so that the aluminum tape is not exposed.
Insulating (Field supply)