32
33
OCH684
11-4. TROUBLE CRITERION OF MAIN PARTS
Parts name
Figure
Check method and criterion
Outdoor fan motor
R.V. coil (21S4)
Expansion valve coil
(LEV)
Measure the resistance between terminals with a tester.
(Temperature:
−
10 to 40°C)
WH - BK
BK - RD
RD - WH
Normal
Measure the resistance between terminals with a tester.
(Temperature :
−
10 to 40°C)
Normal
Measure the resistance with a tester.
Refer to “11-6. Test point diagram and voltage”, 11-6-1. (M25/35/50) or
11-6-2. (M60/71) “Inverter P.C. board”, for the chart of thermistor.
Color of the lead wire
Discharge temperature
thermistor (RT62)
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
Refer to “11-6. Test point diagram and voltage”, 11-6-1. (M25/35/50) or
11-6-2. (M60/71) “Inverter P.C. board”, for the chart of thermistor.
Defrost thermistor (RT61)
Fin temperature
thermistor (RT64)
32 to 43
Ω
Measure the resistance between terminals with a tester.
(Temperature:
−
10 to 40°C)
Compressor
U-V
U-W
V-W
Normal
W
U
V
WH
RD BK
W
U
V
WH
RD BK
Ambient temperature
thermistor (RT65)
Outdoor heat exchanger
temperature thermistor(RT68)
SUZ-M25
1.59 to 2.16Ω
SUZ-M35
1.60 to 2.17 Ω
1.41 to 2.00 k
Ω
SUZ-M50/60
0.82 to 1.11 Ω
SUZ-M71
0.87 to 1.18 Ω
SUZ-M25/35
SUZ-M50
15 to 20
Ω
LEV
WH
RD
YE
OG
BU
Measure the resistance with a tester.
(Temperature :
−
10 to 40°C)
RD - OG
RD - WH
RD - BU
RD - YE
Normal
37 to 54
Ω
Color of the lead wire
SUZ-M60/71
25 to 34
Ω
1.17 to 1.66 k
Ω
SUZ-M25/35/50
SUZ-M60/71
SUZ-M25VA.TH
SUZ-M35VA.TH
SUZ-M50VA.TH
SUZ-M25VA-ET.TH
SUZ-M35VA-ET.TH
SUZ-M50VA-ET.TH
SUZ-M60VA.TH SUZ-M71VA.TH
SUZ-M60VA-ET.TH SUZ-M71VA-ET.TH