How to set up Capacity.
A set-up for automatic recognition and manual input of capacity are possible by this set-up.
After the automatic recognition
,
by setting HoLd
,
automatic recognition is stopped and the capacity
recognized automatically is fixed. You can also manually input.
Control Set-up Menu END is displayed by pressing
SET CONT.
Key for
2
seconds in Operation Mode.
Then
,
the following set-ups are possible.
5.9 Control Set-up Menu 5 (Set-up of Capacity)
Choose
5
from Control Set-up Menu .
(Screen on the right is displayed)
Set up automatic recognition of capacity or
manual setting of capacity.
Set up capacity for every circuit.
Capacity
Auto/HoLd
Capacity
(
Manual Input
)
Note 1. This device recognizes capacity automatically by the following method.
At the time the capacitor is connected, the changed portion in the reactive power, before and after capacitor
connecting, is stored as Capacity. (Can be turned on either automatically or manually.)
Note 1. This set-up is skipped when “Auto” is selected in “Capacity Auto/HoLd”.
Note 2. VAR-6A is the circuit 1 to 6, and VAR-12A is the circuit 1 to 12.
Note 3. The flickering digit can be changed.
Control Set-up Menu
Choose whether to complete the set-up refer
to page
24
and
25
about how to finish the
set-up or to continue other set-up.
ENTER
DISPLAY
ENTER
DISPLAY
⁝
System
Auto (automatic
recognition)
HoLd (manual
setting)
automatic
recognition every
capacitor connection
manual setting
in this set-up
Untill the next
capacitor
connection.
Untill the next
set-up.
setting method
Hold period
Control Set-up Menu
ENTER
DISPLAY
ENTER
ENTER
DISPLAY
* The present setting value is displayed.
* A changed setting value is displayed.
0
9
0
9
The capacity is stored in non-volatile memory and will not be cleared even in the
event of power failure.
Key
+
−
Key
+
−
+
−
+
−
Key
+
−
Key
+
−
NOTE
Furthermore
,
Control Set-up Menu
5
is selected by pressing Key or Key.
+
−